Air Conditioning & Heat Pump Refrigerant Gases
Refrigerant gases, metering devices & piping: this page lists and describes all of the gases used in refrigeratin, HVAC, air conditioners, heat pumps, etc. and provides links to free copies of refrigrant gas pressure tables as downloadable PDFs.
This article series describes the properties of common and historic air conditioning refrigerants. We combine U.S. EPA information with supplemental data and descriptions of refrigerants, refrigerant replacement options for R12 and R22, and their basic data.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Air conditioning refrigerants and agents to transfer heat from one place to another have been in use for a long time and include Ammonia, Sulfur Dioxide, Hydrocarbons like methane, methyl chloride, and methylene chloride, and safer (inert gas) HFCs like R11 (common in older refrigerators and some air conditioners) and R22 (common in older cooling equipment.
Since the realization that HFC's contribute to greenhouse gas problems in the environment, R11 and R22 have been discontinued and are being replaced with alternatives including R-410A (GENETRON AZ-20, SUVA 410A, and Puron (R-410A)), R-134A R-407C.
Also discussed here: Consumer Information about A/C Refrigerant Gases and R-22 substitute gases, US EPA information updated to 2012. R22 refrigerant phase-out schedule; photographs of R12 and R22 dispenser canisters & charging gauges.
Alternatives to R22 refrigerant - "R" refrigerants: R-410A (GENETRON AZ-20, SUVA 410A, and Puron), R-134A R-407C. Properties of R410-A Puron® refrigerant and usage advice.
See this
LENNOX WARNING about use of "alternative refrigerants where R22 or other old gases are not available. U.S. EPA Warning about Recharging Air Conditioners with Substitutes for R-22, 22a or R-22a.
DISCLAIMER: EPA [and this website reproducing this public-domain article] seeks to promote energy efficiency and the safe use of ozone-friendly substances, and does not endorse any particular company or its products.
Watch out: any refrigerant gas and gas container, including the small refrigerant canisters sold for automotive use in charging automobile or truck air conditioners can be dangerous if not properly handled.
Liquid refrigerant can injure an eye and can also cause frostbite. You should cover refrigerant lines or connectors or valves when opening them so that if liquid refrigerant escapes it is controlled. And on at least some refrigerant containers such as the automotive maintenance canisters you'll see warnings about the need for eye protection and other protective measures.
Also some refrigerant gases form highly toxic phosgene gas if released across an open flame, so if a flame is present near where refrigerant gases are being used for service be sure there is good fresh air ventilation.
Refrigerant Gas Asphyxiation hazards: Modern refrigerant gases are heavier than air as well as being odorless and colorless. The gases themselves, such as the Freon family, are not toxic and not explosive. But because the gases are heavier than air, if you were so foolish as to release a sufficient volume of gas into an enclosed space or even a low-lying outdoor area where there is no wind or indoors no ventilation, you could become asphyxiated with little or no warning.
Do not mix refrigerant gases. Each refrigerant gas has its own unique properties. If you were to mix gases within a refrigeration system the properties of the mixture would be unpredictable, making it impossible to properly adjust and operate the equipment.
Do not arbitrarily substitute refrigerant gases by charging refrigeration equipment with a gas other than the one for which it is labeled, for the same reason as above. We discuss replacement refrigerants below.,
In 1987 the Montreal Protocol, an international environmental agreement, established requirements that began the worldwide phase out of ozone-depleting CFCs (chlorofluorocarbons). These requirements were later modified, leading to the phase out in 1996 of CFC production in all developed nations.
In addition, a 1992 amendment to the Montreal Protocol established a schedule for the phase out of HCFCs (hydrochlorofluorocarbons). HCFCs are substantially less damaging to the ozone layer than CFCs, but still contain ozone-destroying chlorine.
The Montreal Protocol as amended is carried out in the U.S. through Title VI of the Clean Air Act, which is implemented by EPA.
An HCFC known as R-22 has been the refrigerant of choice for residential heat pump and air-conditioning systems for more than four decades. Unfortunately for the environment, releases of R-22 that result from system leaks contribute to ozone depletion. In addition, the manufacture of R-22 results in a by-product that contributes significantly to global warming.
As the manufacture of R-22 is phased out over the coming years as part of the agreement to end production of HCFCs, manufacturers of residential air conditioning systems are beginning to offer equipment that uses ozone-friendly refrigerants. Many homeowners may be misinformed about how much longer R-22 will be available to service their central A/C systems and heat pumps.
This fact sheet provides information about the transition away from R-22, the future availability of R-22, and the new refrigerants that are replacing R-22. This document also assists consumers in deciding what to consider when purchasing a new A/C system or heat pump, or when having an existing system repaired.
Under the terms of the Montreal Protocol, the U.S. agreed to meet certain obligations by specific dates that will affect the residential heat pump and air-conditioning industry:
In accordance with the terms of the Montreal Protocol, the amount of all HCFCs that can be produced nationwide must be reduced by 35% by 2004. In order to achieve this goal, the U.S. is ceasing production of HCFC-141b, the most ozone-damaging of this class of chemicals, on January 1, 2003.
This production ban will greatly reduce nationwide use of HCFCs as a group, making it likely that the 2004 deadline will have a minimal effect on R-22 supplies.
After 2010, chemical manufacturers may still produce R-22 to service existing equipment, but not for use in new equipment. As a result, heating, ventilation and air-conditioning (HVAC) system manufacturers will only be able to use pre-existing supplies of R-22 to produce new air conditioners and heat pumps.
These existing supplies would include R-22 recovered from existing equipment and recycled.
Use of existing refrigerant, including refrigerant that has been recovered and recycled, will be allowed beyond 2020 to service existing systems, but chemical manufacturers will no longer be able to produce R-22 to service existing air conditioners and heat pumps.
For more information about this phase out, see fact sheets about the HCFC Phase out Schedule and Frequently Asked Questions on the HCFC Phase out
The Clean Air Act does not allow any refrigerant to be vented into the atmosphere during installation, service, or retirement of equipment. Therefore, R-22 must be recovered and recycled (for reuse in the same system), reclaimed (reprocessed to the same purity levels as new R-22), or destroyed. After 2020, the servicing of R-22-based systems will rely on recycled refrigerants.
It is expected that reclamation and recycling will ensure that existing supplies of R-22 will last longer and be available to service a greater number of systems. As noted above, chemical manufacturers will be able to produce R-22 for use in new A/C equipment until 2010, and they can continue production of R-22 until 2020 for use in servicing that equipment.
Given this schedule, the transition away from R-22 to the use of ozone-friendly refrigerants should be smooth. For the next 20 years or more, R-22 should continue to be available for all systems that require R-22 for servicing.
While consumers should be aware that prices of R-22 may increase as supplies dwindle over the next 20 or 30 years, EPA believes that consumers are not likely to be subjected to major price increases within a short time period.
Although there is no guarantee that service costs of R-22 will not increase, the lengthy phase out period for R-22 means that market conditions should not be greatly affected by the volatility and resulting refrigerant price hikes that have characterized the phase out of R-12, the refrigerant used in automotive air-conditioning systems.
As R-22 is/ was gradually phased out, non-ozone-depleting alternative refrigerants are / were being introduced. Under the Clean Air Act, EPA reviews / reviewed alternatives to ozone-depleting substances like R-22 in order to evaluate their effects on human health and the environment.
EPA has reviewed several of these alternatives to R-22 and has compiled a list of substitutes that EPA has determined are acceptable.
One of these R-22 substitutes is R-410A, a blend of hydrofluorocarbons (HFCs), substances that do not contribute to depletion of the ozone layer, but, like R-22, contribute to global warming. R-410A is manufactured and sold under various trade names, including GENETRON AZ-20®, SUVA 410A®, and Puron®.
Additional refrigerants on the list of acceptable substitutes include R-134a and R-407C. These two refrigerants are / were not yet available for residential applications in the U.S., but are commonly found in residential A/C systems and heat pumps in Europe. EPA will continue to review new non-ozone-depleting refrigerants as they are developed.
Watch out: Using an alternative refrigerant to R-22 in older air conditioners and heat pumps requires more than just using a different gas (such as Puron R410-A). Other components in the system (such as refrigerant metering devices) will usually require change or adjustment.
Be sure to consult the individual air conditioner or heat pump application guidelines and installation or service manual – Air Conditioners and Heat Pumps Using Puron Refrigerant [Carrier or other manufacturer] to obtain required unit changes for specific applications and for R--22 retrofit.
Watch out: EPA Warning: Recharging Air Conditioners with Wrong Refrigerant Poses Injury and Fire Risks
FOR IMMEDIATE RELEASE July 22, 2014 (updated by InspectApedia thorugh 2024)
WASHINGTON – The U.S. Environmental Protection Agency (EPA) is cautioning homeowners, manufacturers of propane-based refrigerants, home improvement contractors and air conditioning technicians of the safety hazards related to the use of propane in existing motor vehicle and home air conditioning systems.
A number of refrigerants with “22a” or “R-22a” in the name contain highly flammable hydrocarbons, such as propane. These refrigerants are being marketed to consumers seeking to recharge existing home and motor vehicle air conditioning systems that were not designed to use propane or other flammable refrigerants.
These refrigerants have never been submitted to EPA for review of their health and environmental impacts and are not approved for use in existing air conditioning systems.
Using propane-based refrigerant in an air conditioner that is not designed for flammable refrigerants poses a threat to homeowners as well as service technicians because systems that are recharged with “22a” refrigerants can catch fire or explode resulting in injury and property damage.
EPA is investigating instances where propane-based refrigerants have been marketed and used as a substitutes for HCFC-22 (R-22) and will take enforcement actions where appropriate.
More information about R-22a and R22 phaseout and R22 alternatives for air conditioning: see this EPA document (this is at the US EPA website, use your browser's "BACK" button to return to InspectApedia)
Residential Air Conditioning and the Phaseout of HCFC-22 What You Need to Know [PDF] (2020) US EPA (final draft)
Quoting advice from Lennox Industries you will see that for their equipment the company does not recommend use of refrigerants marketed as replacements for R22:
Over the past few years, the home comfort industry has been working to phase out the production of the cooling refrigerant known as R-22. However, in early 2012, recent changes to government regulations regarding this transition have created uncertainty in the marketplace, and prices for R-22 have dramatically increased as a result.
In response to rising prices, many refrigerant manufacturers have stepped up their marketing efforts for several "alternate" refrigerants, claiming they are cost-effective "drop-in" replacements for R-22. The three most popular are R-407C, R-438A (also known as ISCEON M099) and R-422.
The problems associated with these alternate refrigerants are many:
Given all the risks, Lennox does not support the use of alternate refrigerants at this time. It is important that you carefully consider the issues associated with their use, including the nullification of your manufacturer and compressor warranty.
Before allowing a technician to service your HVAC equipment, we encourage you to get involved and urge your technician to only replace R-22 with R-22.- [7] Lennox_Refrigerant_Warning.pdf
Watch out: the following excerpt is from Lennox:
The official deadline for all equipment
manufacturers to change over to more environmentally friendly refrigerants is 2010. Aftermarket R−22 will be available
until 2020. HFC−410A is quickly becoming the refrigerant of choice to replace HCFC−22 in residential and light commercial
air conditioning equipment.
R−410A is a near−azeotropic mixture of R−32 and R−125 refrigerants. R−410A operates at 50% higher pressure than
R−22. Due to the higher pressure, Lennox has upgraded system components in R−410A systems. R−410A must not be
used to retrofit existing R−22 equipment. R−410A can only be used in equipment designed for R−410A.
It is recommended that charging with R−410A be done in the liquid phase. Use a commercial−type metering device in
the manifold hose. Charge into the suction line with the compressor running. See Lennox installation instructions for
more details on proper charging procedures.
- Lennox, LENNOX REFRIGERANT PIPING DESIGN & FABRICATION GUIDELINES, [PDF] (2008)
Source: PURONR (R--410A) REFRIGERANT QUICK REFERENCE GUIDE-[5]
There are replacement gases for certain of the now banned refrigerants discussed in this article. Quoting Zeller 1998 [1]
Suva MP39 and Suva MP66 are a mixture of 3 components, HCFC-22, HFC- 152A and ACFH-124, which have been created to replace CFC-12 in medium temperatures. The majority of compressors for CFC-12 can adapt to the use of MP39 and MP66 easily and economically.
This allows for the equipment already installed to continue in service during their lifetime.
The two new refrigerants demonstrate many properties which have been im- proved towards the ozone and the environment, in comparison with CFC-12.
The MP mixtures are compatible with the majority of the materials used for the construction of the CFC systems. T
he composition of each mixture has been selected to be compared with the efficiencies of CFC-12 in specified applications, in energetic capacity and efficiency.
This gives as a result a minimal mechanical interruption when CFC-12 is replaced with MP66 or MP39. O
ther refrigerants like the HCFC-22 or the HCFC-134A, require an extensive mechanical intervention in the systems when they are replaced, which will at times be expensive.
MP66 and MP39 give the user the chance to change refrigerants without spend- ing much in modifications to the CFC-12 systems. CFC-134A can also be used in evaporation temperatures lower than -7 C and 20 F but can demonstrate less capacity in these temperatures than the CFC-12, to cover the whole range of temperatures of the CFC-12, we also have the MP66 and the MP39. [1]
Existing units using R-22 can continue to be serviced with R-22. There is no EPA requirement to change or convert R-22 units for use with a non-ozone-depleting substitute refrigerant. In addition, the new substitute refrigerants cannot be used without making some changes to system components. As a result, service technicians who repair leaks to the system will continue to charge R-22 into the system as part of that repair.
The transition away from ozone-depleting R-22 to systems that rely on replacement refrigerants like R-410A has required redesign of heat pump and air conditioning systems. New systems incorporate compressors and other components specifically designed for use with specific replacement refrigerants.
With these significant product and production process changes, testing and training must also change.
Consumers should be aware that dealers of systems that use substitute refrigerants should be schooled in installation and service techniques required for use of that substitute refrigerant.
Along with prohibiting the production of ozone-depleting refrigerants, the Clean Air Act also mandates the use of common sense in handling refrigerants. By containing and using refrigerants responsibly -- that is, by recovering, recycling, and reclaiming, and by reducing leaks -- their ozone depletion and global warming consequences are minimized.
The Clean Air Act outlines specific refrigerant containment and management practices for HVAC manufacturers, distributors, dealers and technicians. Properly installed home comfort systems rarely develop refrigerant leaks, and with proper servicing, a system using R-22, R-410A or another refrigerant will minimize its impact on the environment.
While EPA does not mandate repairing or replacing small systems because of leaks, system leaks can not only harm the environment, but also result in increased maintenance costs.
One important thing a homeowner can do for the environment, regardless of the refrigerant used, is to select a reputable dealer that employs service technicians who are EPA-certified to handle refrigerants. Technicians often call this certification "Section 608 certification," referring to the part of the Clean Air Act that requires minimizing releases of ozone-depleting chemicals from HVAC equipment.
Another important thing a homeowner can do for the environment is to purchase a highly energy-efficient system. Energy-efficient systems result in cost savings for the homeowner. Today's best air conditioners use much less energy to produce the same amount of cooling as air conditioners made in the mid-1970s.
Even if your air conditioner is only 10 years old, you may save significantly on your cooling energy costs by replacing it with a newer, more efficient model. Products with EPA's Energy Star(R) label can save homeowners 10% to 40% on their heating and cooling bills every year.
These products are made by most major manufacturers and have the same features as standard products but also incorporate energy saving technology. Both R-22 and R-410A systems may have the Energy Star(R) label. Equipment that displays the Energy Star(R) label must have a minimum seasonal energy efficiency ratio (SEER). The higher the SEER specification, the more efficient the equipment.
You should consider energy efficiency, along with performance, reliability and cost, in making your decision. And don't forget that when purchasing a new system, you can also speed the transition away from ozone-depleting R-22 by choosing a system that uses ozone-friendly refrigerants.
CFCs and HCFCs deplete the ozone layer, which acts as a blanket in the stratosphere that protects us from harmful UV radiation. This radiation has been linked to skin cancer, which is now one of the fastest growing forms of cancer. In the U.S., one person dies of skin cancer every hour.
Remember that ozone is "good up high, bad nearby:" even though it protects us when it is in the stratosphere, ozone at ground level can be harmful to breathe and is a prime ingredient in smog. Many man-made sources such as tailpipe emissions from cars contribute to ground-level ozone.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
9/24/2014 Daniel
I think it is important to note that we are talking about refrigerants here, not coolants, and not Freons.
Coolants don't change phase to do their job of transferring heat, the liquid coolant in your car's cooling system is a liquid and is supposed to stay a liquid.
Refrigerants do change phase, usually from a liquid to a gas and back again, but even the ice in a drink can be seen as a refrigerant since it is changing phases, from solid to liquid, to keep your drink cool.
Freons are certain refrigerants, usually CFCs (like R11, R12) and HCFCs (Like R22) made by DuPont Chemicals.
It is somewhat OK to call say R22 from any manufacturer Freon, it's the same as calling any adjustable locking pliers Vise-Grip whether or not they were made by Irwin.
What is not OK is to call refrigerants that DuPont has never called Freon by that name, for instance calling R134a a Freon is wrong, because DuPont calls it Suva.
This comment was originally posted at REFRIGERANT METERING CAPILLARY TUBES
Reply: Clarifications & Definitions of Refrigeration Terms: Coolant, Refrigerant, Freon and Trade Names
Excellently put, Daniel. Thank you for these clarifications of refrigerant terms.
Because many readers are not familiar with proper refrigerant terminology we find that people looking for information about refrigerants search on all sorts of words that we might agree are not quite correct. "Freon" has become about as generic and mis-used as "kleenex" for "tissues".
Your note is helpful to readers who want to speak accurately, while keeping the word "freon" around helps people find it. I'll copy your comments into our text on refrigerants
Can an A/C system that uses R-22 be changed to use R-410a? - Anon 6/3/11
What is involved with converting from R-22 to R0417A? My unit was made in 2005. - Bill 6/5/2011
can R-22 CONVERT TO R134A MY UNIT WAS MADE IN 1999. - Jonathan 6/7/11
Reply:
Changing an R-22 refrigerant-based A/C system over to use R-410a is possible but costly since quite likely you cannot simply charge the system with the new refrigerant.
It may be possible to continue to use the same compressor/condenser unit and air handler, but significant parts inside each of those components, such as controls and possibly evaporator/condenser coils are going to need to be changed out.
There are "swap-in" substitute refrigerants for R-22, but as you can read above in the Lennox warning, they are not recommended by at least some manufacturers.
For this reason, if the R-22 based air conditioner is old and/or if other components are not in pristine condition, you'll want to get a careful price quote that allows comparing conversion of the equipment with replacement.
where can I purchase R 22 freon
Reply:
Charles I'd consider converting the refrigeration system equipment to a R-410 -based refrigerant design, as R-22 is no longer recommended.
However there are some websites offering R-22 refrigerant - though at astronomical prices for the ones I've seen.
Recent reporting (in 2012) has also noted that due to cost pressures and other market factors, some manufacturers continue to sell replacement HVAC parts that operate on R-22 despite its harmful effects on the atmosphere and environment.
regarding your discussions on R22 against R410a.
The pressures are extremely high compared to r22 in the uk we use special gauges with adaptors to fit the equipment operating on r410.
Due to the legislation in place you can not work on any system without certification.
We strength test our pipe work installs to 623 psi and pressure test to 478 psi.
Retrofitting can be carried out but care has to be taken to ensure that the equipments pipe work can take the higher operating pressures. Additionally we can only purchase recycled r22 and new r22 is not available to us. This is something you will all eventually have to come to terms with. - James 7/12/11
Reply:
James, thank you for making several excellent points; we agree completely. The conversion from R22 to R410 is not trivial;
...
Continue reading at GAUGE, REFRIGERATION PRESSURE TEST or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
REFRIGERANT GASES & PIPING at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.