No Heat Diagnosis & RepairWarm air heating furnace troubleshooting:
How to diagnose & fix hot air furnace heating system problems: hot air or warm air heating system troubleshooting, inspection, diagnosis, and repair.
Diagnosis and correction of NO HEAT or NOT ENOUGH HEAT conditions for warm air or hot air furnace and air duct heating systems. We explain how to recognize and fix common heating system operating or safety defects and how to save money on home heating costs.
Page top photo: an antique, but still working octopus gravity furnace providing warm air heat to a New England home.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
If your furnace isn't working, what can you fix yourself and what should you check before you call a heating service company?
If you don't know whether your heat is provided by a furnace (hot air) or boiler (hot water), or whether your fuel is oil, gas, or electric, and whether your heat is hot water, steam, or warm air,
see HEATING SYSTEM TYPES.
If your heating system uses water or hydronic or hot water or radiator or baseboard hot water heating systems, instead of the article found here you should
see NO HEAT - BOILER
Note: some hybrid or mixed heating systems combine both hot water and hot air to heat a building, such as water to air systems which use a heating boiler (oil, gas, or electric) to heat water which circulates through (and inside of) a heat exchanger (that looks like a car radiator).
Above: this sketch of the basic air flow in where a heating furnace is used is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, report writing, and education firm.
Article Contents
...
If you have power and fuel to the heater, next check these controls
Then the furnace draft fan began to pulse several times upon starting.
After making sure the control module showed a steady green, I
asked a friend and he suggested that I wiggle all the spade connectors to be sure there is good contact between the copper and aluminum. It seems that there only needs to be a little corrosion to cause problems. That seems to have done the trick. . - M.F. 12/24/2014
...
Now continue with the No Heat or Insufficient Heat from a Furnace diagnostics given just below.
...
If there is no heat or not enough heat coming from the Furnace (forced warm air) heating system: is any air coming out of the supply registers? Is it warm or cool?
Furnace blows air but it's cool or cold:
See FURNACE BLOWS COLD AIR
No warm air comes out:
If no air is coming out of supply registers, is this true throughout the building (the blower is blocked or not running) or just in some areas (some registers or duct sections are closed or blocked)?
Heating air comes out but it is too weak or slow: check for a dirty clogged air filter.
See AIR FILTERS for HVAC SYSTEMS , a dirty-clogged blower fan, blocked, disconnected ductwork.
Not enough warm air heat is provided
See AIR FLOW TOO WEAK - which of course includes the problem of dirty air filters - iat the link given above.
and
DUCT SYSTEM DESIGN SIZE & DEFECTS
and UNDERSIZED RETURN DUCTS - not enough return air
Details of Hot Air Heat Furnace Controls and Switches
For details about the setting, re-setting, or function of the controls and switches commonly found on hot air heating systems
see FURNACE CONTROLS & SWITCHES and
also FURNACE OPERATION DETAILS
Definition of Water to Air Heat Exchanger Heating Systems
Some heating systems combine both hot water and hot air to heat a building, such as water to air systems which use a heating boiler (oil, gas, or electric) to heat water which circulates through (and inside of) a heat exchanger (that looks like a car radiator).
For a detailed guide to inspecting, diagnosing, maintaining & repairing mixed, hybrid, water to air heating systems
see FAN COIL & FAN CONVECTOR HEATERS & HYDRONIC COILS
These buildings will have both a hot air furnace and a completely separate hot water heating boiler installed. In this case these are completely separate heating systems and usually each serves different building areas.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
I rent and the gas furnace has a problem on occassion (everyday is different) The thermostat turns the heat on and no heat.
The furnace is clicking - sometimes 15 to 40 mins before I hear the burners start. Some days I hear the burners going but no heat is blowing . This can be 15 to 40 mins. What is wrong? How to Fix? Landlord says - "You're getting heat!"On 2013-03-16 by vicky
(mod) - notify building owner of unsafe heating system and check CO detectors
Vicky,
Notify your landlord, IN WRITING, that the heating system is not operating safely nor reliably, with failures to start properly.Particularly with gas heat, there are potential carbon monoxide hazards that could be fatal so also be sure that your home has working CO detectors.
From just the information in your note one cannot properly nor safely diagnose the problem. A service call is needed.Watch out: If at any time you feel unsafe get everyone out of the home and call emergency services
Oil tank very low. Getting no heat but water still hot ? - 2021-03-15 by Steve -
Reply by (mod) - diagnose "getting no heat"
@Steve,
Your comment is on a page for furnaces - forced warm air heat
If your hot water (for washing and bathing) is made by a separate device, see if the furnace runs on a call for heat.
If the same boiler that heats your house (by forced hot water baseboards or radiators) is making your hot water then that suggests that the problem isn't that the boiler itself won't run.
Or start by stepping through the diagnostics at
HEAT WON'T TURN ON
Hi, oil tank slightly overfilled today. Furnace in lock out. Is there some other reset for overfill? - 2020-11-17 by Manny -
Reply by (mod) -
Manny
I don't know why overfilling an oil tank would cause your oil burner "furnace" to lock out;But far more likely, the oil tank fill-up stirred up sludge and debris that caused oil burner malfunction that clogged the nozzle causing a sooty flame and then caused the burner primary control to turn off the burner.
You can press the RESET button on the primary control on your oil burner ONCE - if the burner starts and keeps running you're in business while you wait for the still-needed service and cleaning;
If the oil burner won't run or won't keep running do not keep pushing the reset button lest you cause an oil burner puffback explosion.Followup by Anonymous
Thank you for the response. Do you think sludge is likely even though I wasn’t out of oil? I was only having it topped off. It only took 89 gallons
Reply by (mod) -
I agree that when the tank is an empty string up the bottom slow just less likely but still possible. Consider that the oil tank is usually filled under pressure from the oil truck
pilot working fine but heater wont come on thermostat doesn't click or due anything even if I turn it up all the way - On 2020-11-09 by Gary Grogan -
Reply by (mod) -
An easy test that your service tech might perform is to Simply disconnect the thermostat at the control board or furnace and then to jump those two thermostat wires together.
That's exactly the same functionally as turning the thermostat up above the room temperature. If making the connection doesn't start the furnace in the problem is not the thermostat or it's wiring but the control.
Furnace won’t stop running. The blower is on constantly, and the burner comes on in a cycle with being on for approximately 30 seconds, then off for a few minutes and then back on again. 2019-02-21 by Yooper -
Reply by (mod) - Furnace won’t stop running.
Yoop
See FAN WONT STOP - LIMIT SWITCHand FAN WONT STOP - THERMOSTAT SWITCH
for diagnosis and repair procedures
I have a zoning system. One thermostat for upstairs and one for downstairs. Upstairs comes on and downstairs doesn’t. The furnace will not turn on for the downstairs thermostat. What can the problem be?On 2018-12-29 by Elliott -
Reply by (mod) -
Elliott
I'd check first for open thermostat wires or a bad thermostat wiring connection.
Then , as you're posting on a forced warm air heating page I think you've got a furnace, and if it's a single furnace for the whole house and the house is divided into two different heating zones, look for a zone damper for your downstairs duct zone and see if it's stuck closed.
I have 2 zones for hot air heating. I have two thermostats - one upstairs and one down. The upstairs is nice and warm.
Downstairs is freezing and not actually heating when heat is being called for. I have Honeywell TH421D thermostats. The furnace is in the attic.
It has some sort of sensor thing on it and it shows zone one with a blinking amber light and zone two is greensand the heat shows green as well. Is there something i can do myself to get zone 2 to work? On 2018-01-01 by Brenda
Reply by (mod) -
Brenda
Let's start by finding the brand and model of furnace you have in your attic, then find the installation and operation manual for it. There we will find a specific guide to error lights and codes.
sometimes it will heat but when it is cold just cold air comes out
my furnance heats to about 68 but after that it just blows cold air. On 2018-12-10 6 by Anonymous -
and
my oil furnace will blow hot air for awhile [could be 2 to 4 hours] then blows cold air. while its blowing cold I push and hold [reset] button and the red light goes out and I can hear the burner come on and I get hot air. hours later it starts blowing cold air again. 2018-11-14 by larry -
Reply by (mod) - oil burner that is going off on safety reset
Larry and Anon
It sounds to me as if you are describing an oil burner that is going off on safety reset. Typically that's because of inadequate combustion. You don't want to keep resetting because ultimately you risque puffback explosion.Most likely your system needs cleaning and adjustment. Be sure to ask for help from a trade heating service technician.
My hot air oil burner furnace won't come on.it was working fine and when we came home from Christmas dinner it was cold in here.
I have oil and I put a new oil line filter and nozzle in it but it's not coming on. It does nothing at all after holding The reset button in .The flashing little green light says it's in lockout. What does that mean? Any help would be greatly appreciated. Thanks 2017-12-26 by Jake
Reply by (mod) - what to do if your heat is off on "lockout"
I would start by checking to see that the furnace is running in a response to a call for heat.
And I would confirm that since the blower fan is running air is coming out of The supply registers.
If it's not I would look for a problem in the blower unit such as a broken pulley or fan belt. If the blower is running correctly then you may have disconnected or collapsed ductwork."Lockout" usually means that a safety control has shut down the system after detecting an unsafe condition such as when the burner tries to run but there is no successful ignition of the oil burner flame.
Holding the RESET button in is not quite correct; after the safety control has tripped the reset button is "popped up" or is protruding. You might have to wait 10 minutes or more for the system to cool down. Then pressing the button ONCE and releasing it should re-set the system and the burner will try to run again.
See details at RESET SWITCH, CAD CELL RELAY - https://inspectapedia.com/heat/Cad_Cell_Relay_Reset_Button.php
If you can't reset the button after waiting a time, or if the burner motor run but there is no ignition, leave the system off - it's time to call for repair.
In a heating emergency, while waiting for a trained service technician you could look at the suggestions at OIL BURNER WONT RUN https://inspectapedia.com/heat/Oil_Burner_Wont_Run.php where we give a series of diagnostic steps to follow.
Keep me posted.
Furnace fan powers up, ignitor coil heats up, but burners don't ignite. I have four (4) limit switches on the furnace. If I flick the switch on each one to reset them and restart the furnace, it works fine again for about half a day.
However, when the furnace attempts to power up for a second cycle, the same thing happens again (burner don't ignite) unless I reset the switches again. Any help? (This is getting old and I'm not looking forward to the trip to the basement to reset the limit switches every 12 hours.) Thanks - Jerry 1/31/12
Reply: Check wiring, reset buttons, and check for a tripped flue gas spillage sensor
Jerry,
Check the control wiring connections first; As you are describing a gas furnace, it sounds as if the gas valve is not opening.
Check for a flue gas spill switch attached to the draft hood or draft opening on your furnace. If your chimney has been blocked OR if windy conditions causes a downdraft (perhaps missing a chimney cap) that could cause dangerous flue-gas backdrafting that is sensed by the switch.
The switch will then turn off the gas burner.
Some gas heater spill switches have to be re-set manually by waiting a time, then pushing a button right on the switch.
Details are
I HAVE A LUXAIRE TWO VENT PIPE 90%afue downflow/horizontal gas furnace HI EFFICIENCY HEATER.
The intake sucked in a leaf or leaves during the hurricane into the burner box, or they leaves are either stuck in the intake pipe or somehow is blocking the proper flow of vent air thru the system.
My diagnosis view port is showing a 3 flash led pattern.
The secondarary vent blower continues to run but will not allow system to start.Is their anyway to clear the debris and restart the system - Tom 10/29/12
Reply:
If leaves really got all the way into your furnace through its exhaust vent, I worry that there's debris in the combustion chamber - meaning that the system needs to be cleaned.
For safety you probably need service by a trained technician.
The service tech will remove enough covers to vacuum out any debris and then s/he will inspect the gas burners for proper operation.
Hello my friend (a newly graduated hvac technician) and I have been trying to help a local woman with heating troubles. She has a 'Kerr' Oil Fired Warm Air Furnace.
We have tried on several occasions to help by troubleshooting in order to make it/ keep it functional. It seems to work for a heat cycle or two and even though it starts, each time the system has needed to be reset. The things that have been done so far include cad cell tested and cleaned, air flow adjusted, tested/ adjusted limit settings and changed over to new thermostat.
Can you direct us as to what could be the source of the problem? We really can not afford to hire a technician...and would sincerely appreciate any assistance you can provide. - M.D. 12/28/2013
Reply:
A competent onsite inspection by an expert usually finds additional clues that would permit a more accurate, complete, and authoritative answer than we can give by email alone. You will find additional depth and detail in articles at our website.
Id like to help diagnose the Kerr furnace you discuss, but with so little information I'm not confident about what specific details I can recommend by email. I'll make a few suggestions, then you may be able to tell me more and I may be able to comment further.
While there is nothing harmful in the steps you've taken so far, they sound a bit random to me. I'm doubtful, for example, that changing a thermostat would have much to do with a furnace going off on reset - except for a very odd case of a furnace that kept switching the call for heat on and off very rapidly.
And your cleaning the cad cell is a fine idea, but doesn't consider that if the cad sell was dirty then the flame is probably running smoky and there is an adjustment or fuel or nozzle problem, nor does it consider the possibility of a bad cad cell that needs replacement.
When a heating system keeps going off on reset usually there is a problem with fuel or combustion: dirty oil filter, defective fuel unit, air in oil lines, cracked or improperly set electrodes etc. You can take a look at two diagnostic pathways at InspectApedia, one for furnaces and the second focused on oil burners. See
- DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
- OIL BURNERS - or perhaps better for you
- OIL BURNER INSPECTION
where we include diagnostic flowcharts and very thorough debugging steps.
You should also have at hand the installation and set-up instructions for the Kerr oil fired furnace you mention - though you didn't give me a model and serial.
But most often a problem with an oil fired furnace that keeps going off on reset will be traced to a fuel, electrode, cleaning, or adjustment problem that is more generic to oil burners rather than to the specific furnace model.
Find the manual for your specific heater
at Kerr HEATING EQUIPMENT (Granby)
Kerr oil furnaces are produced by Granby Industries, of which Kerr Energy Systems produces both forced warm air heating furnaces and heating boilers. Contact information: http://www.granbyindustries.com - for furnaces is Granby Furances Inc., 12118 Hwy 209, PO Box 637 Parrsboro NS B0M 1S0 Phone: 902-254-2543 Fax: 902-254-3863 gfisales@GranbyIndustries.com
I would contact the company with the furnace model and serial number to obtain installation instructions if you don't already have them. There are several Kerr furnace models: Gemini, Eclipse, Compact, Paradigm (High efficiency), Summit, Scotty, & Scotsman - so you can see that you'll need your model and serial number to obtain the right installation and maintenance instructions.
General furnace troubleshooting is
at DIAGNOSE & FIX HEATING PROBLEMS-FURNACE (forced warm air heat)
I have a Chrysler air temp gas heater that won't heat the house has a new thermostat but need to move it way up and then there is buzzing and never enough heat. please help it is 15 degress here (Feb 17, 2014) sandy
Reply:
Sandy, what is buzzing? If it is a control on the heater the control may replacement; if it is the low voltage thermostat that's buzzing that may need to be replaced; Have you called for service?
I recently finished a basement. The customer is complaining that they are not getting any warm air in the basement. We confirmed that air flow to the basement was low and complete a camera assessment of the trunk lines that were installed.
They are free of obstruction and there are no misaligned trunks. Outside of normal degree variation of below grade space, do you have any ideas on root cause? Would you agree that the issue is most likely in the furnace and/or blower versus the trunks we installed? What solutions might you suggest? (May 21, 2014) Marty
Reply:
Marty
Let's look at things that would obstruct air flow. Don't forget to include
- dirty air filter
- dirt, even a little dirt, on those blades of the squirrell cage fan
- inadequate return air- defective fan, blower drive belt, blower assembly, voltage
Detailed help is at WARM AIR SUPPLY TEMPERATURE & IMPROVEMENT
I installed a limit switch with the bypass tab on.now nothing works. what would be the most Likely thing that I burned up?
I replaced the switch and still nothing. (Jan 7, 2015) jimmy s
Reply:
Sorry to read that aggravation Jimmy. Check fuses at the furnace and also check to see if the blower motor has a reset button tripped.
But I suspect a wiring error.
Watch out: fooling with a furnace limit control risks bending an internal spring that de-calibrates the unit, making it unsafe, risking a fire or carbon monoxide poisoning hazard.
Detailed help is at FAN LIMIT SWITCH - home
Hello, I recently installed a new T-stat for a customer who wanted to control their T-Stat with their cell phone. They have hot water radiant heat along with forced air that works in conjunction with the boiler. They have several zones that are just two wire stats. They had one upstairs that controlled the ac unit and the furnace.
They had your normal R,W,Y,G wires all hooked up to the appropriate terminals. They had an additional wire that I hooked up for the common so the T-Stat could be powered up. Everything seemed fine when I was there but I received a call from the customer stating that their heat hadn't shut off and it was 94 degrees when they got home...yikes.
Not sure what happened here so any thoughts would help. I had taken apart one of their two wire stats so maybe that thing wasn't working right...although it was just an old mercury stat so not sure what can go wrong with that. When I hooked up the common I followed what I believed to be the common side of the transformer and followed the wire to a group of wires nutted together.
It powered up the stat so I thought it was correct. My thoughts are its maybe the old stat downstairs, as that is a heat only. I have to find out what stat is keeping it on first. Not too familiar with these systems working with a furnace so I'm not sure what I did but maybe it will be apparent once I look at it. Thanks (Jan 23, 2015) Tom
Reply:
Hi Tom
Just last weekend in Chicago we helped a brother-in-law install another Nest thermostat. Nest has a website and cellphone app that gives nice remote control of the thermostat as well as providing data on house temperature when you're away.
We lucked-out: the thermostat wires (there were four, two cooling, two heating) plugged right into where we thought they should by following the color codes.
In your case I'm not sure what that additional wire was; some thermostat models require an additional power or voltage wire to operate or power the thermostat. You might check that with your DMM or VOM. But it does sound as if something is calling for heat.
Don't forget to check for shorted or crossed thermostat wires (or an un-wanted jumper) anywhere in the circuit. That can leave you permanently calling for heat.
Tom
More details on thermostat wiring are in our article series on that topic - see
THERMOSTAT INSTALLATION & WIRING MANUALS
or
I have a Trane model bld080e936b1 gas furnace that is not igniting. The thermostat seems fine and if I jumper the R and W wires together I get nothing. It has a standing pilot light that stays lit just fine. The thermocoupler seems to be ok.
When I tested the R to G with a multimeter I get 27 volts. Same with R to Y but R to W gives only 2.4 volts. I checked the R and C connections on the transformer and I have 27 there too. Any thoughts? 12 Feb 2015 Hoodoo said:
My garage heater. it was clicking on but not firing up.i made sure i bled system,i replaced tip and adjusted the electrode,replaced transformer, cad eye too.
i got it fierd up and ran it for few hrs. then turned off power because it was 30* out and thermostat only went down to 50*. next day went to start up and nothing. reset button won`t reset when pushed in.
i checked rest button on motor and wasn`t popped. i replaced relay switch brand new. and it wont even kick engine over. i have electric which i test witha testergoing to every thin including thermostst . scratching my head and cold can u help me marc santora
Reply:
If wiring is correct and nothing is inadvertently grounded I usually suspect a bad igniter or a bad igniter control module.
I have a 1987 Goodman furnace with no AC change thermostat and now the furnace won't do nothing but the limit switch will turn on blower on manual but will not light when thermostat is on Auto pilot light is lit very confused (Oct 8, 2015) Lance Cundiff said:
Reply:
start by stepping through the diagnostics at
HEAT WON'T TURN ON
Do I have forced draft on my mobile home unit it is a heat pump and why do I need it (Oct 17, 2015) Jon
Reply:
John if your mobile home heat pump is working then there is an indoor air handler that is blowing cool or warm air into your home. You would not need forced draft unless your backup heat uses a gas or oil fired heater that operates in that manner.
I have a gas furnace the blower is stuck to manual and i cant get the burners to fire. I installed a new thermostat but cant figure out how to make the burners fire but the pilot is lit (Dec 28, 2015) Jasongutman
Reply:
Jason
Some thermostats include a FAN -ON switch that will keep the fan on. Others don't. Check to see if you have that switch.
But to me it sounds as if you have a wiring error; Search InspectApedia.com for FAN LIMIT SWITCH to read about how to turn off the manual -on switch on your blower; also check the thermostat settings; that's where I'd start.
(Feb 19, 2016) jose said:
I replaced nozzle, oil filter, air filter, and cad cell. my forced air furnace runs for 3 to 4 hours and wont start again only cold air comes out. I reset it and it starts again no problem until hours later the same thing. could it be my thermostat?
Reply: no
I don't think so. A bad thermostat only calls for heat ir doesn't. That's not going to explain a heater tripping the rest button.
jose said:
Thanks, could it be the relay even though it runs for hours(mod) said:
If the furnace is going off on rest its safety device is telling you that the oil burner is not producing a proper flame - an ignition problem.That can show up under varying conditions, can be intermittent, and basically merits a visit from a trained hvac tech. You wouldn't normally need to replace a cad cell though on occasion they do go bad. Check the new cell for evidence of soot on its face or for a loose connection
Watch what happens when the burner tries to start. No flame? Should go off on reset
...
Continue reading at FAN LIMIT SWITCH - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
DIAGNOSE & FIX FURNACE PROBLEMS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.