How to identify & wire or use BX, flexible armored cable electrical wire.
This article discusses the history of BX electrical cable, its uses, wiring methods, and inspection.
In this article series, we list common old building electrical wiring system safety concerns and we illustrate types of old electrical wires and devices. This article series answers basic questions about assessing and repairing the electrical service, capacity, wiring type, condition, and safety in older homes.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Editor/Publisher - See WHO ARE WE?
The photo above illustrates two generations of metallic-sheathed armored cable or "BX" electrical wire. The vertical armored cable is an earlier generation of BX while the two flexible metal cables coming off the left side of the electrical box are its modern counterpart.
As the terms are generally used, synonyms for "BX" electrical wire include BX cable, armored cable, armor clad cable, and flexible metal conduit cable wire.
The larger diameter wider-wrapped armored cable is probably Greenfield flexible steel armored cable, a wiring type patented in 1898.
The flexible metal exterior of BX flexible armored cable provides considerable protection of the electrical conductors inside, guarding them from mechanical damage.
Where does "BX" come from? Dini (2006) explains that this cable was produced by Greenfield, one of its inventors, in two experimental forms AX and BX (X = experimental). The second version "B" was the more successful version that was produced.
The illustration above is excerpted from Greenfield's 1898 patent for Armored Electric Cable.
The term "BX" stuck on later versions of flexible metal armored cable: the smaller-diameter modern "BX" wire is in the left of the photo and connects to the left side of the electrical box.
BX wire appeared in the U.S. National Electrical Code in 1903, was popular and in wide use as early as the 1920s (earlier in some locations), very widely used in the 1950s, and remains in use today in new work where flexible armored cable is required, often by local codes.
Just above and also below: flexible aluminum BX or armored cable, stamped with AL, found in a 1955 Montreal home, courtesy of InspectApedia reader PE.
This aluminum sheathed BX cable contains a hot (black) and neutral (white) fabric and rubber insulated conductor, a fire-and moisture-resistant paper wrapping, and a thin flat aluminum strip.
Modern BX or flexible metal conduit (FMC) electrical wire provides conductors that will be plastic-insulated rather than the older rubber.
[Click to enlarge any image]
Watch out: Notice that the wire in the photo above does not include an approved grounding conductor.
Below at BX CABLE GROUNDING CONDUCTOR we discuss proper grounding when using BX cable.
Defects often found in the flexible conduit are discussed separately
Greenfield's original armored cable design used multiple strands of copper conductors, typically twisted, and surrounded by a pitch-like insulating material like that we illustrate in Edison's original underground electrical cables shown
at STEAM BOILERS GENERATORS CONTROLS, PRATT.
Here are the original image and a text excerpt from Edwin T. Greenfield's 1898 patent:
My invention is directed particularly to improvements in electric cables designed for ocean service, and has for its objects,
first, to devise an armored cable of such nature that the insulation of the cable will be thoroughly protected from the attacks of borers or other insects or animals which usually attack cables of this nature when sunk in the body of the ocean
second, to devise an armored cable of such a nature that its exterior armor will fully protect it (the cable) from unnatural wear when it is suspended over ledges of rock in the body of the ocean;
third, to provide a cable of the nature indicated in which the armor is of steel, phosphor-bronze, or any preferred metal having the desired strength and qualities for adapting it for use in the ocean and in making such armor of a flexible nature, so that the completed cable may be wound upon a drum in the usual way when it is desired to lay it in the bed of the ocean, and,
fourth, to provide a lead or equivalent covered cable with a flexible protecting armor which will protect the lead covering from the action of metal slivers when drawn into a conduit.
Also see a brother wiring material sold without conductors in this article:
1960 CIRCLE WIRE & CABLE Advertisement [PDF] in Electrical Engineering Magazine, Issue No. 9, Sept.-1960 p. 26A - excerpt shown just above, describes Circlesheath® Type RR armored cable for use underground (buried).
This advertisement describes the company's products as "Rubber covered wire & cable, varnished cambric cable, plastic insulated cable, neoprene sheathed cable, and cirtub EMT."
More Circle Wire & Cable products are described
at CIRCLE WIRE and CABLE Corporation
Below: an early advertisement for Cres-Flex armored cable or "flexible metallic-sheathed" wire:
Crescent Insulated Wire & Cable Co. also made fabric-insulated electrical wire described further
Armored cable or metallic-sheathed electrical cable has been in use since 1896 (in the U.K.) and in its most basic form contains two electrical conductors (black-hot and white-neutral) each individually insulated and both usually wrapped with a spiral of paper which is in turn enclosed in a flexible metallic sheathing such as shown in our abandoned wire photograph below.
Watch out: often we find that the rubber-insulated conductors in older electrical wire such as this BX, possibly a G.E. product, are so deteriorated that the insulation is crumbly and unreliable. If you can not strip back the wire to conductors whose insulation is intact then the wire should be replaced.
Watch out: When cutting BX, the saw cut should be diagonally across one rib of the armor, and you need to take care to cut just the metal armor and not the wire insulation.
In the U.S., the National Electrical Code Article 320 Armored Cable: Type AC covers the installation and use of BX electrical wire.
See ELECTRICAL WIRE STRIPPING TIPS where we discuss proper wire stripping details and how to work with BX or armored cable.
When cutting armored cable (AC) or metal-clad (MC) cables, you can either CAREFULLY use a hacksaw or tin snips or you can use a tool designed specifically for the job. The cable is laid inside the tool, which has a round cutting blade on a crank.
This comment and reply were posted originally
at ELECTRICAL WIRE STRIPPING TIPS
The BX cutting tool is squeezed with one hand to clamp the blade against the armor sheath and the crank is turned a few times with the other hand to cut a clean slot in the metal sheath without damaging the wires.
The cable with the split armor is then taken out of the tool, the sheath is twisted and it pops apart cleanly.
[Click to enlarge any image]
Our photo above of an AC cutting tool provided courtesy of NH Firebear and is discussed in more detail below.
Make certain that the electrical power has been turned off
and that you've used a test tool such as a VOM or neon tester to confirm that the wires you're working on are not electrically live. Failure to take this step risks a fatal electrical shock.
Note that when type AC (trade name "BX") is used, there must also an insulated bushing (known as a "red-head" or "Red Hat") inserted to protect the internal conductors from damage and shorting on the cut end of the armor. Connectors for Type AC have a slot through which to inspect for the red-head.
This anti-short bushing is required by U.S. NEC Article 320.40 whenever AC type "BX" cable is being installed.
(See details at NEC Article 320.40 Boxes and Fittings at BX & MC CABLE WIRING CODE )
But MC type electrical cables do not require an anti-short bushing like that shown above.
Where MC (Metal Clad) cable is installed, listed fittings may or may not include an insulated throat or bushing but MC fittings are required to provide a rounded, smooth end-stop through which the conductors pass so that they won't be damaged in passage.
For MC wiring, those bushings are optional and may be provided by the MC cable manufacturer.
Most types of red-heads now have a "tail" that can be left sticking out of the hole for easier inspection. Ref NEC® Article 320.40. The bonding conductor may be bent back, over the sheath, either before or after the red-head is inserted.
Watch out: the BX flexible metal sheathing cut in this case extends through more than one rib and is not good practice.
Unlike AC (Armored Cable), Type MC (Metal Clad) installations do not generally require a red-head and have no inspection hole, although some local codes may still require them.
Type MC connectors are designed to prevent the conductors from contacting the armor. Not all electrical inspectors can recognize the difference without taking things apart.
These photos used a Type MC cable having 12-2 with ground. A type AC would have a bonded ground. The red-head and AC connector were used for demonstration only. Do not use the wrong type of connectors for your particular type of conduit as they may damage the metal sheath.
For instance, a set-screw connector could crush an aluminum AC sheath and damage the conductors inside.
It is worth noting that Type AC and Type MC, while similar in appearance and construction, have different code restrictions on where they may be used. - NH Firebear by private email 2016/07/27
Excellent and helpful details, published above. Thank you NH Firebear.
Indeed, as I've reported elsewhere, my brother-in-law, a theater electrician in New York City, re-wired his apartment into an electrical disaster when he used BX armored cable throughout (as required in NYC), with no protective "red-head" plastic protective inserts in the cable ends. That mistake combined with zealously over-tightening the set screw in every BX cable clamp at every electrical box.
Where the BX cable cut into the hot wire, the circuit breaker shorted immediately and sparks flew when power was restored. Those mistakes were quick to find. But additional shorts between the neutral conductor and the (grounded) BX cable exterior shell meant that Matt's GFCI breaker kept tripping until all of those snafus were also found and fixed.
"Fixing" the short circuits in this case was a pain as the nick into the wire insulation was right at the cut end of the BX metal jacket. A proper repair would have involved stripping back past that nick into the insulation and preparing new stripped wire-ends - a proposition that proved difficult where not enough slack or extra length remained in the original wires.
NH Firebear's moisture-resistant or more generically "waterproof" flexible conduit shown in the photo above is most often seen at outdoor compressor/condenser units of air conditioners or heat pumps but may also be proper indoors in damp locations such as shown above.
The electrical connection between the cable exterior and the electrical box body is through the bushing set screw that is tightened against the BX cable exterior - an inconsistent and unreliable electrical connector whose credible function is to mechanically secure the cable to the box as a strain relief.
Here we show two of several types of connectors for use with armored cable/flexible metal conduit, using a set screw (above) and using a two-screw clamp connection (below).
Watch out: our now ex-brother-in-law Matt, a theater electrician, wired his NYC apartment using the NYC-required BX electrical cable. But being a strong fellow he over-tightened every single set screw connector at every electrical box.
When he turned on electrical power to the circuits none of the breakers would stay "on" because the over-tightened set screws plus the omission of the required plastic bushing insert in the open end of the BX caused the BX exterior edge to cut into either the hot or the neutral wire on every one of his connections.
The BX exterior became electrically live, shorted to the grounding conductor, and blew the breaker.
The flexible aluminum strip is also not usable by itself as a grounding conductor. (It would likely be undersized.)
The flat aluminum tape that you see inside this 1950s BX and the thinner aluminum wire found wrapped around some newer BX cable is an internal "bonding strip" intended to improve the reliability of the external jacket of this cable should it become energized with electrical current.
When the cable is connected to an electrical box, this tape or the smaller aluminum wire is bent back or wrapped around the outside of the cable before it inserted into the BX cable connector that secures the cable to the electrical box.
The electrical code does not explicitly address this question, as we excerpt from Texas' Electrical Code adoption of the NEC:
Article 320.108 Equipment Grounding Conductor
Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor.
It is also important that you use the proper connectors to secure the metal BX exterior to a metal electrical box so that if the metal exterior does become energized it can also be connected through the circuit ground to earth, thus tripping a circuit breaker or blowing a fuse.
Watch out: when routing and installing BX cable, don't bend BX over too sharp an angle or you will break the external flexible metal conduit.
Excerpting from the US NEC as adopted by Texas:
Article 320.24 Bending Radius [for BX cable]
Bends in Type AC cable shall be made such that the cable s not damaged.
The radius of the curve of the inner edge of any bend shall not be less than five times the diameter of the Type AC cable.
Above: BX cable installed at an electrical receptacle box without using the proper strain relief bushing. This is an improper and unsafe electrical wiring job. Note also the additional wires routed through the same electrical box opening - also improper and unsafe.
This photo also illustrates a worst case example of discontinuous grounding of the metal sheathing of the BX cable.
The US NEC specifies that the metal exterior sheath of BX must be electrically continuous - so capable of serving as a ground path. Indeed plenty of sources assert that the external flexible metal sheath on BX armored cable is allowed to serve as the electrical grounding conductor for the circuit whose hot and neutral wires are inside of the cable.
Both AC and MC wiring provide a protective metal sheath that guards the electrical conductors from mechanical damage.
These electrical wire types can be pulled or "fished" over long distances, can be routed near or even touching metal pipes or ductwork, and the wire can its own weight when run between AC-90® Cables from Atkore, sometimes referred to as BX cable, are a commercial wiring method favored by installers for their flexible interlocked steel armor, which provides mechanical protection.
These versatile 600V cables with THHN conductors have certain construction limitations due to the inception and design of UL Standard 4 over 100 years ago.
The UL Standard allows for 2, 3, or 4 conductors, individually wrapped with moisture-resistant, fire-retardant paper and twisted from 14 AWG to 1 AWG.
Type AC Cable is the foundation of all interlocked armored cable assemblies we have today. - Kaf-Tech cited below.
But there are important differences between AC and MC electrical wires that we describe here.
Watch out: an inexperienced installer or inspector may not see the difference between AC - Armored Cable and MC - Metal-Clad cable. The presence of the insulating sheath in MC cable may not be visible by external inspection unless the open end of the cable and its constituents are visible.
The outermost PVC jacket in our example above is not present on all MC cable.
Photo: adapted from NNC, Nassau National Cable Co., Tel: 1-516-482-6313, nassaunationalcable.com. The company describes this product as Type MC Metal Clad Aluminum Interlocked Armor AIA PVC Jacketed Copper Feeder Conductor, available in various gauges.
Excerpting portions of the Texas electrical code adoption of the US NEC:
This article covers the use, installation, and construction specifications for armored cable, Type AC. 3
The definition in this section shall apply within this article and throughout the Code.
Armored Cable, Type AC.
A fabricated assembly of insulated conductors in a flexible interlocked metallic armor.
See 320.100. 320.6 Listing Requirements Type AC cable and associated fittings shall be listed.
Type AC cable shall be permitted as follows:
For feeders and branch circuits in both exposed and concealed installations
In cable trays
In dry locations
Embedded in plaster finish on brick or other masonry, except in damp or wet locations
To be run or fished in the air voids of masonry block or tile walls where such walls are not exposed or subject to excessive moisture or dampness Informational Note: The "Uses Permitted" is not an all-inclusive list.
Type AC cable shall not be used as follows:
Where subject to physical damage In damp or wet locations In air voids of masonry block or tile walls where such walls are exposed or subject to excessive moisture or dampness
Where exposed to corrosive conditions
Embedded in plaster finish on brick or other masonry in damp or wet locations
Exposed runs of cable, except as provided in 300.11(B), shall closely follow the surface of the building finish or of running boards.
Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage.
Type AC cable shall be protected in accordance with 300.4(A), (C), and (D) where installed through or parallel to framing members.
Type AC cables in accessible attics or roof spaces shall be installed as specified in 320.23(A) and (B).
(A) [BX - Armored] Cables Run Across the Top of Floor Joists
Where run across the top of floor joists, or within 2.1 m (7 ft) of the floor or floor joists across the face of rafters or studding, the cable shall be protected by guard strips that are at least as high as the cable.
Where this space is not accessible by permanently installed stairs or ladders, protection shall only be required within 1.8 m (6 ft) of the nearest edge of the scuttle hole or attic entrance.
(B) [BX - Armored] Cable Installed Parallel to Framing Members
Where the cable is installed parallel to the sides of rafters, studs, or ceiling or floor joists, neither guard strips nor running boards shall be required, and the installation shall also comply with 300.4(D).
Bends in Type AC cable shall be made such that the cable is not damaged. The radius of the curve of the inner edge of any bend shall not be less than five times the diameter of the Type AC cable.
(A) General [Support AC on 4 1/2 ft. intervals]
Type AC cable shall be supported and secured by staples; cable ties listed and identified for securement and support; straps, hangers, or similar fittings; or other approved means designed and installed so as not to damage the cable.
Unless otherwise permitted, Type AC cable shall be secured within 300 mm (12 in.) of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 1.4 m (4 1/2 ft).
(C) Supporting Unless otherwise permitted, [for BX - Armored Cable]
Type AC cable shall be supported at intervals not exceeding 1.4 m (41/2 ft).
Horizontal runs of Type AC cable installed in wooden or metal framing members or similar supporting means shall be considered supported and secured where such support does not exceed 1.4 m (41/2 ft) intervals.
(D) Unsupported [BX - Armored] Cables
Type AC cable shall be permitted to be unsupported and unsecured where the cable complies with any of the following:
Is fished between access points through concealed spaces in finished buildings or structures and supporting is impracticable Is not more than 600 mm (2 ft) in length at terminals where flexibility is necessary
Is not more than 1.8 m (6 ft) in length from the last point of cable support to the point of connection to a luminaire(s) or other electrical equipment and the cable and point of connection are within an accessible ceiling
For the purposes of this section, Type AC cable fittings shall be permitted as a means of cable support.
At all points where the armor of AC cable terminates, a fitting shall be provided to protect wires from abrasion, unless the design of the outlet boxes or fittings is such as to afford equivalent protection, and, in addition, an insulating bushing or its equivalent protection shall be provided between the conductors and the armor.
The connector or clamp by which the Type AC cable is fastened to boxes or cabinets shall be of such design that the insulating bushing or its equivalent will be visible for inspection.
Where change is made from Type AC cable to other cable or raceway wiring methods, a box, fitting, or conduit body shall be installed at junction points as required in 300.15.
The ampacity shall be determined in accordance with 310.14.
(A) Thermal Insulation [for BX - Armored Cable Wiring]
Armored cable installed in thermal insulation shall have conductors rated at 90°C (194°F). The ampacity of cable installed in these applications shall not exceed that of a 60°C (140°F) rated conductor.
The 90°C (194°F) rating shall be permitted to be used for ampacity adjustment and correction calculations; however, the ampacity shall not exceed that of a 60°C (140°F) rated conductor.
Where more than two Type AC cables containing two or more current-carrying conductors in each cable are installed in contact with thermal insulation, caulk, or sealing foam without maintaining spacing between cables, the ampacity of each conductor shall be adjusted in accordance with Table 310.15(C)(1).
(B) Cable Tray [for BX - Armored Cable Wiring]
The ampacity of Type AC cable installed in cable tray shall be determined in accordance with 392.80(A).
Type AC cable shall have an armor of flexible metal tape and shall have an internal bonding strip of copper or aluminum in intimate contact with the armor for its entire length.
Insulated conductors shall be of a type listed in Table 310.4(A) or those identified for use in this cable.
In addition, the conductors shall have an overall moisture-resistant and fire-retardant fibrous covering.
For Type ACT, a moisture-resistant fibrous covering shall be required only on the individual conductors.
Type AC cable shall provide an adequate path for fault current as required by 250.4(A)(5) or (B)(4) to act as an equipment grounding conductor.
The cable shall be marked in accordance with 310.8, except that Type AC shall have ready identification of the manufacturer by distinctive external markings on the cable armor throughout its entire length.
Above: electrical wire insulation illustration from Burlery's 1923 patent cited below.
...
Continue reading at OLD HOUSE ELECTRICAL SYSTEMS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
BX WIRING GUIDE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.