Measurement & Size Codes for Stairs, Railings, Landings Stair, railing, guardrail, handrail, landing & platform building design & build specifications: summaries of stair and railing code & design specifications quoted from model building codes.
For each stair specification & code citation we include links to in-depth articles providing more details.
This article series lists all major building code specifications for stairs, railings, landings, and guardrails - information useful for constructing or inspecting indoor or outdoor stairs, railings, landings, & treads, and for evaluating stairways and railings for safety and proper construction.
We compare stair and railing code requirements for various model, national, state and local building codes and we include explicit text & specifications from those building codes.
Page top photo: our inspection client at unsafe angled, concrete exterior stairs with deteriorated, sloped stair tread edges or nosings.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Here we illustrate and summarize typical building code requirements for stairs, railings, landings, and guardrails. We also include references to key building codes that provide more detailed specifications for stair, landing, and railing safety.
Because more people are injured by trips and falls than other hazards, experts have looked closely at the specifications for stairs, steps, and rails to reduce the falling hazards.
This article has been adapted from specific stair and railing specifications that are similar among codes and countries (but not identical). -- IBC, IRC, BOCA, Kingston NY Stair Code, New York State Residential Building Code for Stairs (included here), Florida, Pennsylvania, New Jersey, & other sources.
In-depth stair design articles listed at the ARTICLE INDEX the bottom of this article provide detailed descriptions of each stair feature, building codes, photographs and sketches of defects and requirements. Text comparing key provisions of several building code sections on stairs and rails is given at the end of this document.
We provide sketches and photographs of stair, railing, landing, and construction details and hazards
Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
A device that has a series of steps between 50 and 70 degrees (0.87 and 1.22 rad) from horizontal, usually attached to a center support rail in an alternating manner so that the user does not have both feet on the same level at the same time. - IRC R-202 - [14a]
1009.10 Alternating tread devices.
Alternating tread devices are limited to an element of a means of egress in buildings of Groups F, H and S from a mezzanine not more than 250 square feet (23 m2) in area and which serves not more than five occupants;
in buildings of Group I-3 from a guard tower, observation station or control room not more than 250 square feet (23 m2) in area and for access to unoccupied roofs.
Shown above: alternating tread stairs used to access a rooftop utility area, Guanajuato, Mexico. Courtesy D.P. & L.M.
Stairway handrail & stair balusters & guard details are in this sketch.
See GUARDRAILS on BALCONIES & LANDINGS for details. A summary is below.
Balusters (vertical posts comprising the barrier in guards and railings)
Hand-railing heights are given:
Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Details about guardrail or railing balusters are at
Building exits, particularly in an emergency, are likely to be a source of additional injuries or worse if they are not properly constructed.
Where a stairway is generally not used and falls into abandonment, such as a "second means of egress" that is not normally accessed, serious trip hazards often develop.
The exit stair shown here, from Real de Catorce, would be a disasater in an emergency.
SECTION 1007 ACCESSIBLE MEANS OF EGRESS
1007.1 Accessible means of egress required.
Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress.
Where more than one means of egress is required by Section 1014.1 or 1018.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress.
Exceptions:
1. Accessible means of egress are not required in alterations to existing buildings.
2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3 or 1007.4.
3. In assembly spaces with sloped floors, one accessible means of egress is required from a space where the common path of travel of the accessible route for access to the wheelchair spaces meets the requirements in Section 1024.8.
1007.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components:
1. Accessible routes complying with Section 1104.
2. Stairways within exit enclosures complying with Sections 1007.3 and 1019.1.
3. Elevators complying with Section 1007.4.
4. Platform lifts complying with Section 1007.5.
5. Horizontal exits.
6. Smoke barriers.
Exceptions:
1. Where the exit discharge is not accessible, an exterior area for assisted rescue must be provided in accordance with Section 1007.8.
2. Where the exit stairway is open to the exterior, the accessible means of egress shall include either an area of refuge in accordance with Section 1007.6 or an exterior area for assisted rescue in accordance with Section 1007.8.
1007.3 Enclosed exit stairways.
An enclosed exit stairway, to be considered part of an accessible means of egress, shall have a clear width of 48 inches (1219 mm) minimum between handrails and shall either incorporate an area of refuge within an enlarged floor-level landing or shall be accessed from either an area of refuge complying with Section 1007.6 or a horizontal exit.
Exceptions:
1. Open exit stairways as permitted by Section 1019.1 are permitted to be considered part of an accessible means of egress.
2. The area of refuge is not required at open stairways that are permitted by Section 1019.1 in buildings or facilities that are equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
3. The clear width of 48 inches (1219 mm) between handrails and the area of refuge is not required at exit stairways in buildings or facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
4. The clear width of 48 inches (1219 mm) between handrails is not required for enclosed exit stairways accessed from a horizontal exit. 5. Areas of refuge are not required at exit stairways serving open parking garages.
The IBC Egress code also includes 1007.4: Elevators, 1007.5 Platform Lifts and 1007.6 Areas of Refuge - all of which can be read in the document cited just below.
Above: my sister, Linda Ann is demonstrating an attractie but really too-big-to-grasp newel post at the bottom of a stairway in Mexico.
Guards or guard rails referred to in stair codes and specifications refer to the safety barrier placed along the open sides of a horizontal walking surface such as a landing, balcony, deck, or porch.
Stair rails: the equivalent safety barrier placed along a stairway and called a stair rail is discussed
Handrails are intended to be grasped to assist the user in climbing or descending the stairway and to help prevent a fall.
Guardrails are enclosures to prevent someone from falling through or off of a stairway, deck, balcony, etc.
Note that in most codes it is permitted to make the stair guard or stair rail graspable, making it also usable as a stair handrail. But if the stair rail is not graspable, a graspable handrail must also be installed.
Railings in stair codes and specifications refer to the safety barrier along steps or stairs.
Photo: the author demonstrating a ridiculously-low handrailing along the stairway of a New York home.
Also see GUARDRAIL CODES & STANDARDS for details about safety railings on landings and open hallways, porches, screened porches, balconies - horizontal walking surfaces.
Guards [guardrails] are required by section R316 for open sides of stairways, porches, balconies or raised floor surfaces located more than 30 inches above the floor or grade below, except for open sides of a flight of stairs with a total rise of 30 inches or less, although handrails are still required when there are two or more risers.
Guards protecting floor surfaces must be 36 inches in height, while guards for stairs must be 34 inches in height measured vertically from the tread nosing.
A guard may also serve as the required handrail (34 to 38 inches high) provided the top rail meets the requirements for grip size. The guard must have intermediate rails or ornamental closures that do not allow the passage of a 4-inch diameter sphere. The triangular openings formed by the riser, tread and bottom rail of the guard must be sized to prevent the passage of a 6-inch sphere.
Details about guardrails, handrails, and stair railings are at these articles:
Using a local building code citation from Glen Cove, New York, for outdoor double-retaining walls outdoors, the lower retaining wall is 48" in height, the space between the retaining walls is four feet or more, and the top of the wall is 24" high. -- Richard Kralstein
A handrail, unlike a stair rail or guard rail, must be graspable and is is defined as:
A horizontal or sloping rail intended for grasping by the hand for guidance or support.
Handrails have multiple requirements such as graspability, projection into the stairway, handrail height, & mechanical security rules.
Photo: the author measured the guardrail and handrail width at this stairwell as part of documentation of an stairway whose handrail was not graspable (too wide). A user was injured at a stair fall at this stairway.
Complete details about handrails such as those used along stairs and ramps are
at HANDRAILS & HANDRAILINGS Excerpts are bleow.
Handrail cross section and size:
Figure 4 (left) shows the recommended cross-section and dimensions of a good handrail. Ideally the cross-section should be round (diameter 4-5 cm, with circumference of 12-14 cm) to allow for a good firm grip.
You should be able to run your hand smoothly along the entire length without having to adjust your grip. You should apply the so-called "tennis-racket grip" at all times when possible.
Guardrails of at least 40 cm above the surface of the stairs are needed to prevent falls off the side of the stairs that are not equipped with a banister.
Details about safe graspable and unsafe non-graspable handrailings are found
at GRASPABILITY of HANDRAILINGS.
[From Canadian Occupational Safety Regulations - Stairways & Fall Prevention, but this dimension and concept of graspability is widely used]
Clarification from Residential exit doors, stairways, landings, handrails and guards [PDF] for New York:
RCNYS section R315 requires stairways having two or more risers to have at least one handrail, at a height of between 34 and 38 inches above the nosing.
There must be a clearance of at least 1 ½ inches behind wall mounted handrails. Handrails must be continuous from a point above the top riser to a point above the lowest riser of each flight of stairs.
This would allow a newel post to be attached to the face of the bottom riser, with half of its base resting on the bottom tread.
See details
at NEWEL POST CONSTRUCTION
Exceptions to R315.1 involving newel
posts are contained in the original ICC version of the code and have been issued as a clarification to the
RCNYS and are effective as follows:
Exceptions:
1. Handrails shall be permitted to be interrupted by a newel post at a turn.
2. The use of a volute, turnout or starting newel shall be allowed over the lowest tread.
The section of a stairway leading from one landing to the next is a flight of stairs. Therefore, handrails are not required on landings [though guardrails might be if the landing is open - Ed.].
Continuous handrails are required on the side of where the tread is narrower for winders. The maximum variation in riser height and tread width is 3/8 inches to maintain uniformity in the flight. Handrail grips may be circular, 1 ¼ to 2 inches in diameter.
If they are not circular the perimeter of the sides must total 4 to 6 ¼ inches with a maximum cross-section dimension of 2 ¼ inches.
When the total perimeter of the sides exceeds 6 ¼ inches, a graspable finger recess complying with section R315.2 must be provided on both sides of the handrail. There are no dimensional provisions for newels.
Above: a non-graspable railing along the top of a stair guard, Mexico City. The newel post at the landing is also sometimes used to arrest a fall.
No one who was walking down the right side of this stairwell and who slipped could possibly grasp this very wide surface to try to arrest a fall.
This discussion has moved to newel POST CONSTRUCTION
Photo: our inspection client is demonstrating one of our all-time favourite unsafe exterior deck stairs: tall risers, narrow treads, no handrails, no guardrails, and though it's hard to see in this photo, algae-covered wood steps that are extremely slippery when wet.
Details about stair risers are
A summary is just below
2008 NYS Stair Code: R311.5.3.1 - Stair Riser height Requirements. The maximum riser height shall be 8 1/4 inches (209 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm.) (Courtesy Arlene Puentes).
Stair riser heights shall be 7 inches (178 mm) maximum and 4 inches (102 mm) minimum. Stair tread depths shall be 11 inches (279 mm) minimum. The riser height shall be measured vertically between the leading edges of adjacent treads.
The greatest step riser height within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm).
The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread's leading edge. - 2007 NYS Stair Code: 1009.3 Stair treads

Closed stair treads using a solid riser are shown in Carson Dunlop's sketch just above.
Notice that the minimum stair tread thickness is increased when the stair tread is not supported by a solid riser.
Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Exceptions:
1. Solid risers are not required for stairways that are not required to comply with Section 1007.3, provided that the opening between treads does not permit the passage of a sphere with a diameter of 4 inches (102 mm).
2. Solid risers are not required for occupancies in Group I-3.
Open stair risers are shown in our photo below:
Details: see
Details about the construction of & building code specifications for building stair stringers - the angled beam that supports stairs - are
at STAIR STRINGER SPECIFICATIONS.
For stair stringer defect inspection tips and safety hazards also
see STAIR STRINGER DEFECTS
The notched stringer approach shown at left is very secure provided that the stringer depth is great enough and the cutout depth shallow enough that the remaining stringer material is strong enough to carry the weight of the stairway and its users (1-? arrow in sketch at left).
The stair stringer may also support stair treads using grooves routed into the stringer, or stairs may be butted into the inner face of the stringer and nailed or screwed through the stringer opposite side - a dangerous approach that risks stair collapse if additional measures are not taken.
2007 NYS Stair Code: 1009.3 Stair treads Shown in our photo: worn stone stair steps at the Hacienda Jaral de Berrio, Mexico.
These steps are a trip and fall hazard, increased by the absence of guard railings and handrails.
The greatest stair tread depth within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm). (Or 3/8" or 3/16" in some codes).
Winder treads shall have a minimum tread depth of 11 inches (279 mm) measured at a right angle to the tread's leading edge at a point 12 inches (305 mm) from the side where the treads are narrower and a minimum tread depth of 10 inches (254 mm).
The greatest winder stair tread depth at the 12-inch (305 mm) walk line within any flight of stairs shall not exceed the smallest by more than 0.375 inch (9.5 mm).
Where the bottom or top riser adjoins a sloping public way, walkway or driveway having an established grade and serving as a landing, the bottom or top riser is permitted to be reduced along the slope to less than 4 inches (102 mm) in height with the variation in height of the bottom or top riser not to exceed one unit vertical in 12 units horizontal (8-percent slope) of stairway width.
The nosings or leading edges of treads at such nonuniform height risers shall have a distinctive marking stripe, different from any other nosing marking provided on the stair flight.
