Air Conditioner Compressor & Refrigerant Pressure ReadingsRefrigerant charge quantity for air conditioners & heat pumps:
This air conditioning repair article series discusses the the diagnosis and correction of abnormal air conditioner refrigerant line pressures as a means for evaluating the condition of the air conditioner compressor motor, which in turn, is a step in how we evaluate and correct lost or reduced air conditioner cooling capacity.
We explain how overcharging or undercharging of refrigerant in an air conditioner or heat pump is detected and we list the effects of overcharged or undercharged refrigerant.
We discuss how to diagnose refrigerant pressure problems; how to determine the proper refrigerant charge quantity.
Definitions of Heating Ventilation Air Conditioning & Refrigeration (HVACR) "high side" & "low side" pressures; typical refrigerant pressures; effects of overcharged or under-charged refrigerant are found here as well.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Measuring the refrigerant pressure in air conditioning, heat pump or other refrigerant systems can diagnose a range of operating problems including a refrigerant leak, over charging or under charging.
Low refrigerant pressures: Refrigerant pressure readings measured at the air conditioning compressor/condenser unit and which are found to be too low on the high pressure side (compressor output) or on the low pressure side (compressor input or suction line) can indicate a problem with the compressor's ability to develop normal operating pressure ranges and thus will affect the cooling capacity of the air conditioning system.
High refrigerant pressures: Abnormally high compressor output pressures are also possible but are less likely.
Both of these conditions are explained here.
If after reviewing the refrigerant pressure, temperature, and compression ratio information in this article, you have determined that you have a refrigerant pressure problem or a refrigerant leak, there are procedures to address those issues.
These corrections will include getting the right refrigerant charge by any of several means (weight or volume measurements or some techs monitor refrigerant line temperature).
It also means finding and fixing the refrigerant leak if the problem was simply lost refrigerant.
For help with these corrections,
see our RECOMMENDED ARTICLES list at the bottom of this page.
...
Let's explain "low-side" and "high-side" air conditioner compressor motor pressures and what they mean.
Air conditioning service manuals and training refer to:
Low-side air conditioner compressor motor pressure:
This is the pressure in the air conditioner's refrigerant suction line
(low side pressure during compressor operation) and this will be a relatively low number, often
less than 100 psi.
During operation, refrigerant gas is returning to the compressor from the cooling (evaporator)
coil in this line.
If we connected the suction line directly to a sealed vacuum test gauge we'd actually find
that the compressor could pull an actual vacuum on the line.
The low-side of an air conditioning system is always located inside of the space to be cooled, or inside of an air handler which moves air through the space to be cooled.
By lowering the pressure in the cooling coil located on the "low side" of the air conditioning system, the compressor permits liquid refrigerant to be discharged into the cooling coil where the change of refrigerant state from a liquid to a gas absorbs heat and brings the cooling coil to the proper operating temperature.
The LOW SIDE of a refrigeration system is the low-pressure and low temperature half of the system. Normally this is the indoor air handler - located inside the space that is to be cooled by bringing indoor air to operating temperature. (For a refrigerator this is typically 38 to 45 °F.)
On my own graduation from HVAC school the instructor suggested that since most of the time when people are tossing out an old refrigerator the problem was electrical rather than the compressor, we should look for an old Frigidaire refrigerator and salvage its compressor motor.
Indeed I did just that and for years we used to use an old Frigidaire™ rotary-design compressor motor as our vacuum pump when we needed to get the air out of a refrigeration system prior to charging it with new refrigerant. - Daniel F.
...
Typical residential air conditioning refrigerant pressures vary depending on the model, compressor motor size and design, and the refrigerant used.
The design pressures may be provided on labels attached to the equipment but the actual air conditioner operating pressure will vary in part as a function of the incoming air temperatures.
"Charging Charts" (such as the commercial unit charging chart shown here) are provided in service manuals to determine the target suction vacuum (negative) pressure and output (positive) pressure for a given compressor motor.
Use of the charging chart for the specific compressor is the correct way to service it.
The following example refrigerant pressures are based on "rules of thumb" that get you in the right "ballpark" if no charging chart is at hand.
Example of actual air conditioner compressor high side output pressure:
Using R-22 refrigerant and assuming an outside air temperature of 85 °F called for 120 °F inside the compressor (add 35 °F to incoming air temperature) and an output high-side compressor pressure of about 260 psi.
Example of actual air conditioner low side input or suction line pressure during operation:
Low-side pressure during normal operation of the same compressor model and refrigerant and the same outdoor air temperature of 85 °F called for 45 °F temperature entering the compressor (subtract 40 °F from incoming air temperature) which on the service chart indicates that the incoming or suction line pressure would be about 75 psi.
Example of a more theoretical air conditioner or heat pump pressure and temperature at the compressor and at the cap tube or thermostatic expansion valve:
During normal operation: at an outdoor temperature of 72 °F, liquid refrigerant (R12 for example) leaving the outdoor condensing coil and entering the cap tube or TEV might be at 100 psi and 95 °F.
These numbers vary by changes in ambient temperature, compressor model, and refrigerant gas used.
On the low side of the TEV or cap tube (in the cooling coil in the air handler) where the liquid refrigerant is changing state to a gas, it may be cooled down to 10 °F. and by the time the refrigerant leaves the cooling coil (evaporator coil) and gets back to the compressor motor it will be all vapor and may be at just 15 psi.
[R12 refrigerant changes from liquid to vapor at 14.6 psi at 10 °F.]
What do "High" or "Low" Refrigerant Pressures Mean? |
|||
| Low Side Pressure Reading | High Side Pressure Reading | Compression Ratio | What to Do |
| Normal Range | Normal Range | HVAC: 2.3:1 to 3.5:1 Coolers: 3.0:1 to 5.5:1 Freezers: 6.0:1 - 13.0:1 |
Proper Operation No Action Needed |
| Low | Low | Refrigerant Lost |
|
| Low | High | Check for blocked TEV or capillary tube | |
| High | Low | Check compressor operation Check TEV operation |
|
| High | High | Check/Correct refrigerant charge (probably over-charged) | |
When you measure heat pump or cooling system pressures makes as much difference as where you measure it.
When an air conditioning or heat pump system has turned off and been off for some time (30 minutes or more) pressures equalize throughout the system between the high and low sides.
At that point the refrigerant pressure in both the high side and low side of the air conditioner or heat pump system will be in accordance with the ambient air temperature and the properties of the particular refrigerant gas present.
The static or equalized system refrigerant pressure will be defined by the refrigerant gas type (which defines its boiling point and pressure at various temperatures).
For example with that cute old R12 refrigerant, as long as there is just about any refrigerant in the system - enough so that there is some liquid refrigerant, i.e. it's not all just gas) then in equalized condition at 70 psi ambient temperature the refrigerant pressure will be 70 psi.
With a temperature correction chart you can read the static or equalized refrigerant pressure for any refrigerant gas and the actual ambient temperature.
Reminder: this refrigerant gas behavior means that if you use pressure test gauges to measure the refrigerant pressure in the static or equalized air conditioning or heat pump system, the gauges only tell you the refrigerant pressure, not the quantity of refrigerant that is present in the system.
...
Information and tables on normal and abnormal HVAC compression ratios are now found
...
Comparison of Refrigerant Gas Properties |
||||||||
| Refrigerant Gas | Properties | Refrigerant Type14 |
Replaces Substitutes20 |
Replaced By20 |
GWP1 | ODP1 | Com- |
Pressure Charts & Details |
| R11 | Trichlorofluoromethane CFC-11 = Freon-11 = R-11. Banned-1996 Montreal Protocol |
CFC | 4000 | 1.0 | Y | Basis for ODP comparisons | ||
| R12 | Dichlorodifluoromethane Freon No remaining life Banned-1996 Montreal Protocol |
CFC HFC |
R124 R134a R401a R401b |
2400 | 1.0 | N | n/a | |
| R12 B1 | CFC | R124, R142b | N | |||||
| R13 B1 | Bromotrifluoromethane Halon 1301 or BTM CBrF3 |
CFC Halon |
R410A, ISCEON® MO89 R402B? |
10 | N | |||
| R22 | Chlorodifluoromethane No remaining life Do not go to R-410A |
HFC HCFC |
R404A | R407c ? | 1700 | 0.05 | Y | R22 REFRIGERANT PRESSURES R22 pressure chart, high & low side |
| R23 | Additions banned 1 Jan 2020 Reclaimed use permitted to end of 2029 |
HFC | R13, R503 Halon 131 |
18,400 | 0 | N | ||
| R32 | Difluoromethane, CH2F2 Use in new equipment |
HFC | R134A ? R410A ? |
N ? | R32 REFRIGERANT PRESSURES | |||
| Eco 32 | Blend: Propane R290 + Ethane R170 reduced-GWP |
HC |
R32, R410a | ? | ? | Y | Eco-32 REFRIGERANT PRESSURES 17 | |
| R32 | Difluoromethane R 410A replacement in new equipment Not to be used as a retrofit |
HFC | R410A | 650 | 77119 | 0 | Y | R32 REFRIGERANT PRESSURES |
| R113 | Trichlorotrifluoroethane |
CFC | 4800 | 0.8 | ||||
| R114 | Dichlorotetrafluoroethane Banned-1996 Montreal Protocol |
CFC | R124, R142b | 3.9 | 1.0 | |||
| R123 | Dichlorotrifluoroethane | HCFC | R11 | 0.02 | 0.02 | |||
| R1234YF | Automotive AC 2,3,3,3-Tetrafluoropropene |
HFO | R134A | 4 | Y | R1234YF PRESSURE CHART [PDF] 10 | ||
| R1234ZW | [citation needed] | |||||||
| R124 | Chlorotetrafluoroethane | HCFC | R12, R114 | 620 | 002 | |||
| R125 | Pentafluoroethane | 3400 | 0 | |||||
| R134A | Tetrafluoroethane |
HFC | R12 |
1234yf R-152a R-744 |
1300- 1430 |
0 | N | R134 REFRIGERANT PRESSURE CHART |
| R143A | Trifluoroethane | 4300 | 0 | |||||
| R152A | Difluoroethane | 120 | 0 | Y | ||||
| R245A | Pentafluoropropane | ? | 0 | N | Flammable under pressure | |||
| R290 | Pure HC Propane, CARE® 40 | HC | R12, R22, R502 ? |
3 | ? | Y | R290 PRESSURE CHART [PDF] 3 | |
| R401A | Blend 53% R-22, 34% R-124, 13% R-152a |
HCFC | R12, R500? | 1100 | 0.037 | N | ||
| R401B | Blend 61% R-22, 28% R-124, 11% R-152a |
HCFC | 1200 | 0.04 | N | |||
| R402A / HP80 | Blend of R-22 & R-125 w/ hydrocarbon R-290 (propane) 38% R-22, 60% R-125, 2% R-290 |
HCFC | R502 | 2600 | 0.02 | N | R402A PRESSURE CHART [PDF] 13 | |
| R402B | Blend of R-22 and R-218 w/ R-290 (propane) |
HCFC | R502 R-13B1? |
N | ||||
| R403B | Blend of R-22 and R-218 w/ R-290 (propane) |
HCFC | R502 | N | ||||
| R404A | Blend, replaces R502 & R22 Short remaining life2 44% R-125, 52% R-143a, R-134a |
HFC | R502, R22 | 3300 3922 ? |
0 | N | R404A PRESSURE CHART [PDF] 4 Flammable under pressure |
|
| R407A | Blend 20% R-32, 40% R-125, 40% R-134a |
HFC | R22 | 2000 | 0 | N | ||
| R407C | Blend 23% R-32, 25% R-125, 52% R-134a |
HFC | R22 | 1600 | 0 | N | ||
| R407H | Mixture of R32, R125, R134A, not ozone resistant |
HFC | R22, R-404A?, |
1490 1495 |
- | N | R407H PRESSURE CHART [PDF] 5 16 |
|
| R408A / FX10 | Blend, Forane® | HCFC | R502 | 3152 | 0.024 | N | R408A PRESSURE CHART [PDF] 13 | |
| R409A | Blend of R-22, R-142b | HCFC | R12 | N | ||||
| R410A | Domestic HVAC |
R-22 | R-32 Eco-32 |
2088 | N | R410A REFRIGERANT PRESSURE CHART | ||
| R414B | Blend of R-22, R-124, R-142b w/hydrocarbon R-600a (isobutane) |
HCFC | R12 |
N | ||||
| R448A | Blend R32, R125, R134A, R1234YF, R1234ZW |
HFC HFO |
R404A or R507 | 1273 | N | R448A / N40 PRESSURE CHART [PDF] 6 | ||
| R449A | Blend | HFC HFO |
R404A | 1282 | N | R449A PRESSURE CHART [PDF] 7 | ||
| R452A | Blend | HFC HFO |
R404A, R507 | 1945 | N | R452A PRESSURE CHART [PDF] 8 | ||
| R452B | Blend blend R32 + R125+ R1234yf? |
HFC HFO |
R410A | Y | ||||
| R454B | Blend | HFO | R410A | Y | ||||
| R500 | Blend R-12 / R-152a Banned-1996 Montreal Protocol |
CFC | R12 | N | ||||
| R502 | Freon |
CFC | R-22 / R115 | R404A | 4.1 | 0.283 | N | R502 PRESSURE CHART [PDF] 12 Becomes flammable under pressure |
| R507 | Blend 50%-50% R-125 & R-143A - or 45% R-125, 55% R-143 |
HFC | R22, R502 | 3300 | 0 | N | R507 PRESSURE CHART [PDF] 11 Becomes flammable under pressure |
|
| R600A | Iso-butane | R12, R134 | 3 | Y | R600A PRESSURE CHART [PDF] 9 | |||
| R717 | Ammonia - NH3 Among oldest refrigerants |
R134A-? R32-? |
0 | 0 | Y | Flammable at high temp. | ||
| R718 | Water - H20 | 0 | N | |||||
| R729 | Air | 0 | N | |||||
| R744 | Carbon Dioxide - CO2 GWP REFERENCE GAS |
1 | 0 | N | ||||
...
These refrigerant line pressures are the natural pressure at which each refrigerant gas would be found at ambient temperature. If your HVAC equipment has been off long enough for all of its components to reach ambient temperature and thus its high side and low side pressures have had time to equalize, then at our example temperature of at 30°C / 86°F Ambient Temperature you will see the gauge pressures given in our table below.
Comparison of Refrigerant Pressures at 30°C / 86°F Ambient Temperature |
|||
| Refrigerant Gas | Gauge Pressure - BAR | Gauge Pressure - PSIG | Pressure Charts & Details |
| R22 | 10.9 | 158.2 | R22 REFRIGERANT PRESSURE / TEMPERATURE CHARTS - and rules of thumb |
| R32 | 18.26 | 264.80 | |
| R134A | 6.69 | 96.00 | |
| R290 | 9.78 | 141.77 | R290 PRESSURE CHART [PDF]3 |
| R404A | 13.3 | 190.40 | R404A PRESSURE CHART [PDF]4 |
| R407H | see R404A / R507 | R407H PRESSURE CHART [PDF]5 | |
| R410A | 17.82 | 258.42 | |
| R448A | 11.18 | 162.07 | R448A / N40 PRESSURE CHART [PDF] 6 |
| R449A | 10.83 | 157.02 | R449A PRESSURE CHART [PDF] 7 |
| R452A | 12.00 | 173.97 | R452A PRESSURE CHART [PDF] 8 |
| R502 | 12.00 | 173.97 | R502 PRESSURE CHART [PDF] 12 |
| R507 | 13.57 | 196.82 | R507 PRESSURE CHART [PDF] 11 |
| R600A | 3.03 | 44.00 | R600A PRESSURE CHART [PDF] 9 |
| R1234YF | 6.82 | 98.92 | R1234YF PRESSURE CHART [PDF] 10 |
| R1234ZW | |||
...
Here is a list of pages where you can download free refrigerant pressure/temperature charts, provided courtesy of various HVACR manufacturers that we cite.
...
Information on different types of refrigerants can now be found
...
More about environmental concerns among refrigerants and the move towards refrigerants that offer less contribution to global warming and its costs is now found
...
...
Continue reading at REFRIGERANT PRESSURE DIAGNOSIS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see REFRIGERANT PRESSURE READING & CHART FAQs - questions & answers posted originally at this page.
Or see these
REFRIGERANT PRESSURE READINGS & CHARTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.