Legionella contamination in air conditioners & heat pumps:
This article explains cause, hazards, & prevention of Legionella bacteria contamination in air conditioners, how to clean air conditioning systems, Legionnaire's disease prevention & cleaning suggestions for air conditioning equipment and condensate trays, including condensate piping, traps, drains, condensate pumps, and concerns for mold, Legionella bacteria, and other hazards associated with air conditioning systems, cooling towers, and evaporative coolers.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Legionellosis or Legionnaire's Disease and Pontiac Fever are serious respiratory illnesses with roughly a 10% fatality rate in the United States.
The chart at left shows the increase in the rate of reported cases of Legionnaires' disease in the U.S. from 2000 to 2017, as given by the US CDC. Original source: National Notifiable Diseases Surveillance System at the CDC. The cause of this increase is uncertain but experts pose a combination of an increase of Legionnella bacteria in the environment (is global warming a factor?), an improvement in and increased use of testing for Legionella contamination in building cooling towers and water supplies, and possibly an increase in the susceptability to Legionella in the U.S. population.
It's also significant that occurrences of Legionnaires' disease are probably significantly under-reported and under-diagnosed in the U.S.
Yet the disease is almost entirely preventable by appropriate inspection, testing, and management of water systems in buildings. Those systems include building air conditioning systems, particularly cooling towers and potable water supply systems, including both hot and cold water supply but particularly water heaters.
The most-significant sources of Legioniella bacteria in buildings are cooling towers used in large commercial building air conditioning systems and potable water systems, both hot and cold water, but particularly water heaters that can serve as a bacteria farm for Legionella and other bacterial contaminants.
Legionella bacteria were first recognized as a source of respiratory illness and disease in the air conditioning system at the Bellevue-Stratford Hotel in Philadelphia, PA in the U.S. in July 1976. There the American Legion was hosting a three day convention attended by more than 2,000 Legionnaires. Of 189 diagnosed cases of what was at first an unidentified illness, 29 people died.
By the end of January 1977, a U.S. CDC investigation had isolated the cause of these illnesses and deaths to the Bellevue-Stratford Hotel's air conditioning system cooling tower that bred the bacteria along with the air conditioning duct system that spread the bacteria through the building's occupied space. (Confusing the investigation was the occurrence in the same population of the American Legion Convention attendees of 14 cases of swine flue of whom six died.)
Except for rooftop swamp coolers and a much smaller number of evaporative coolers used in private homes (mostly in the American Southwest), the principal cooling tower bacterial hazard occurs on larger buildings such as hotels and offices. However Legionella bacteria hazards are indeed possible in private homes as well, in air conditioning condensate handling systems and in potable water supply equipment, particular water heaters.
In this article we discuss cleaning procedures for HVAC equipment in order to prevent Legionella bacteria formation or to remove it if present, a key step in preventing Legionnaires' disease.
We discuss steps to prevent Legionella bacteria growth in water heaters in a separate article found
at Legionella BACTERIA in WATER HEATERS
Should we be putting bromide or chlorine tablets in our condensate trays to keep bacteria from growing?
If we should be, then do we need to alternate bromide with chlorine on some type of frequency to prevent development of resistant bacteria?
[Click to enlarge any image]
We're discussing condensate trays from mechanical equipment like heat pumps, fan coil units and air handlers with AC coils.
These pieces of equipment have condensate trays which are then drained through a small pipe, usually clear, but not always, with a trap in it, to a drain.
These condensate trays have some standing water in them when the AC is functioning. Should these condensate trays be treated with an algaecide of some sort?
There are risks beyond mold and algae, in particular Legionella bacteria (legionnaire's disease) which can have an alarmingly high mortality rate, and also potential hazard sources such as biofilms that can include other bacterial and maybe other pathogens.
However the risk of formation of problem levels of mold, bacteria, or other pathogen is probably not the same across all buildings nor types of equipment, and much of the risk may depend on installation and maintenance details at individual installations.
Particularly in climates with a high humidity and a heavy cooling load, and depending on details of the design and installation of the air handler unit and duct work, there is risk of blowing pathogen-contaminated water droplets downstream inside the air conditioning duct work and thus exposing building occupants.
With rooftop-mounted cooling units such as cooling towers using water, conditions may be still more attractive for growth of pathogens and there is some risk of movement of pathogens out of the cooling equipment to people located nearby and downwind from the equipment, even if they are outside the building which the equipment actually serves.
Photo: a residential swamp cooler or evaporative cooler atop an Arizona home. Evaporative coolers, operating in a manner similar to commercial-sized cooling towers, may harbor Legionella bacteria.
See details at SWAMP COOLERS
Use the links listed at the ARTICLE INDEX the bottom of this article to read additional details on this topic including recommended cleaning procedures and details of the Legionella hazard in air conditioning systems, humidifiers, etc.
...
Continue reading at WISCONSIN PROTOCOL for Cleaning A/C or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
Legionella BACTERIA & HVAC EQUIPMENT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.