The distinctive marking stripe shall be visible in descent of the stair and shall have a slip-resistant surface. Marking stripes shall have a width of at least 1 inch (25 mm) but not more than 2 inches (51 mm).
See STAIR DESIGNS for UNEVEN / SLOPED SURFACES for details.

Step tread depth (=> 10") (measured 12" from smaller side of irregular stair shapes such as triangular treads on curves or spirals)
Details about stair step tread codes and specs
The steep, thick wooden-tread stair shown here, located in Campo San Maurizio, Venice Italy, are old, creaky, and steep with minimal hand-rail, no top landing, and a too-short landing as shown in our photo.
This stairway is what can fit in the available space. Notice the tiny and incomplete handrail made of 1/2" pipe, the tall stair treads, the too-short landing platform, and the absence of any stair guard along the lower treads.
In older buildings it's often impossible to meet modern stair codes - stairs like these were crammed into a space too small to meet modern stair dimensions.
Details about stair tread dimensions including width, depth or run, and tread nose requirements are found
[The above specification of allowable variation in stair tread slope] was probably taken from the chapter on Means of Egress, in which case it is applicable to a means of egress, and not stairs outside the means of egress, like in a public way. It is very hard to maintain such tolerances for exterior sidewalks and public ways.
At least I think that is the way it is in the IBC. I am not a code official, however, and I know they may see things differently. - J.M., AIA
Reply: the above discusses stair treads and does not refer to sidewalks - Ed. CONTACT us to suggest building code citations or stair tread specifications that vary from these.
Also see STAIR TREAD SLOPE where we discuss slip hazards.
Details about tread construction for outdoor stairs include opinions about avoiding cupping and slippery ice or algae:
see BARK SIDE UP on DECKS & STEPS
Details about the proper design of stair tread nosings in shape & dimensions as well as history, research & stair tread nose hazard discussion are
at STAIR TREAD NOSE SPECIFICATIONS
A summary is below
1009.3.2 Profile. The radius of curvature at the leading edge of the tread shall be not greater than 0.5 inch (12.7 mm).
Beveling of nosings shall not exceed 0.5 inch (12.7 mm). Risers shall be solid and vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 degrees (0.52 rad) from the vertical.
The leading edge (nosings) of treads shall project not more than 1.25 inches (32 mm) beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight.
I am looking for information on stair noses. I am having hardwood flooring installed in a home that previously had carpet and vinyl.
The stairs are pine that previously had carpet installed over them and were not finished at all.
The current hardwood floor installer has installed the top stair bullnose, that ties into the upstairs flooring, right over the existing bullnose so that two rounded edge bullnoses are visible.
The installer refuses to trim the nose flush to the riser so that only one bullnose is visible stating that trimming the nose/lip would effect the integrity of the stairs. To confirm this is only the top stair that ties into the floor. It looks very bad aesthetically.
Is this common practice? There are numerous videos and periodicals showing proper installation would be to trim the existing lip. Please help. - Anon by private email 2017/10/30
While building codes cannot anticipate every possible way that a stair-builder can foul up a set of stairs, in our OPINION the stair tread nose shown below is a trip hazard, principally because of its double thickness.
The stair tread double-nose photograph above, provided by the InspectApedia.com reader, appears to violate the stair tread nose curve radius and stair tread nose profile (greater than 1/2-inch).
A double-thick stair tread nose may catch the tip of a shoe, particularly when ascending the stairway. In my vew these treads need to be repaired.
I would trim back the under-tread to flush with the riser face - a job taht would have been easier before the top level of flooring was installed (and may be a too-thin tread nose).
Watch out: if the double layer of walking surface was installed only on the topmost step (the floor) then the riser heights of these stairs may also be inconsistent by 3/4" at the topmost step - another trip and fall hazard.
The radius of curvature at the leading edge of the [stair] tread shall be no greater than 9 / 16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 1 1/4 inch (32 mm) shall be provided on stairways with solid risers.
The greatest [stair tread] nosing projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm) between two stories, including the nosing at the level of floors and landings.
Beveling of [stair tread] nosing shall not exceed 1 / 2 inch (12.7 mm). Risers shall be vertical or sloped from the underside of the leading edge of the tread above at an angle not more than 30 (0.51 rad) degrees from the vertical.
Open risers are permitted, provided that the opening between treads does not permit the passage of a 4-inch diameter (102 mm) sphere.
Exceptions [to stair tread nose requirements]:
1009.5.1 Stairway walking surface. The walking surface of treads and landings of a stairway shall not be sloped steeper than one unit vertical in 48 units horizontal (2-percent slope) in any direction. Stairway treads and landings shall have a solid surface. Finish floor surfaces shall be securely attached.
Exception: In Group F, H and S occupancies, other than areas of parking structures accessible to the public, openings in treads and landings shall not be prohibited provided a sphere with a diameter of 11/8 inches (29 mm) cannot pass through the opening.
Relevant to the slipperiness of stairs is this outside stair provision
1009.5.2 Outdoor conditions. Outdoor stairways and outdoor approaches to stairways shall be designed so that water will not accumulate on walking surfaces.
In other than occupancies in Group R-3, and occupancies in Group U that are accessory to an occupancy in Group R-3, treads, platforms and landings that are part of exterior stairways in climates subject to snow or ice shall be protected to prevent the accumulation of same.
[Not found in NYS Code] - A walking-surface that provides a coefficient of friction of 1.02 dry and 0.98 wet will comply with ADA, OSHA, and most local building codes and insurance requirements. This requirement is reiterated in our summary of Canadian OSH stairway rules below.
Details about stair slip and trip hazards due to walking conditions are at

While individual stair riser heights and tread dimensions determine the walking comfort and safety of stairs and stairways, here are some typical overall slope specifications that characterize different types of building entrances and exits.
You can see from the sketches above and below the recommended range of slopes or angles for various types of ramps, stairs and ladders.
From: Kodak's ergonomic design for people at work. 2nd ed. John Wiley & Sons, 2004. p.24
Details:
Stair Landings are required at top and bottom (with exceptions at top of interior stairs or in garage if door swings in, away from the stairs)
See details about stair landing codes and specifications
at STAIR PLATFORMS & LANDINGS, ENTRY. A summary is below.
Examples of Stair Platform or Landing Defects
Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
1009.4 Stairway landings. There shall be a floor or landing at the top and bottom of each stairway.
The width of landings shall not be less than the width of stairways they serve. Every landing shall have a minimum dimension measured in the direction of travel equal to the width of the stairway. Such dimension need not exceed 48 inches (1219 mm) where the stairway has a straight run.
Clarification from Residential exit doors, stairways, landings, handrails and guards [PDF] for New York:
Section R312 requires a floor or landing at the top and bottom of each stairway and on each side of each exterior door. The exception provides that on all exterior doors, except the required main exit door, where there are two or fewer risers, a landing is not required.
Section R312.1.2 also provides that at the required main exit door, the landing be no more than 1 ½ inches lower than the top of the threshold, while landings at all other exterior doorways may be as much as 8 ¼ inches lower than the threshold.
However, the State Fire Prevention and Building Code Council amended this section in 19 NYCRR section 1220.3, effective July 10, 2003, as follows:
Landings at required exit doors. In lieu of compliance with section R312.1.2 of the Residential Code of New York State, an exit door required by section R311.1 of the Residential Code of New York State may have an exterior landing which is not more than 8 ¼ inches (209 mm) below the top of the threshold.
With this amendment, there is no longer a requirement that the level of the landing outside the required main exit door be limited to no more than 1 ½ inches below the threshold. Additionally, landings have to be at least as wide as the door or stairway and at least 36 inches long measured in the direction of travel.
And from the same document
Landings are required on the exterior side of a sliding glass door when served by a stair having more than two risers. A 6-0 x 6-8 sliding door (even if it is an emergency escape and rescue opening required in a sleeping room) is still a door and requires a landing per section R312.1.2.
Considering only the operable part of the sliding door, the width of the landing does not need exceed 36 inches. It would also be permitted to install a guard on the exterior of the sliding door in lieu of the required landing and stairs when the door threshold is more than 30 inches above grade.
Stairway Lighting is Required, with light switches at top and bottom of the stairway if the stairs encompass more than three stair treads (Canada) or six stair treads (U.S.).
Details about lighting requirements and codes for lighting requirements over stairs are at
Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

Clarification from Residential exit doors, stairways, landings, handrails and guards [PDF] for New York:
Stairways are regulated by section R314 and include winders, spiral stairs, circular stairs, and bulkhead enclosure stairs.
Stairways shall be not less than 36 inches in clear width at all points above the handrail height and the handrail may project no more than 4 ½ inches on either side of the stairway.
Thus, the minimum clear width of a stairway at or below the handrail, when one is required, is 31 ½ inches, and 27 inches where two are required. Stair trim, stringers and other features may reduce the stairway width as long as they do not extend beyond the allowable handrail projection.
