Building Inspection, Diagnosis & Repair Info

Attic pull down stair (C) Daniel Friedman Attic Stairway Codes

Attic stair & pull-down or folding stairway construction, installation, inspection, hazards & repairs:

This article explains how to inspect the condition and safety of attic stairs, folding or pull-down attic stairs and ladders, and attic stairway railings, landings, & treads, and related conditions for safety and proper construction.

We include references to key documents on building codes and stair and railing safety.

Our page top photo shows a remarkable attic access method encountered by the author.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





attic Stair Inspection & Safety Concerns

Clutter on steps is a trip hazard (C) Daniel FriedmanWe've had several reports of severe injury involving collapsing attic stairs, including involving home inspectors as well as occupants. Attic & Basement stair defects can be grouped by the stair type:

Conventional or home-made attic stairways - hazards and defects

Watch out for attic stairs that do not meet recommended standards for

Defective & Unsafe Attic Folding Stairs or Pull-Down Attic Stairs

Attic pull down stair (C) Daniel Friedman Attic pull down stair (C) Daniel Friedman

Watch for these common folding attic stair or ladder defects:

Bad attic pull down spring arm (C) Daniel Friedman Bad attic stair spring arm (C) Daniel Friedman Unsafe attic pull down stair (C) Daniel Friedman Loose stair hardware risks collapse (C) Daniel Friedman

The hardware used on most attic folding stair kits is not redundant. If a nut or bolt falls out of a hinge because it was not kept tight there is serious risk of stair collapse.

Attic pull down stair too short (C) Daniel Friedman Attic pull down stair not secured in rough opening (C) Daniel Friedman

As you can see in our photo, this attic pull down stair frame has been tacked in place using a pair of roofing nails set through a cedar shingle shim.

An ASHI home inspector was seriously hurt when descending a set of attic stairs like these when the stair set came away from the rough opening and fell to the floor below.

Warning label on attic stair (C) Daniel Friedman

Warning labels attached by attic pull-down folding stair manufacturers list the requirements for safe attic folding stair maintenance:

This label is from a stair produced by American Stairways, Inc. and it indicates, among other things:

Examples of Other Bad Attic Access Stairs & Railings

More eccenctric attic accesses: an attic pull down stair ladder that is too short (below left) and a near-vertical "stairs" with a turn, (below right).

Bad attic pull down spring arm (C) Daniel Friedman Narrow turning attic access stair © D Friedman at InspectApedia.com

Cluttered, steep attic stair is an access hazard and possibly a fire egress hazard.

Bad attic access - clutter (C) Daniel Friedman

Building Codes for Attic Stairs, Attic Stair Construction Questions & Comments

No guard at an attic access in Poughkeepsie NY (C) Daniel Friedman Paul Galow

Question: are attic pull-down stairs required by code?

I recently purchased a home in Euless Texas and had to replace the complete HVAC system located in the attic. The pull down ladder to the attic was missing but the company that did the work said by law the were required to put in a ladder.

The cost was around $1100.00.

I asked why so much and the answer we were given was the new ladder would be heavy duty 500lb capacity and the opening would have to be expanded to accommodate taking the system out if it needs to be replaced so they wouldn’t have to remove the stairs every time that might happen.

My thought was, I hope that doesn’t happen for At least twenty years, but if that is code, then I guess we should. My question is, is that really building code? - Anonymous by private email from Texas, 2018/02/03

Reply: non-habitable attic access stairs are not required by law for residential construction but might be advisable

I have not found any model or national building code that requires specific stair installations, pull-down or other designs, to provide permanent access to a a non-habitable attic regardless of whether or not an HVAC system is installed there. Non-habitable attics are not regularly accessed by building occupants and do not require stairs.

At the end of this article where we cite other building codes and guidelines for accesses to attics and lofts you will find description of the minimum requirements for ladders used to access lofts where access might be required for example to service mechanical equipment.

Regarding expanding the existing opening to your attic to accommodate a pull-down stair, that is probably quite correct if what is there now is a small rectangular hatch and if you are going to install a pull-down stair.

Standard rough openings for typical attic pull-down stairs

For residential buildings a model code you would consult might be the the

Current International Residential Code IRC–12/13 Section R807 - Attic Access.

