InspectAPedia®

Fire stopping at a chimney (C) Carson Dunlop Associates Fire Stopping Requirements at Chimneys

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Chimney construction: fire stopping.

This article describes the basic requirement for fire stopping needed where building chimneys or flues pass through building floors.

Fire stopping is a measure taken to slow the spread of fire between building floors - an event that could occur at openings cut to permit a chimney to pass through from one floor to another.



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

Fire stopping at Chimney Passage Through Building Floors

Due to the drying of lumber and movement in structures the chimney shaft must remain free of any ties into the framing of the building. The space between the shaft and the building is or can be sealed with "fire code" [fire-rated] sheetrock or metal flashing if a fire stop is required between floors.

Fire stopping at a chimney (C) Carson Dunlop Associates Fire stop at metal chimney (C) Carson Dunlop Associates

Chimneys that pass through several floor levels of a home may be required to be fire stopped at each penetration. Typical fire stops are sheet metal or fire code sheetrock.

Carson Dunlop Associates [at REVIEWERS] sketch shows fire stopping at the fire-clearance gap provided between the chimney and wood floor framing (above left) and fire stopping around a metal chimney as it passes through building floors (above right). Sketches here were provided courtesy of Carson Dunlop. [Click to enlarge any image]

Other Common Examples of Indoor Fire Clearance Safety Hazards

Fire clearance too close to combustibles (C) Daniel FriedmanWe often find flue vent connectors routed too close to combustible wood framing or, as in our photo at left shows, too close to other combustible materials such as the foam insulation just a few inches above this flue pipe.

Many building fire safety codes specify that the fire clearance between a flue vent connector and combustibles needs to be that specified by the appliance manufacturer.

Indeed some modern heating appliances permit pretty close clearances, as little as a few inches.

In the absence of a manufacturer's specification, we want to see at least 18" between the flue and the nearest combustible surface.

The reason for Fire Clearances from Wood Materials

The reason that building codes specify a healthy distance between wood materials (or other combustibles) and flue vent connectors is not just that the heat from the flue will immediately set the wood on fire. Rather it is also that wood that has been heated over time, even to the relatively low temperature of 200 to 300F, will be chemically affected to become more readily combustible.

Details are at PYROLYSIS EXPLAINED - separate article

Fire Stopping where Chimneys Pass Through Closets, Walls, Floors

Fire blocking foam insulation installed at the passage of a metal chimney through a building interior partition wall (C) Daniel FriedmanWhere a metal chimney passes through building walls or floors fire blocking or use of a fire-blocking foam insulation may be required by local building codes.

At left you can see the orange fire-block foam spray insulation that oozed out from the partition wall that was sealed with this material. The building inspector also required us to trim away the excess foam.

NHFireBear, a frequent contributor to InspectApedia commented:

Ideally, there should be no unsealed openings from your closet to the attic, since any fire in the closet would naturally convect into the attic, possibly spreading the fire in an area where there are not smoke alarms or heat detectors.

That would create a life-threatening hazard to anyone in the building, if that were to happen. The ceiling should have a pass-through "ceiling mount" thimble/support, listed for the purpose (connector below, chimney above), and the chimney pipe through the roof should have shielding around it (metal hardware cloth, solid metal or solid wood), where it passes through the attic, to prevent combustibles from coming into direct contact with it.

A chimney fire should preferably stay in the chimney (even at 1,500 degrees) at least long enough to get the fire department there to save the roof.

Combustion air may be drawn into the burner either from a louvered closet door or from a properly installed air pipe from the outside or the attic, terminating in the burner or within a foot of the closet floor. Some local jurisdictions do allow gas-fired burners to have an unsealed overhead vent OUT to the attic.
- NFPA 54 (2009): FIGURE A.9.3.3.1(1)(a).

I would prefer not to have that hazard for the citizens and firefighters in my town. The same is not allowed for OIL-fired burners.
- NFPA 31 (2011): 5.4.3.1.

- NHFireBear 10May 2015 [This comment was originally posted at FIRE CLEARANCES, SINGLE WALL METAL FLUES & VENTS

This article series on chimneys, chimney construction, and chimney safety provide detailed suggestions describing how to perform a thorough visual inspection of chimneys for safety and other defects. Chimney inspection methods and chimney repair methods are also discussed.

...


Continue reading at FIRE & SMOKE DAMPERS, AUTOMATIC or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see these

Fire Stopping & Fire Clearance Articles

Suggested citation for this web page

FIRE STOPPING in BUILDINGS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING FIRE SAFETY

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman