Draft Measurement Guide for Chimneys & Flues
How to measure draft at heating equipment or at chimneys.
This article explains the methods of measurement and proper adjustment settings for draft regulators or barometric dampers on oil fired heating equipment.
We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.
Page top photo: my draft gauge sits atop the water heater (arrow 1 at left in the photo) and its measuring tube has been inserted into a test hole in the breech or flue vent connector of this oil fired boiler (arrow 2 in the photo).
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
As we explain at our home page for this topic,
DRAFT REGULATOR, DAMPER, BOOSTER,
a barometric draft control, also called a "damper" or barometric damper, is a hinged, weighted door on an opening at a heating flue.
Barometric dampers are used on oil-fired heating appliances (furnaces, boilers, water heaters) to assure constant draft and thus uniform combustion.
Without this regulation (hence the term "draft regulator") as building and outdoor conditions vary (wind, doors open or shut, temperature etc), the draft seen by the heating appliance will vary, making maintenance of proper combustion conditions at the oil burner impossible.
A typical draft regulator is deceptively simple: The hinged door opens or closes to let extra air into the flue to assure that the draft in the flue remains constant at the proper setting needed for proper heating system operation.
Details about draft control for gas fired heating systems, including LP or natural gas fueled furnaces or boilers, are discussed separately
at DRAFT REGULATORS / HOODS GAS HEATERS On gas fired equipment.
...
Normally we measure draft at two locations: over the fire or in the combustion chamber where typically we may see -0.02 to -0.03 inches of water column pressure, and in the breech or at the stack pipe (properly, the flue vent connector) measured just a few inches above the boiler or furnace top, and before the barometric damper itself.
[Click to enlarge any image]
Notice that we're using negative numbers for draft measurement - that's because gases in the flue are moving up, up, and away, like superman, and onwards out of the building - away from the heating equipment.
The gas pressure in the chimney needs to be less than atmospheric pressure in the boiler room for gases to leave.
This sketch of a barometric damper used on oil fired heating equipment (heating boilers or water heaters) is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
In the breech we want to see about -0.05 inches WC pressure for typical oil fired heating equipment.
If the breech draft is too low the combustion process and venting process may be inadequate, and if the draft measured in the breech is lower than the draft measured over the fire, the oil burner and combustion chamber are operating under pressure - which is often a problem on residential heating systems since few of them are designed to work this way. Thanks to reader L. - for correcting our WC pressure data.
Photo above: draft gauge at left (arrow 1) and measuring draft in the breech before the barometric damper (arrow 2).
We do not measure draft in the flue vent connector past the barometric damper since the damper is regulating the draft and we're not seeing what the oil burner is seeing at the fire.
Lots of companies make draft gauge measurement devices, including Bachrach™, and including nice little pocket units that anyone can carry.
Our photo (left) shows a traditional Bachrach kit draft measurement gauge in use (green arrow) and its connection to the flue vent connector at the top of a boiler (red arrow) that in this case had no barometric damper installed.
This boiler had a poor draft, a history of sooting problems and a too-short chimney that we were in process of replacing when these photos of draft measurement procedure were made.
At this New York home (photos just above and below) the draft in the breech was running at about -0.02" w.c. - it should have been at least twice that amount.
Above you can see that the draft was hovering around 0.02" and below you can see our connection of the draft gauge sensing probe into the flue vent connector just above the boiler top.
...
In sum the draft we typically see on oil fired heating equipment is
Note: wood stoves, coal stoves, pellet stoves, and catalytic wood stoves have different draft requirements.
See details at
...
By moving a weight along a scale. You can see a weight and scale in our photo of the Field Type AF Draft Control.
In general, for oil fired heating equipment the draft regulator is set to the lowest draft that gives good combustion and proper oil burner operation. Higher wastes energy.
While the heating equipment is operating at normal temperature, the draft is set to a number specified by the oil burner manufacturer, so we can only give approximate settings in this discussion.
To find the proper weight setting to control the draft regulator, the heating service technician will make three measurements - for oil fired heating equipment
It is the position of the weight along a moveable scale,
usually by screwing the weight in or out, or by sliding the weight along a scale (see our photo), that adjusts how far the draft regulator door will open in response to these three conditions described above.
It's basically a principle of leverage - the weight is moved closer to or farther out from the axis of rotation of the moving draft regulator door.
So do not change the barometric draft control's weight setting
unless you're a trained service technician who knows when, where, how, and why to measure draft at an oil fired heating appliance.
Watch out: other heating fuels and other heater types such as woodstoves, coal stoves, and pellet stoves each will have its own draft setting requirements. Be sure to read the proper instructions that fit the device whose draft you are regulating.
Example: a woodstove using a catalytic combustor may require a draft setting of 0.05" WC
See details at WOOD STOVE, CATALYTIC PUFF-BACKS
See also PELLET STOVE DRAFT CONTROL
...
In the heating industry, traditionally draft measurements around -0.02" w.c. are considered "low", and around-0.06" w.c. are "high" draft levels.
After we replaced the too-short chimney with one of proper height, and with a draft regulator (barometric damper) now installed at the boiler top, our measurement showed that we had a good draft in the flue vent connector - almost 0.06" w.c. in the breech (photo above left).
In our chimney replacement photo (above right) the new chimney extending 24" above the roof of a new addition (green arrow) is much taller than the original 20" chimney (red arrow). That's how we got good draft in the new chimney set-up.
See details of diagnosing and fixing chimney draft problems found at
...
Weight location & adjustment on barometric draft controls: the weight that is adjusted to regulate the operation of the draft control needs to be properly located as well as adjusted.
The weight location switches on most regulators depending on whether the regulator is installed on a vertical flue or a horizontal flue. Field ships their draft regulators with the weight installed in position for a vertical flue.
The adjustment weight is in the right-hand slot when you are facing the control. If the damper is to be installed on a horizontal flue, the weight must be removed from the right-hand slot and attached to the left hand slot as shown in the illustration and sketches above.
Thanks to boiler expert Dirk Faegre for suggesting these additional details.
Because chimney defects also can have a severe effect on draft seen by the heating appliance, readers should also
see details at
...
This multi-dial gauge provides critical information used to assure safe and proper function of the oil burners used to heat water to steam in the Pratt Engine Room steam boilers.
From left to right, this gauge measures wind-box pressure, furnace draft and uptake draft. Here the term "furnace" is being loosely applied as these are boilers. (Furnaces heat air, boilers heat water.)
The center gauge or "furnace draft" on most oil burners is measured in the combustion chamber right over the burner and is a critical data point.
Photo provided courtesy of NY photographer / director Dustin Cohen.
At STEAM BOILERS GENERATORS CONTROLS, PRATT we describe the multiple-readings of the draft gauge shown above.
...
Above: one of my favorite draft tools is this little Bachrach Draft-Rite that fits into a shirt pocket. Here the tool's probe has been inserted into the flue vent connector above a heating boiler.
When the hole is much larger than the probe Bachrach advises sticking the probe well into the flue (6 inches).
Below: a view of the Draft-Rite showing its zeroing opening covered by my thumb. With the hole covered and the gauge held upright it is turned until its pointer is at zero. At that point you're ready to take a draft measurement.
Below: view of this draft measuring tool showing the zeroing opening on its back and the detachable probe that, once assembled and screwed into the gauge back opening, is inserted into the flue vent connector opening or over the fire to measure draft.
Watch out: you would not actually make a measurement with the tool held as shown, as it's got to be upright and leveled with its pointer zeroed first, as shown above.
Below: The Bachrach DraftRite tool assembled, ready for use
Below: an example measurement of draft using the Draft-Rite showing - 0.04" of water or "negative" draft or "updraft. This gauge can measure updraft (on the right-hand scale) as negative numbers or updraft, or the tool can measure downdraft (on the left-hand scale) as positive numbers or pressures.
The gauge is reading just over 0.04" of water negative draft or "updraft" in a flue or chimney.
See also these
...
Checking the wood stove draft helps manage the fire's strength, heat, and assures proper exhaust venting.
Wood stove damper control: adjusts the rate of exhaust of combustion gases and smoke from the woodstove up into the chimney. More exhaust = hotter fire and less heat transfer into the room; Less exhaust = slower, smaller fire.
Shown here: our yellow arrow points to the draft outlet control on this wood burner.
A simple empirical test of woodstove draft adequacy is to watch the fire when you close-down or open-up the air inlet control to your woodstove.
Fire is brisk and the only combustion air inlet is through the normal stove's combustion air inlet: this shows that there is a good draft.
Fire doesn't change: If even after watching for a minute or two you see no change in the wood stove fire's height or level of activity when you change the air inlet settings, then look for draft problems and their cause
See details on how to measure, test or adjust the draft at a woodstove
and in that article also see
...
Our reader asked:
During a "Back Puffing" event what would the draft measurement be above the flue collar?
And let me also ask, is it unreasonable to expect a catalytic wood stove to work properly with a draft at the collar between .04 and .08 inches of H2O ?
Properly meaning no fumes being pushed out during operation. (2021-12-06) JR
Illustration, one of three models of the Blaze-King KE40 catalytic combustor woodstove cited in more detail below.
Reply by Inspectapedia Com Moderator - puff-backs or back-puffing woodstove using a catalytic combustor
@JR,
Short answer: check with what your manufacturer says, or start with 0.05" of water column. You also want to check the operating temperature of your stove and you want to assure that the catalytic combustor remains bypassed until the stove is at proper operating temperature.
In your initial question you asked about draft associated with a "puffback" and we thought you were referring to the explosive force that we describe below, associated with a malfunctioning oil burner.
But from the ensuing discussion it looks as if we're actually discussing a type of "puffing" or "puff-back" that occurs specifically in catalytic-type wood stoves - wood burning stoves that use a catalytic combustor to extract more heat out of the burned-wood than a conventional wood stove.
To have room for a complete and detailed answer, we've moved your question and our reply to a new page now found at:
WOOD STOVE, CATALYTIC PUFF-BACKS
Please review those details and don't hesitate to post any new comments or questions.
...
In the oil heating industry, “draft” describes the vacuum, or suction, which exists inside most heating systems. The amount of vacuum is called draft intensity.
Draft volume specifies the cubic feet of gas that a chimney can handle in a given time.
Draft intensity is measured in “inches of water”.
Just as a mercury barometer is used to measure atmospheric pressure in inches of mercury, a draft gauge is used to measure draft intensity (pressure) in inches of water.
Natural Draft is thermal draft. It occurs when heated gases expand.
A given volume of hot gas will weigh less than an equal volume of the same gas at a cool temperature.
Since hot combustion gases weigh less per volume than room air or outdoor air, they tend to rise.
The rising is contained and increased by enclosing the gases in a tall chimney. The vacuum is then created throughout this column of hot gases.
...
...
Continue reading at CHIMNEY RESERVE DRAFT MEASUREMENT or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see DRAFT MEASUREMENT & ADJUSTMENT FAQs - questions & answers posted originally on this page.
Or see these
DRAFT MEASUREMENT, CHIMNEYS & FLUES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Or see
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
One image per comment; please Bookmark this page to find our response. Comments with an Image or a web link appear after moderator approval.
Private comment? Email editor@inspectApedia.com
In addition to any citations in the article above, a full list is available on request.