Refrigerant piping noise diagnosis
How to diagnose running water sounds in refrigerant piping at the air conditioner, heat pump, or refrigerator:
What causes running water sounds or burbling or gurgling noises heard in the refrigerant piping or tubing in an air conditioning or heat pump system?
Gurgling noises in HVAC or refrigeration equipment is often traced to an improper refrigerant charge, refrigerant gases in the liquid refrigerant line.
This air conditioning repair article series discusses the diagnosis and repair of air conditioning compressor noises which range in importance from normal (if annoying squeaks and squeals, to rattling loose bolts and hardware, to costly compressor damage indicating air conditioning compressor or A/C compressors at or near end of their life.
Page top photo: the author's refrigeration equipment gauge set.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
I have a 4 ton heat pump that hisses when it shuts down in 40* weather. The frig. lines run in the wall near bedroom. Sounds like freon running back to or from compressor, Only in heat cycle. - richdunegan@gamil.com 12/11/11
Question: Just this morning I noticed when my heat unit/pump was running it sound as if water was draining through pipes. (The out side connections to the pump/inside unit run over head in my laundry room) So far there's been no other issues. Any idea what this could be? Should I be concerned? Once the heat shuts off this draining sound quits. - Ruth 1/25/12
Question: I live in a 1st floor apartment. When the A/C of the resident on the 2nd floor turns on, there is a sound like cascading water in about 1 minute intervals and lasts for 15 seconds or so. This continues under the unit turns off
I have been told by maintenance that it's the freon rushing through the pipe and that it's normal. I have lived in several apartments and have never heard this before. Invariably, for some reason, condenser units are always just outside bedroom windows. lol
So, my question is, is this indeed normal? - Anonymous 2016/06/27 by private email
Running water sounds, bubbling, burbling, gurgling noises in the air conditioning or refrigeration system suction line may be due to liquid refrigerant in the suction line on the low-pressure side of the system.
Floodback happens in the suction line when liquid refrigerant is burbling along where we expect to find only refrigerant in a gas state. That might be caused by a problem with the refrigerant metering device or by an HVACR system that has been overcharged - too much refrigerant has been added to the system.
Watch out: A severely overcharged system compressor can have floodback when running and this can lead to compressor failure from oil being flushed from compressor or broken valves in reciprocal compressors. - Tommy 1/15/2012
Also check for running water sounds traced to drain piping that receives air conditioner or heat pump condensate from a condensate pump.
Because the condensate pump only runs when its reservoir is filled, the pump on-off cycle will be irregular, but the pump may be sending water into a building drain that, because of its material (plastic) and location (not through sound-insulated space) could show up as a running water or gurgling sound.
"Normal" to some techs is "problem" to others - it depends on exactly what's going on.
For example, insufficient charge of refrigerant or air contaminants in the system can cause one to hear refrigerant burbling along in the high pressure line where normally the line is full and silent.
If my guess is right, ultimately the 2nd floor resident will have no cooling and the system will have to be repaired properly.
Question. Would evacuating and recharging the system be a course of action? And is this an expensive process? Or is the way to look at it do this and you won't have to replace the compressor?
Yes. And yes. But the cost to properly charge an HVACR system is certainly significantly less than wholesale replacement of the compressor/condenser. I'm unclear on why someone has suggested that compressor replacement is needed for this problem.
Keep in mind that anybody diagnosing a complex system by e-text is unable to see onsite clues that would shout loudly to any competent expert who is on-site.
Assuring that the system is properly charged is a step techs take to address the running water sound problem we're discussing as would be appropriate for a low refrigerant charge for any reason. Some HVACR systems include a sight glass on the refrigerant line that allows the tech to actually see the refrigerant gas bubbles but most residential systems don't.
Returning to the question of refrigerant charge vs. running water sounds in the piping:
A tech who's trying to guess at the refrigerant charge on a running system will measure temperatures on the high and low lines, but all that tells you is that there is enough refrigerant to cool the coil, not that the full measured charge called for by the manufacturer has been placed into the system.
It's an expensive and low quality but very common repair to simply add enough refrigerant to get the system cooling. That is very likely to be less than the charge volume specified by the manufacturer (and profitable for the service company). If there is an ongoing refrigerant leak, the system will ultimately stop cooling again, perhaps first icing the coil then stopping cooling entirely.
A proper and best repair when the refrigerant charge is low is to find and fix the refrigerant leak, then place a proper charge in the system, charging with the quantity of refrigerant specified by the manufacturer. Most HVACR systems other than very small ones include a receiver that buffers a charge of refrigerant that is larger than simply the bare minimum needed to fill the tubing and compressor.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
After installing my 1HP split AC, on testing, it gives a low hissing soung along the length of the pipes.
I also noticed condensate and water droplets along the whole length of the pipe. I had to extend the pipe as a result of the distance from the room to where the outdoor unit is to be located. On 2017-05-18 by Shehu
Suggestions by (mod) re: hissing sound along refrigerant pipes
I'm not sure what's happening Shehu. If there was a refrigerant leak that you heard hissing, the system will very quickly stop cooling.
Or is the noise coming from the expansion valve?
Refrigerant bubbles inside of piping usually mean the refrigerant charge is too low (or there is a sticky TEV).
The condensate along the refrigerant piping suggests that it is not insulated where it should be.More HVAC hissing noise causes, meaning, and repair advice is
Running water or gurgling sound at Trane A/C Air handler
New Trane a/c Air handler TEM4A0C48S41SA, Condenser 4TTR4048L1000A installed Saturday, May 18. 2019. Unit is loud with running water or gurgling sound. Tech just left he turned off the fan and could no longer hear any sound, but did not test the pressure of the refrigerant.
He adjusted the fan motor to run slower. But the unit is still much to loud and we still hear the running water or gurgling sound.
We have lived forty years in Florida in four different residence both homes and condo's and never had a loud sounding a/c like this. Would greatly appreciate your help. Thank you, George Zeller - On 2019-05-21 by George Zeller
Bubbling noises when our heat was turned on
Just turned heat on first time this year and I hear bubbling when the fans on. Should I turn it off - On 2018-10-14 by Libby -
Reply by (mod)
See the diagnostics at REFRIGERANT PIPING GURGLING and let me know if that was the problem.
Fix the Water noises in my new window air conditioner
I bought my window unit in June now I hear water in it what can I do - On 2019-08-13 by Christine
Reply by (mod) - is the noise gurgling water - condensate drainage, or is it bubbles in the refrigerant line?
Christine:
If the "water" noise is actually water - that is condensate - then the condensate should be draining out of the back of the window AC unit. If the unit is leaking into the room then it needs service to find and fix the drain blockage.
If on the other hand, you're actually hearing a gurgling sound that has nothing to do with condensate (actual water) the unit may have a refrigerant leak - call the company and ask for warranty service as your unit is only a couple of months old.
What does running water sound mean if I heaer it in my air conditioner?
What does it mean when it sounds like water running in a air conditioner - On 2018-06-18 by Anonymous
Reply by (mod) - gas bubbles in the liquid refrigerant line
I would call for repair: Sounds like gas bubbles in the liquid refrigerant line. That can mean low refrigerant and thus a leak to find and fix. Let me know what your technician says.
Diagnose odd gurgling sound at our HVAC system
Gurgling Sound / HVAC. This is odd. Our heat pump is off. It hasn't run in 3 days. (It's set to 60 degrees and it's currently 68 in the house). It was 70+ degrees the past 2 days (dropping down to appx 46 degrees at night). It's currently midnight and I was just in the basement where I heard a gurgling / "water flowing" noise in the small line going into the Air Handler.
It lasted for about a minute or so and then "died out". Any thoughts ? On 2018-04-24 by Brian
Reply by (mod) - Gurgling Sound / HVAC: condensate vs refrigerant vs ?
Often gurgling sounds in the refrigerant piping are a telltale of low refrigerant or a TEV malfunction - gas bubbles in the liquid line, for example.
If the sound is from the condensate drain it's water - a different topic entirely.But indeed I've come across a clogged condensate drain line that causes refrigerant to back up in the drip tray, then the line clears, perhaps by a combination of soaking, water pressure, and time, and the drain opens enough for the condensate to drain out thorugh a partly-blocked and gurgling drain trap.
That's just a guess as I can't see and know almost nothing about your system. Check that and then we'll continue.
Followup by Brian
Thanks. It's definitely not from the condensate drain. The lines are very closely routed but it appears to be coming from the smaller / liquid line going in to the air handler. That's the location where I hear it.
I have about 20 feet or so between the Heat-Pump pump outside and the Air handler inside the basement and I will occasionally with hear "the liquid noise" about 1 foot before the line goes into the air handler.
It's funny though: Is it the changing / cooling temperatures outside as the temps drop, that makes the sound happen?(I ask this because the heat pump was not running for 3 days prior to me hearing the sound in the liquid line).
I only hear it "every now and again" when the heat pump has not been running like this. (I do hear the same noise when the unit is running as well - usually before / after the reversing valve switches).
Reply by (mod) -
Sounds like gas bubbles in the liquid refrigerant line - as I suggested.
After running the shower our toilet gurgles, then drains out
After running the shower for 10 minutes, the toilet gurgles, drains out, and then fills to the brim - hands off. - On 2017-06-22 by yhanja T
Reply by (mod)
This isn't a refrigerant piping noise (the subject of this page) but I know that toilet gurgle problem.
I suspect either inadequate or blocked plumbing vent piping at your building OR a partical building drain blockage that is downstream from both toilet and shower.
See the diagnosis and repair advice
at BLOCKED PLUMBING VENT & GURGLING / SLOW DRAINS - glub glub noises from toilets or other fixtures
On 2016-09-20 0 by Anonymous- Gurgling sound in our HVAC system after work on the refrigerant piping system
I have a split system with two zones. An upper (second floor) and a lower (basement).
The upper system stopped working and was diagnosed as a leaking coil.
The coil was replaced with a "higher capacity" coil , and now works fine.
But now, only when the system is running, I hear very loud running water sound from this upper unit. It's like a faucet full blast!
It stops , and starts, as soon as the unit shuts off or on. The installer , via a phone call, said it may be the condensation from the more efficient new coil.
As loud as it is, I have a hard time believing it's condensation.
Thoughts?
Reply by (mod)
That sounds more to me like an improper refrigerant charge and bubbling in the refrigerant piping. Ask your service company to check the refrigerant piping for gas bubbles and to correct the charge.
The air sending unit continues to make a running fluid noise in the pipes after the fan shuts.
The weird thing is that a loud noise will stop the running water noise in the air sending unit. It makes no sense. When I yell "stop" it stops if not the water sound in the pipes continues. Any ideas? 520-302-9990 John (Aug 31, 2015) john stanaway
Reply:
John:
Maybe we can hire you to get some other annoying things to stop by shouting at them - sounds remarkable!
I'm guessing there is gas in the refrigerant piping OR condensate drain water noise. See if you can pinpoint the source
More gurgling sounds that are also described as "running water noise" are described
at GURGLING SOUNDS from the AC or refrigerant piping
Just wanted to update you on the water rushing sound when my neighbors A/C is running.
The property manager had a heating and cooling contractor look into this and he concluded that the problem is how the lines were run during construction. There are three sets of lines running through the foundation just below the outside wall.
That outside wall is my bedroom wall. He did check the freon and found it to be correctly serviced.
So that's it. They say it's not financially feasible to repair.
I want to thank you again for your time and help. - by private email from Paul Murnane 2016/07/17
Reply:
Thanks for the update. I'm disappointed, though and I'm not confident in that "checked the freon" step. An A/C unit may continue to cool with improper refrigerant charge - for a while. While of course there may be a design or condition about which I'm uninformed, in normal A/C systems properly set-up, there are no "running water sounds" in the refrigerant piping.
The high pressure line from compressor/condenser to the refrigerant metering device at the cooling coil is filled with liquid refrigerant. Filled. The suction line on the outlet end of the cooling coil is filled with low pressure gas. Filled.
Running water sounds in refrigerant piping might come from:
Sooner or later this noise chicken will come home to cackle (or roost) as gas bubbles in the liquid refrigerant line probably mean an undercharge and perhaps a refrigerant leak that ultimately means the system will stop cooling. If you and I are still around I hope you'll let me know when that happens.
Reader follow-up:
Question. Would evacuating and recharging the system be a course of action? And is this an expensive process? Or is the way to look at it do this and you won't have to replace the compressor? - Paul Murnane
Moderator reply:
Yes. Keep in mind that anybody diagnosing a complex system by e-text is unable to see onsite clues that would shout loudly to any competent expert who is on-site.
But generally assuring that the system is properly charged is a step techs take to address the problem we're discussing. Some HVACR systems include a sight glass on the refrigerant line that allows the tech to actually see the refrigerant gas bubbles but most residential systems don't.
A tech who's trying to guess at the refrigerant charge on a running system will measure temperatures on the high and low lines, but all that tells you is that there is enough refrigerant to cool the coil, not that the full measured charge called for by the manufacturer has been placed into the system.
It's an expensive and low quality but very common repair to simply add enough refrigerant to get the system cooling. That is very likely to be less than the charge volume specified by the manufacturer (and profitable for the service company). If there is an ongoing refrigerant leak, the system will ultimately stop cooling again, perhaps first icing the coil then stopping cooling entirely.
Reader follow-up:
I've convinced my property manager to get yet another contractor to come address this. The intent is get someone to evacuate and service the system.
Hopefully, they'll really fix what cause the problem in the first place. She told me that I could have you come and access the situation. I sure wish you could! But I told her that wasn't possible.
She did ask about you as far as your credentials. I didn't recall for sure, but I knew you had years of experience.
I'll keep you advised.2016/07/22 My latest update.
Maintenance supervisor says he evacuated system and serviced it. He says he did this Wednesday. Odd thing. I was home all day and the Property manager gave me a heads up that he would be doing the work that morning and I didn't see anyone that day around the condenser in question.
I was wondering if you would be kind enough to provide a list of equipment needed to perform this task. I know you have to have something to capture the old freon, right? And you need a pump to suction the system.
And if I recall it's usually a good practice to leave it in a vacuum to check if you have a change in your gauges over a two hour period which if you did meant you had a leak.
Anyway. if you could do this, it'd be nice. Of course I would understand if that's not in your realm. I can research it and come up with the info. - Paul Murnane
Moderator reply: equipment needed to evacuate and then properly charge an HVACR refrigerant system
As we state at REFRIGERANT LEAK REPAIR, SAE J-2788, requires that
... all service equipment manufactured after December 31, 2007, must recover 95% of the refrigerant and recharge to within 1/2 ounce
To put a *measured* or "factory-specified" refrigerant charge into an HVACR system the system has to be evacuated - as you say. TO do that in compliance with current codes, the tech has to hook up a pump that removes refrigerant and pushes it into a storage cylinder (presumably for later recycling) as we no longer discharge refrigerant to the atmosphere.
In the old "destroy the earth" days we used to dump refrigerant to the atmosphere, run a vacuum to remove air from the system, possibly install a new filter-drier on the system to remove any remaining (and troublesome) moisture when the system was to return to operation, and then use a can of refrigerant and a charging cylinder to install the new measured charge.
Currently that job is typically handled by a wheeled kit that includes the vacuum pump, hoses, gas recovery and gas charging cylinders. It's not something that fits in someone's back pocket un-noticed.
Below I copy in a typical example photo though there are both larger and smaller versions of this machine.
The pump is typically connected to the service fittings (Hi and Lo port connections) on the compressor/condenser unit outdoors.
Similar equipment is then used to place a measured charge into the system. Yes good procedure would be to leave a vacuum for 24 hours to check for leaks; not every tech might do that, however.
Watch out: Incidentally a second source of bubbling sounds heard in the refrigerant piping suction line near the compressor could be refrigerant oil pooling in that location. However for in your case a refrigerant oil pooling problem does not sound like the noise source that you have been describing.
More information on charging refrigerants in an air conditioner, heat pump, or other refrigeration equipment is
...
Continue reading at UNDER CHARGED REFRIGERANT, EFFECTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
REFRIGERANT PIPING GURGLING at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.