There is a width exception for spiral stairways. The maximum riser height is 8 ¼ inches and the minimum tread depth is 9 inches.
Open risers are permitted provided the vertical opening between treads does not permit the passage of a 4-inch-diameter sphere in stairways which have a rise exceeding 30 inches.
The minimum headroom is 6 feet, 8 inches measured vertically from a sloped plane along the tread nosings or from the floor or landing surface.
Sketch above, courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Details are
at STAIR DIMENSIONS, WIDTH, HEIGHT.
Exceptions may be at ATTIC STAIR CODES & HAZARDS and
at BASEMENT STAIRS depending on how these areas are used or intended to be occupied.
Moved to FIRE ESCAPES & FIRE STAIRS
Photo above: our inspection client demonstrasting walking down an angled stairway in New York City.
Details about circular, spiral, and winder stairs and their code & construction requirements are at
Above: Carson Dunlop Associates' sketch illustrates that the minimum tread width for curved stair treads is 6-inches deep (across from nose to riser) at the most-narrow point and that the treads must be at least 9-inches deep at a point measured 12-inches from the narrow edge of the stair step.
Sketch above, courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Two interlocking stairways providing two separate paths of egress located within one stairwell enclosure - IBC 1002 [14a]
Scissors stairways may be installed to avoid crowding or safety issues between people ascending and descending between building floors - where you may see an UP staircase marked separately from a DOWN staircase.
Stairway headroom (=> 6'8" over tread or landing)
Stairways shall have a minimum headroom clearance of 80 inches (2032 mm) measured vertically from a line connecting the edge of the nosings.
Such headroom shall be continuous above the stairway to the point where the line intersects the landing below, one tread depth beyond the bottom riser.
The minimum clearance shall be maintained the full width of the stairway and landing. - NYS
Headroom is allowed to be reduced to 78" over spiral stairs in some codes such as New York State.
Details are at STAIR HEADROOM
Sketch showing stairwell width and landing details is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Stairwell width and stair landing platform requirements are summarized by this sketch.
The minimum recommended stair width is between 34" and 36" ACROSS.
The minimum recommended stair landing length is 36" (or a length and width sufficiently greater than the swing of the door if a wider door is present.
Notice that a stair top landing is not required if the door at the top of the stair opens away from the stairwell.
In these sketches required handrails have been omitted for clarity.
1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44 inches (1118 mm). See Section 1007.3 for accessible means of egress stairways.
1009.6 Vertical rise. A flight of stairs shall not have a vertical rise greater than 12 feet (3658 mm) between floor levels or landings.
This means that if the floor to floor height traversed by a stairway is more than 12 feet of vertical distance, one or more landings is required.
Moved to FIRE STOPPING for STAIRWAYS
This list has moved to BUILDING CODE DOWNLOADS
In theReferences or Citations section of this article you will find more model codes and other key documents on building codes and stair and railing safety.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
Can my door from house to garage swing open over a stairway?
In-swing door from a garage...can it open to the top step of a stairway? Step is same elevation as garage slab. - On 2020-09-14 by Rick Dawson dawson@rrdawson.com
Reply by (mod) -
Rick I'm confused about this question; if the step is the same elevation as the garage slab then how can it be a step at all?
In general we do not want a door to open by swinging out over a step - people fall down those very often.
A door can swing out over a platform or landing.But the landing's walking surface should be at the same level as the walking surface of the floor on the other side of the doorway.
What's the required spacing between balustes
Spacing between balusters - On 2020-09-04 by Anonymous
Reply by (mod) - 4 inches
4 inches
Is it OK for my step to slope 9 degrees to the sidewalk?
I'm building a new house. I have six front steps that end about 12 inches from the sidewalk.
The sidewalk is 9.5" below the tread of the last stair.
The builder has poured concrete at a 9 degree angle sloping upward so that it meets the bottom of the first stair at 7.75" below the tread to "meet code".
Is this acceptable? It seems like a tripping hazard that shouldn't meet code. Any help would be appreciated. Thanks! - On 2020-06-22 by phelps.es
Reply by (mod) - No. There are multiple trip hazards at your bottom step: maximum slope allowed on stair treads & platforms should be no more than 1/4" per foot
OPINION: I can't make out enough of what's going on with these steps but that looks like a trip hazard to me. Inconsistent step rise, too short bottom landing platform (we want 3 ft. in the direction of travel), no visible handrails, landing doesn't extend the width of the steps above!
Stair treads, landings and platform walking surfaces should be level within 2% of dead flat - a maximum slope of 1/4" per foot. Your 9% then is 4 1/2 times the allowable slope for a stair tread or platform. And as I listed above, that's just one of the hazards and code violations in your photo.
Using the International Residential Code IRC 311.7.7 as an example, the code says that the
Stairway walking surface of treads and landings shall be sloped not steeper than 1 unit veritical in 48 inches horizontal (2-percent slope).
Let's do the math: 2% of 48" = 0.96"
Now divide that by 4 to get the slope per foot
0.96 / 4 = 0.24 or 1/4" per foot of slope.
Really? For proper drainage we may deliberately slope outdoor steps and landing platforms to 1% or 1/8" per foot.
So strictly speaking your bottom step or "platform" is sloped excessively, per model building codes.
Too much slope and uneven tread riser heights and possibly a too-narrow step if it's less than the width of the step above, are multiple trip hazards and ought to be called out by the code inspector.
Is a 1x6 a graspable handrail?
Is a 1x6 considered to be graspable - On 2020-05-20 by William
Reply by (mod) - No
No. Not without modification - and since 1x lumber is really thin, just 3/4" of actual thickness, there's not enough thickness to route out indentations for thumbs and fingers along such a board if it's set on edge. If the board is set on flat it's absolutely not graspable either - too wide.
Do we need a guardrail in the loft?
We recently constructed a small loft under the sloped ceiling of our living room. It’s about 6 feet off the ground, and the ceiling ranges from 26 inches - 36 inches above the floor of the loft.
We were thinking of putting a ladder up against it and making it a hangout space for our kids. I’d put a railing up there for them of course, but I’m wondering about the minimum height of the railing since the ceiling is so low.
(I’d prefer to keep it around 26 inches and not run the balusters up to the ceiling). I’m also wondering if there are any other code requirements to worry about with the ladder leading up to the loft. Or if you think an inspector would have an issue with this idea altogether! Thanks for your advice! - On 2020-04-27 by Kelly
Reply by (mod) - Yes
I would expect an inspector to consider the falling hazard as significant. Lets put safety ahead of approval in any case. What about a floor to low ceiling guardrail?
Followup by Kelly
thanks for your reply. The guardrail is one option. I’m starting to wonder if they will care how I finish it since it is non-habitable space. Seems like code isn’t very well defined for space like this.
Reply by (mod) -
agreed
Non-habitable spaces are generally excluded from the stair and guardrail codes.
Still if your kids are going to enter it you want to make it safe.
Mobile home is missing entry steps
I live Louisiana and in August of 2016 our area was determined a Federal Disaster after a great flood flooded 90 percent of our parish. I was approved for a grant in the amount of 45,000 through FEMA/LA Restore Program to replace my mobile home.
However NO correctly height STEPS were provided to allow safe entry into the mobile home.
There was still another 3 feet to the threshold from top of steps provided. I discussed this issue before purchasing the mobile home and was told I would be provided with proper stairs.
This was supposed to be a TURN KEY transaction. Is this something you would consider fair to do to a single lady and her 9 year old son ? - On 2020-04-18 by Aimee Deville
Reply by (mod) - home seller did not fix unsafe mobile home steps as promised
No, Aimee of course it is not "fair" nor proper nor ethical nor decent for a home seller to agree to do something and then fail to do it.
However unfortunately the history of real estate transactions is so rife with bad behaviour that real estate law has evolved to include this point:
If you don't have it in writing you don't have it. period.
All you can enforce is what's in your written contract - I'd expect your lawyer to explain this to you.
Or put another way, an oral rider or promise can not be made to a written contract - whatever you were told orally - by someone just saying it aloud - is worthless.
The number one concern here is safety. In event of a fire or emergency or even in daily use, you must have stairs that let you safely enter and exit the home.
Do Ramps have to be secured against movement if just temporary?
Do temporary ramps placed over outside stairs need to be bolted to the concrete? - On 2019-11-05 by Abe
Reply by (mod) - bolt temporary ramp to concrete ?
I haven't seen that requirement but you absolutely want to be sure that the ramp is not in the slightest possibility going to move when it's being used. Otherwise someone could be badly injured. -
Can bottom step riser be different from rest of steps?
If your deck steps join to a sloping surface what is the variation allowed for that bottom riser? - On 2019-10-04 by Jim Bentley
Reply by (mod) - deck steps join to a sloping surface
Jim
You ask an important question and one for which I don't think there's a single right answer. The variation in Riser height across the width of the stair will depend of course on the slope of the ground left to right and that's not going to be the same for all Sites.
When I build stairs that descended to a slope that descended across the width of the stairway I chose my bottom Riser height to be such that in the middle of the width of the step I have the same rise as the rest of the risers in the stairway.
Wooden steps with no guardrail - OK?
Recently built a set of wooden steps outside unprotected,meaning there are no walls or anything around they are just out in the open with a metal rail on 1 side. What are all of the requirements for the 1 metal railing,and any other requirements if any ? - On 2014-08-24 by ccole0521
Reply by (mod) -
Open stairs need a handrail and need guardrails on both sides. If the step width exceeds your local code's spec for handrails on just one side, then a second one is needed on the other side.
Second set of steps at a landing are different in height from other stairway - OK?
At the top of my stair case there is a landing - 44" wide and 60" deep.
At this landing, there are two sets of stairs with two risers a piece, one to the left and one to the right, running perpendicular to the main stair case.
The riser height of these smaller stairs/steps is different from the main staircase.
Is there a minimum landing dimension required in order for those smaller stairs to fall under a new set of stairs so the risers don't have to be the same as the main stair riser height? I have it in my mind that it should be 48"x48" but I'm not finding it anywhere. - On 2014-08-21 by Anonymous
Reply by (mod) -
My impression (I'm not a legal authority) is that once you've crossed a landing space the new or second set of stairs don't have to have the same rise as the other stairway.
You'll want to confirm this interpretation with your local building code officials as theirs is the final legal word in your jurisdiction.
Let me know.
Daniel
Deck stairway has newell post in middle of the run - OK?
I have a home with a legal means of egress from the home to grade from inside the home second means is off the rear deck.
Issue we see is the deck stairway has an opening of 34 inches wide and a secondary rail will also be needed as length is over 12 feet so its broken up by a newal post in the middle of the run
So width of deck stairway will be closer to 30 inches from edge of secondary rail to edge of vinyl handrail on other side of steps since we have one legal means of egress,
are deck rails allowed at such width?
heard as along as one means of egress are legal, other means can be less the 36 inches wide for clearance. thank you - On 2014-07-30 by jim alburtus
Reply by (mod) -
Jim
1. I think we need to look at guidelines about projections into stairways such as
ICC 1003.3 Projections
1003.3.3 Horizontal projections.
Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches (102 mm) over any walking surface between the heights of 27 inches (686 mm) and 80 inches (2032 mm) above the walking surface.
Exception: Handrails serving stairs and ramps are permitted to protrude 4.5 inches (114 mm) from the wall.
2. Your local building code compliance official is the final legal authority. Give them a call since it's a bit of a waste of time and money to design and build a detail if the local officials are not going to approve it.
In case it helps I wanted to add this 2006 ICC model code. example1003.3.2 Free-standing objects.
A free-standing object mounted on a post or pylon shall not overhang that post or pylon more than 4 inches (102 mm) where the lowest point of the leading edge is more than 27 inches (686 mm) and less than 80 inches (2032 mm) above the walking surface.Where a sign or other obstruction is mounted between posts or pylons and the clear distance between the posts or pylons is greater than 12 inches (305 mm), the lowest edge of such sign or obstruction shall be 27 inches (685 mm) maximum or 80 inches (2030 mm) minimum above the finished floor or ground.
Exception: This requirement shall not apply to sloping portions of handrails serving stairs and ramps.
Comment by (mod) - Keep stairways free of clutter and obstructions
Very interesting point. The codes can't and don't try to cite every snafu that people are going to be able to come up with, as we're a creative animal.
But such stairs violate saf design and likely run afoul of requirements to keep a stairway free of clutter or obstructions when such a drawer is open.
Even a small opening violates requirements for uniform treads and violates stair nose projection dimensions.
...
Continue reading at BUILDING CODES for STAIRS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see CODE DETAILS for STAIRS & RAILING, FAQs - questions and answers about stair and railing codes and standards posted originally at this article
Or see these
STAIR CODE DETAILS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.
OSHA estimates that there are 24,882 injuries and as many as 36 fatalities per year due to falls from stairways and ladders used in construction.
Nearly half of these injuries are serious enough to require time off the job--11,570 lost workday injuries and 13,312 non-lost workday injuries occur annually due to falls from stairways and ladders used in construction.
These data demonstrate that work on and around ladders and stairways is hazardous. More importantly, they show that compliance with OSHA's requirements for the safe use of ladders and stairways could have prevented many of these injuries. -osha.gov/doc/outreachtraining/htmlfiles/stairlad.html