There you'll see that an access opening is all that is specified, not stairs. You will also see that for smaller attic areas no access is required whatsoever (In my view some access to all such limited-space areas is desirable to permit visual inspection for leaks or damage, pest control, etc.)

Excerpt:

R807.1 Attic access. Buildings with combustible ceiling or roof construction shall have an attic access opening to attic areas that exceed 30 square feet (2.8 m2) and that have a vertical height of 30 inches (762 mm) or greater over an area of not less than 30 square feet.

The vertical height shall be measured from the top of the ceiling framing members or any permanent obstruction to the underside of the roof framing members or any permanent obstruction.

The rough-framed opening shall not be less than 22 inches by 30 inches (559 mm by 762 mm) and shall be located in a hallway or other readily accessible location.

When located in a wall, the opening shall be a minimum of 22 inches wide by 30 inches high (559 mm wide by 762 mm high).

When the access is located in a ceiling, minimum unobstructed headroom in the attic space shall be 30 inches (762 mm) at some point above the access measured vertically from the bottom of ceiling framing members. See Section M1305.1.3 for access requirements where mechanical equipment is located in attics. - Source: https://codes.iccsafe.org/public/document/IRC2015/chapter-8-roof-ceiling-construction retrieved 2018/02/03

Other Model Building Code Citations for Attic Access & Stairways

2009 IBC (Commercial Construction) requirement for attic space access

1209.2 Attic Spaces. An opening not less than 20 inches by 30 inches (559 mm by 762 mm) shall be provided to any attic area having a clear height of over 30 inches (762 mm).

A 30-inch (762 mm) minimum clear headroom in the attic space shall be provided at or above the access opening.

2006 IRC (Residential Construction): for access to attic spaces:

R807.1 Attic Access. Buildings with combustible ceiling or roof construction shall have an attic access opening to attic areas that exceed 30 square feet (2.8m squared) and have a vertical height of 30 inches (762 mm) or more.

The rough-framed opening shall not be less than 22 inches by 30 inches, and shall be located in a hallway or readily accessible location.

A 30-inch (762 mm) minimum unobstructed headroom in the attic space shall be provided at some point above the access opening.

Final legal authority for attic stair or access requirements:

For a non-habitable space a mere access hatch might be permitted by your local building department (give them a call as they are the final legal authority where you live).

Other Building codes discussing attic stair construction & regulations

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2021-02-08 - by (mod) -

David

Thank you for that important and helpful update.

For homes whose hallways or other areas that provide access to attics that have traditionally been accessed by a hatchway or a pull-down folding-ladder type stairway, (an attic access that required only a small floor area below) a requirement to install a permanent stair (as opposed to a fold-down one) is in my OPINION likely to lead to some griping by people who face a significant increase in construction cost to increase the area of the floor plan where attic access is to be provided now by a permanent stair.

If you have details and/or a source citation that clarifies this point that would be helpful .

On 2021-02-08 by David Bixby

For the upcoming 2021 IRC-Mechanical code change cycle, ACCA has proposed adding a new requirement for a permanent attic stairs or ladder to be installed to access attics that will have HVAC equipment installed for servicing. There is an exception for HVAC that already exists in residential buildings, so it's for new construction or if you are moving HVAC into an attic that has never had equipment installed before.

On 2021-01-10 - by (mod) -

Michael:

First about ladder slope: a ladder base should be about 1 foot out from vertical for every four feet of elevation. So if a ladder has to ascend eight feet its base needs to be two feet out from vertical.

Second, while dimensions may vary, a typical stepladder has about 10" or 10 1/4" between the surfaces of ascending steps. I have long legs and could live with your 11.75 but that may be a bit much for other users.

Third: you might have an issue with a building code inspector or with a real estate appraiser IF the cabin loft is intended to be counted as occupied space, for example as a bedroom or sleeping area, then accessing it by ladder might be questioned. Ladders are of course permitted in buildings as are pull-down stairs, to access non-habitable spaces such as attics, storage areas, mechanical areas;

Fourth: With a three foot width for your ladder, handrails on both sides would be adequate; using actual stair codes as a reference point,

For a stairway with a handrailing along both sides, the clear stairway width is permitted to be smaller still, with a clear width of 27".

Finally, for safety you may want guardrailings around the ladder opening on the loft floor.

In the 1970s I built a loft accessed by a site-built ladder; my youngest daughter Mara was in diapers but at the point where when she woke during the night with a wet diaper she wanted a dry one. She learned to climb the ladder up to the loft, holding a dry replacement diaper in one hand, asking to be changed. But this is not a safety procedure that I would recommend to others.

On 2021-01-10 by MICHAEL DAVID PETERS

Im building a cabin iwth a loft and need advice on a permanent loft ladder verses steps. First, I have room for 30 degree ladder or stairs, however my risers will have to 11.75 inches. Should I go with a ladder which allows for 14 inch maximum or go with stairs, if allowed? Also, if I go with a ladder, is there maximum distance between rails. The minimum isn't a problem. I have 3 feet of space. But without middle support don't know how wide I can made the ladder. There will be handrails. full height landing at the top and bottom.

On 2020-11-25 - by (mod) -

Robby,

If it's not occupied space I don't think the height restriction will pertain.

But if you want to see the code take a look at STAIR PLATFORMS & LANDINGS https://inspectapedia.com/Stairs/Stair_Landings.php

where among other guidelines you'll see

Using the 2003 IRC as a stair landing code example, we obtain the requirement for landings at the top and bottom of the stairway and a maximum stair rise of 12 feet before an intermediate landing is required.

On 2020-11-25 by Robby

How many steps are allowed in a straight run from garage to attic?

On 2020-11-06 - by (mod) -

James

A safety railing around the opening in the Attic floor for the pull down stair is a good idea. However is if the attic is not being used as living space it's not likely that your local Building Code Compliance inspector is going to require that measure

On 2020-11-03 by james bogle

on pull down stairs for the atic do you need railing at top floor so it prevents a person falling back through the opening of the stairs

On 2020-10-02 - by (mod) -

Not that I've found, in codes, Alan but there is an obvious need for minimum safe access space into an attic. I've seen ladders that opened such that the direction of travel smacked the user's head into the roof deck, through which nails protruded to give a nasty laceraion; that's the going-up hazard.

The going-down hazard is horrible too as it's difficult to get onto the ladder safely.

On 2020-10-02 by Alan

Is there a minimum landing space at the top of the attic access ladder for non-livable space / attic in the direction of travel?

Unsafe top step on attic pull-down stairs (C) InspectApedia.com KevinOn 2020-09-14 by (mod) - unsafe attic pull down stair top step riser height

Kevin

That uneven rise in the top step shown in your photo is a serious trip/fall hazard. Your local building code inspector is the final authority. She MIGHT leave you alone on this stair as it's not an access to occupied space, but the safety hazard remains

While maximum stair tread riser height and depth are specified in the stair codes cited at the end of this article, that does not pertain to pull-down attic stairs that are considered as an access to a limited-use non-occupancy area of a building. You'll see more specifics on attic stair access codes cited below in my answer to Pat.

On 2020-09-14 by kevin

Is there any specific code in Texas concerning the distance between the floor of an attic and the top step of a pull-down access ladder? It seems to be a larger than normal step from the top of the ladder into this attic.

On 2020-07-23 by Rick s

For storage attic what is the maximum riser height and minimum tread width?

On 2019-12-16 by (mod) Building Codes for Attic Access Stairs

Pat

Access to non-occupied space such as a storage attic is not generally ruled by stair codes; But attic access IS mentioned in the model codes, for example the International Residential code IRC–12/13 Section R807.1

IRC 807.1 Attic access

In buildings with combustible ceiling or roof construction, an attic access opening shall be provided to attic areas that exceed 30 square feet (2.8 m 2 ) and have a vertical height of 30 inches (762 mm) or greater. The rough-framed opening shall not be less than 22 inches by 30 inches (559 mm by 762 mm) and shall be located in a hallway or other readily accessible location.

A 30-inch (762 mm) minimum unobstructed headroom in the attic space shall be provided at some point above the access opening. See Section M1305.1.3 for access requirements where mechanical equipment is located in attics.


That paragraph simply requires that attic access be provided - depending on space and use; it might simply be a hatch; However for attics with mechanical equipment a pull-down ladder or folding stair would be required.

IRC Section M1305.1.3 sets access requirements where mechanical equipment is located in attics. Where this code applies - for example if YOUR attic contains mechanical equipment (like an air conditioner or heat pump air handler) then this code applies:

IRC M1305.1.3 Appliances in attics.

Attics containing appliances requiring access shall have with an opening and a clear and unobstructed passageway large enough to allow removal of the largest appliance, but not less than 30 inches (762 mm) high and 22 inches (559 mm) wide and not more than 20 feet (6096 mm) long when measured along the centerline of the passageway from the opening to the appliance.

The passageway shall have continuous solid flooring in accordance with Chapter 5 not less than 24 inches (610 mm) wide. A level service space at least 30 inches (762 mm) deep and 30 inches (762 mm) wide shall be present along all sides of the appliance where access is required. The clear access opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm) by 762 mm), where such dimensions are large enough to allow removal of the largest appliance.

Exceptions:

1. The passageway and level service space are not required where the appliance can be serviced and removed through the required opening.

2. Where the passageway is unobstructed and not less than 6 feet (1829 mm) high and 22 inches (559 mm) wide for its entire length, the passageway shall be not more than 50 feet (15 250 mm) long.

Typically a building code compliance inspector might accept such an attic accessed through an operable hatch with no pull-down folding ladder or steps, but she would in that case most likely require that there be adequate space below the hatch to set up a ladder of sufficient size to give access.


So in sum your folding stair, if installed, needs to be usable but I don't think we'll find a provision in the model codes that say it has to be accessible without having to resort to an accessory such as a string, pull-down rod, or temporary stepladder.

(Though in my OPINION an installation that makes it difficult to use the pull-down stair is foolish.)

If your fold-up attic access ladder reaches fully from attic level to floor below so that it is, once opened and un-folded, usable by itself to access the attic, then I speculate (as I can't see your situation) that perhaps all that's needed is a longer pull-down string, or a lightweight pole with a hook on its end used to grab and pull down the stair. Continuing:

Specifically New York City attic access code specifications at -

27-375 Interior stairs - includes this text:

New York City Stair COde 27-375 Interior stairs (3)

In buildings or in building sections classified in occupancy group J-1 or J-2 two stories in height and in occupancy group J-2 three stories in height with not more than one dwelling unit per story with roofs having a slope of fifteen degrees or less, access to the roof shall be provided through a scuttle at least twenty-one inches in width and twenty-eight inches in length and shall comply with subdivision (c) of section 27-338 of article four of subchapter five of this chapter. Scuttles shall be located within each stair enclosure with a stationary iron ladder leading thereto.

And depending on building classification, a permanent iron ladder may be required by New York City code:

Title 27 / Subchapter 6 §[C26-604.8] 27-375 Interior stairs. - Interior stairs shall comply with the following requirements:

(k) Roof access. -

(3) In buildings or in building sections classified in occupancy group J-1 or J-2 two stories in height and in occupancy group J-2 three stories in height with not more than one dwelling unit per story with roofs having a slope of fifteen degrees or less, access to the roof shall be provided through a scuttle at least twenty-one inches in width and twenty-eight inches in length and shall comply with subdivision (c) of section 27-338 of article four of subchapter five of this chapter.

Scuttles shall be located within each stair enclosure with a stationary iron ladder leading thereto.

On 2019-12-15 by Pat

I have question regarding attic ladder in NY city. Contractor installed attic ladder but I have to use other ladder to pull down and fold attic ladder. Is it acceptable according building code safety?
Thank you .

On 2019-12-02 - by (mod) -

never pay for a job before you are satisfied that it's correct.

Ask the installer to come back to install the stair properly so that it is safe and usable.

On 2019-12-02 by Bobbie

The installer put the ladder in the opposite way the original one was because the legs were the wrong size. Now I can't get up into that attic because at the top there's just insulation not wood flooring, its also at the slant if my roof and between two rafter beams. I didn't notice how bad this was this until I went up to get my Christmas stuff. Can they do that

On 2019-11-24 - by (mod) -

Richard

As long as a spaces intended for occupancy or regular used by the building occupants then the destination of the stair does not change the standard requirements for stair tread and riser Dimensions indoor handrails are other stair construction details.

If your loft is a storage only area and it's not normally in a regularly accessed, then regular stair rules don't apply.

On 2019-11-24 by Richard

Width of stair tread going to a loft area

On 2019-03-05 - by (mod) -

Jerry

Generally the ladder manufacturers hire a label printing company or service to print the necessary labels to their specifications. I haven't seen generic ladder capacity labels for sale and I suspect that's because the detailed requirements vary among products, markets, and manufacturers.

On 2019-03-05 by Jerry

Where can I buy Attic ladder capacity label?

Reader Question: what would be the right way to provide attic access?

(Nov 26, 2012) salah

So, what would be the right way. Is there a link in this page that takes you to examples or recommended construction of stairs to the attic? Also, if the attic is considered a livable space, doest that change the building code of the stairs?

Reply:

Salah,

If you've got some specific questions I'll be glad to research and address them here.

There is no single "right" way to construct attic stairs, as there are so many varying circumstances.

Attic access "stairs" range from a normally pitched stairway with railings, even landings, headroom, lighting, etc. to pull-down folding stairs, to ladders, to open hatches that must be accessed by a temporary ladder.

Attic space is not livible space for purposes of bedrooms in most jurisdictions because of fire egress issues.

But I'd agree that if a finished attic floor and space were considered as habitable space, say for an office, there must be safe stairs built to normal stair codes. And your local building department may require a fire exit or other egress.

Reader Question: attic access over a basement stairway

(Dec 28, 2012) JoAnn

Hi,
My attic ladder was installed in the ceiling above my basement steps. It was a new home and passed inspection.

The hose is over 40 years old and the attic ladder has not been a problem. However, we are replacing the wood ladder with aluminum and I think I read somewhere, according to building code, that the ladder must land on the first step at the top of the stairs when installed over existing stairway. Are you familiar with this code? Thanks for your help.

Reply:

I've often seen pulll-down stairs to an attic that extended downwards to land on a stairway themselves. Depending on the direction of travel and considering the absence of a landing this is not an easy-to-use nor particularly safe design (in my OPINION) even where permitted.

But for spaces that are not designed for occupancy, for example spaces accessed only for inspection or to service mechanical equipment, exceptions to standard stair design are often permitted.

No I've not found a building code citing that an attic pull down stair into a stairwell is acceptable if it lands on the first step of the stairway. More likely it'd be a non-issue if the pull-down stair landed on a level walking space with at least 36" of clear landing in the direction of travel.

Reader Question: California requirements for attic stairs

5/31/2014 Maggie McGee said:

Hello, Can you tell me the CA rules - Monterey Co. in particular - for new staircases leading to storage attics? The attic will not be used for anything but storage. The stairs rise (8") and run (9") number of 17 stairs and width is 36" with railing on one side.

The building inspector says these aren't "to code" but architect says they are "to code for stairs running to un-livable space". The inspector wants us to tear out completely or will red-tag our home. We just moved back in 18 mos. after a house fire.

I feel the inspector is being ridiculous. Our old ladder access to attic is much more dangerous than these stairs. Can you offer any advice or at least tell us our architect is wrong? We have 19 days left before we need to "vacate". Thank you for any help whatsoever, Maggie

Reply:

Maggie,

The local building inspector has final legal authority and must be satisified. And often the building regulations call for on-site or plan-review judgments of design and safety.

If you want to deviate from what the Monterey County building department says you should do you might start by asking if the department will accept a plan or drawing by a licensed design professional - your architect for example.

In a pinch, to avoid code issues, you may be able to satisfy the inspector by installing a pull down attic access stair that enters the access through a scuttle opening.

I also agree with the building department that a 9" stair run depth for treads is undersized and a fall hazard. It would not be acceptable as an access to occupied space.

But many model, state and local building codes codes allow different rules for non-occupied spaces such as storage attics, lofts, and utility areas.

Where you might get into trouble about whether an attic is non-living-space is if you constructed what you are calling an "attic" but to the building inspector by size, location, and finish (e.g. drywall installed) appears to be a space that could be occupied in the future. Your inspector may also hold the view that if you build a permanent stairway then the area being accessed could b considered an additional story in the home.

...

Continue reading at STAIRS, RAILINGS, LANDINGS, RAMPS - INSPECTIONS, CODES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see ATTIC STAIR CODE & HAZARD FAQs - questions & answers posted originally at this page

Or see these

Recommended Articles

Suggested citation for this web page

ATTIC STAIR CODES & HAZARDS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to STAIRS RAILINGS LANDINGS RAMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT