Building Inspection, Diagnosis & Repair Info
InspectAPedia®   -   Search InspectApedia

New York city fire escape (C) Daniel Friedman at InspectApedia.comFire Stairs & Fire Escapes

Fire Escape Stair Construction Codes,
Design Specs, Measurements, Clearances,
History of Fire Escapes

Fire escape stairway width requirements & the history of building fire escapes for both residential properties and larger, multi-story buildings are described here, including both indoor fire stairs and outdoor fire escapes.

Page top photo: an exterior fire-escape on a six-story New York City building.

This article series lists all major building code specifications for stairs, railings, landings, and guardrails - information useful for constructing or inspecting indoor or outdoor stairs, railings, landings, & treads, and for evaluating stairways and railings for safety and proper construction.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Stairway Widths for Escape Stairs & Fire Escapes

Outdoor fire escape stairs on a Poughkeepsie NY home (C) Daniel Friedman at InspectApedia.comFire safety codes specify a number of parameters including dimensions for indoor fire-stairs as well as outdoor fire escapes - as we will describe here.

Components of fire escape stairways shall be constructed of noncombustible materials. Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.78 kN/m2).

Fire escape stairways and balconies shall be provided with a top and intermediate handrail on each side.
...
The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escape stairways shall extend to the ground or be provided with counterbalanced stairs reaching the ground.

Exception: For fire escape stairways serving 10 or fewer occupants, an approved fire escape ladder is allowed to serve as the termination.

- excerpts from the New York City Fire Escape Code cited below.

Photo: a third floor fire escape required by local building code officials for a Poughkeepsie, New York home whose third floor is used as a sleeping area.

[Click to enlarge any image]

US Fire Stair Widths

 

UK Escape Stair Widths:

Escape stair widths in the UK - at Inspectapedia.com source cited in detail

Above: escape stair width for the UK excerpted from UK FIRE SAFETY, VOLUME 2 cited below. See p. 45-46 in that document.

[Click to enlarge any image]

Escape stair widths in the UK - at Inspectapedia.com source cited in detail

For stairs that form part of means of escape, refer to Approved Document B: Fire safety, Volume 2 – Buildings other than dwelling houses.

Fire Stairway Width Codes & Standards

Also see the discussion of the derivation of the necessary stairway width from human dimensions and walking habits, including the 44-inch width requirement for Class A stairways, found at

Window Size for Fire Exits or Access to Fire Escapes

Example U.S. Natioanal Fire Escape Codes

Fire Escape & Fire Stair Codes

The following examples are from the New York City and New York State fire escape codes.

The window or door giving access to fire-escapes shall not be less than two feet (2') in width and the sill of the window shall not be more than three feet (3') above the floor. Window openings shall be not less than two feet six inches (2'-6") high in the clear.

Local New York City LAW 11 requires Fire Escapes that are 7 stories and above to be inspected AND certified every 5 years. New York State's fire escape code requires Fire Escapes to be inspected AND certified every 5 years.

 

Examples of Unsafe Buildinug Fire Stairs & Fire Exits

Outdoor fire escape unsafe, blocke by heavy growth of vines (C) Daniel Friedman at InspectApedia.com

Fire stairs or outdoor fire escapes are also unsafe if use of the stairway is blocked by stored items or by overgrowth of vines or plants, or if the required exit platform and stair guards are missing - shown below.

Fire escape platform missing guard rails in Hudson NY (C) Daniel Friedman at InspectApedia.com

Illustrated below, local building codes may require construction of an exterior fire-stair even at residential buildings like this Wappingers Falls, NY home, when the home's third floor is to be used as a sleeping area.

In our OPINION the wood fire stair shown in our photo is unsafe lacking proper stair guards, graspable handrailings and other features.

Unsafe wood fire stairs in a New York Home (C) Daniel Friedman at InspectApedia.com

History of Early Fire Escapes in the U.S.

Fire escapes on a New York City Building (C) Daniel Friedman at InspectApedia.com

Above: fire escapes in New York City (2018)

Wood's 1880 fire escape patent illustration cited & discussed at InspectApedia.com

Above and below: illustrations of early fire escape patents in the U.S. by Wood (1880) and Vieregg (1898).

Vieregg's 1898 Fire Esacape Patent cited & discussed at Inspectapedia.com

A New York City 1867 tenement law was the first to require that its buildings install fire escapes. The first patented fire escape designs in the U.S. were not registered until the 1880s, as we illustrate here.

You will note that some of the earliest "fire escape" patented designs (Murphy, 1892 & Ockers, 1900) allowed one person at a time to be lowered from a building's roof or window - not, in our OPINON, a design that could come close to meeting the need to quickly and safely evacuate large numbers of building occupants in the event of a building fire.

An early fire escape idea was from Sperry (1883) who proposed a small cannon or "gun" that could shoot up a rope to permit lowering an outdoor elevator attachment on the building - shown just below and perhaps a solution we'd view today as rather dubious but so remarkable that we include detail from Sperry's explanation of how the gun-fired rope and building-attached windlasses would be used. The anchors themselves might be an expansive device that was to be literally "shot" into and thence adhered to the building's wall.

Sperry-fire-escape-patent-US276090 cited & discussed at InspectApedia.com

The rope-carrying projectile suggested by Sperry was to spear itself into the building wall with sufficient force and of adequate design to then support the lowering of people by rope safely to the ground below.

Sperry-fire-escape-patent-US276090 cited & discussed at InspectApedia.com

A similarly dubious fire escape design was described by Betten (1889). Betten provided a special rope-reinforced jump-suit to which a chest-harness control would be strapped to allow the wearer to lower herself out of a building's window using ropes and a double-wheeled pulley.

Other early fire escape patents in the U.S. focused on individual rescue systems that might even have been carried by or provided for individual travelers such as traveling salespeople. (Fell, 1883).

The Wood and Viregg patents provided for a ladder that could be lowered to permit multiple people - at least those physically able - to clamber down to safety.

Any discussion of fire safety and fire escapes must include acknowledgement of the terrible Triangle Shirt Waist Company fire that occurred in New York's Greenwich Village on Saturday afternoon, March 25, 1911.

The top three floors of the building were the site of the factory which was New York's largest fabricator of what was at the time a popular design: the high-necked shirtwaist. The company had been successful in preventing union efforts to improve the safety of working conditions for women.

When the fire broke out there was no escape, in fact doors were locked, probably to prevent workers from sneaking off to take a work break. In less than half an hour 146 young Jewish and Italian immigrant workers, all but 13 young women, died in the fire - some having leapt to their death from the windows of the top floors of the building, others trapped inside.

Below we summarize a history of early attention to the need to escape from a building fire by a sequence of the earliest U.S. patents for various types of fire escapes - none of which availed the women in the Triangle Shirt Waist factory fire.

But even the most cursory reading about this early and tragic fire should make clear that early fire escape designs that provided for the escape of one person at a time down a rope or in a lowering device would have been completely inadequate to handle the fire escape needs for the occupants or workers in large, tall, buildings.

Fire Escape History in Patents

Fire escape in Hudson New York in 2024 (C) Daniel Friedman at InspectApedia.com

Above, a rather antique fire escape on a building in Hudson New York in 2024.

Below: the High fire escape patent illustration.

High-Fire-Escape-Patent-US316969 cited & discussed at InspectApedia.com

Below, John Betten's fire escape design includes a rope-reinforced jumpsuit.

Betten-fire-escape-patent-US416550 cited & discussed at InspectApedia.com

Below: the Murphy/Rankin 1892 fire escape patent design.

Murphy fire escape patent No. 484042 cited & discussed at InspectApedia.com

Ocker's 1900 Fire Escape patent No 659093 cited & discussed at InspectApedia.com

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Minimum requirement for width of a exterior steel fire escape staircase?

What is the minimum requirement for width of a exterior steel fire escape staircase? On 2019-07-31 by Joe Caruana

Answer by (mod) - emergency egress minimum stair widths

Joe,

If you are in the United States, since 1914 the recommended exterior exit / fire stair minimum width is 44-in for exit stairs (unobstructed width except that handrails would be permitted to intrude not more than 3 ½ in on each side).

Keep in mind that the type of stair permitted and its width will vary depending on

- the type of building and stair class (A B C)

- the building occupancy (including number of people) typically referred to as "occupant load per floor"

Class A - 44 in stair width

Class B - same width as A but different riser height rules

Class C - in existing buildings: stairs at least 36" wide, with no less than 32" between handrails

Detail:

Clearly, the current 44 in (1100 mm) minimum exit stair width is intended to support two queues of occupants either standing still (capacity method) or moving down the stair (or a single queue of occupants moving down and being passed by firefighters
moving up, known as counterflow).

- readers interested in a superb and thoughtful exposition on stairway design, human flow up and down stairs, design concepts should see this paper:

See details about fire escape stair widths for the U.S. and U.K. at

FIRE ESCAPES & FIRE STAIRS - you are on this page

...

Continue reading at BUILDING CODES for STAIRS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FIRE ESCAPES & FIRE STAIRS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to STAIRS RAILINGS LANDINGS RAMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING FIRE SAFETY

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

article above, a full list is available on request.

  • ADA (Americans with Disabilities Act), Public Law 101-336. 7/26/90 is very often cited by other sources for good design of stairs and ramps etc. even where disabled individuals are not the design target.
  • "A Parametric Study of Wall Moisture Contents Using a Revised Variable Indoor Relative Humidity Version of the "Moist" Transient Heat and Moisture Transfer Model [copy on file as/interiors/MOIST_Model_NIST_b95074.pdf ] - ", George Tsongas, Doug Burch, Carolyn Roos, Malcom Cunningham; this paper describes software and the prediction of wall moisture contents. - PDF Document from NI
  • [12] Slips, Trips, Missteps and Their Consequences, Second Edition, Gary M. Bakken, H. Harvey Cohen,A. S. Hyde, Jon R. Abele, ISBN-13: 978-1-933264-01-1 or ISBN 10: 1-933264-01-2, available from the publisher, Lawyers ^ Judges Publishing Company,Inc., www.lawyersandjudges.com sales@lawyersandjudges.com
  • [13] Slips, Trips, Missteps and Their Consequences, Gary M. Bakken, H. Harvey Cohen, Jon R. Abele, Alvin S. Hyde, Cindy A. LaRue, Lawyers and Judges Publishing; ISBN-10: 1933264012 ISBN-13: 978-1933264011
  • [14] The Stairway Manufacturers' Association, (877) 500-5759, provides a pictorial guide to the stair and railing portion of the International Residential Code. [copy on file as http://www.stairways.org/pdf/2006 Stair IRC SCREEN.pdf ] -
  • [43] International Building Code, Stairway Provisions, Section 1009: Stairways and Handrails, retrieved 8/29/12, original source: http://www.amezz.com/ibc-stairs-code.htm [copy on file as IBC Stairs Code.pdf]
  • [44] Model Building Code, Chapter 10, Means of Egress, retrieved 8/29/12, original source: http://www2.iccsafe.org/states/newjersey/NJ_Building/PDFs/NJ_Bldg_Chapter10.pdf, [copy on file as NJ_Bldg_Chapter10.pdf] adopted, for example by New Jersey. International Code Council, 500 New Jersey Avenue, NW, 6th Floor, Washington, DC 20001, Tel: 800-786-4452
  • Washington State SAFETY STANDARDS for CONSTRUCTION WORK Part J, STAIRWAYS [PDF] Chapter 296-1655 WAC, Part J, STAIRWAYS
  • WASHINGTON STATE STAIR CODE WAC 296-155-477 [PDF] retrieved 2017/12/10,
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT