Building Inspection, Diagnosis & Repair Info

Gutter defects (C) Daniel Friedman Gutter Defects, Leaks, Problems

Roof gutter defects & how they cause building leaks, damage, or wet basements & crawl spaces.

Here we list and describe gutter problems and defects including clogged gutters, leaky roof gutters, overflowing gutters, sagging, loose, poorly-sloped or damaged gutters and other roof drainage system problems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Common Gutter Defects & Causes of Leakage & Wet Basements / Crawl Spaces

Gutter Clogs (C) Daniel Friedman

[Click to enlarge any image]

Article Series Contents

The two most common building leaks that cause wet basements or crawl areas originate at the roof drainage system:

  1. Gutter defects: Clogged, overflowing gutters; also gutters that are falling off, improperly sloped, or leaky - discussed here at GUTTER DEFECTS LIST
  2. Downspout defects: Downspouts that are emptying too close to the building; also downspouts or "leaders" that have been disconnected or were improperly connected . Downspout defects are detailed at Roof Downspout or Leader Defects.

Roof Gutter Defects List

Metal roof snow brakes - Bard College (C) Daniel FriedmanOur list of common gutter defects shown just below is followed by illustrations or photographs of many of these conditions.

Clogged, Overflowing Gutters - Inspect & Clean Gutters Regularly

If you see shrubs growing in your gutters (below) you know the roof drainage system has not been cleaned in a long time - look for basement water entry, building wall damage or rot, and related water problems.

Gutter Clots (C) Daniel Friedman

Inspecting from a ladder you may also find that even a small handful of leaves and crud can block the downspout connection (also called an "end drop") leading to gutter overflowing and building water entry (below).

Gutter Clogs (C) Daniel Friedman

Loose Gutters

Take a look around your building for gutters that are actually falling off (or have already fallen off - below left) but also look for loose gutter spikes or brackets (below right).

Loose gutters, before they have fallen away from the building, are permitting roof runoff to miss the gutter and run down building walls, enter soffits or eaves (rot), and by falling close to the building foundation wall, the water concentrating there is likely to enter the building basement or crawl area.

Gutter defects (C) Daniel Friedman Gutter defects (C) Daniel Friedman

Try looking "up" from below the building's gutter system (photo below left). If you see daylight between the back side of the building gutter and the fascia board, check further for gutter backflow, leaks, or simply a gutter that has begun to pull away from the building.

Loose gutter clue (C) Daniel Friedman

A second easy-to-spot loose gutter warning is the gutter spikes projecting out from the gutter edge (below right).

Loose gutter clue (C) Daniel Friedman

Watch out: Don't forget to inspect the gutters closely from the roof edge as well.

Loose gutter (C) Daniel Friedman

A loose gutter may be out past the shingle edge or drip edge but may not be visible from the ground. When it rains, water runs down the building wall at this point.

Inadequate or Improper Gutter Slope

Gutter slope (C) Daniel Friedman

Improperly-sloped gutters will not empty properly and in heavy rain are likely to overflow.

Check that the roof gutters are properly sloped, both in the pitch and in the direction of pitch towards the gutter drains or downspouts.

Our photo (left) shows a desperate attempt to get back proper slope and drainage in a long gutter run that had sagged at its center.

On long gutter runs attached to a roof with a rather short fascia board, it can be difficult to obtain adequate slope.

Roof gutters should slope at least 1-inch in every 200 inches of run; also see SAGGING GUTTERS since even if the gutters were originally installed with proper slope they may have sagged due to loading from clogs, water, ice or debris.

But if the total length of the gutter run is long and the fascia is not very tall, say 6 to 8", then it may be impossible to get adequate gutter slope throughout its total run, even if we push the high end of the gutter right up against the shingle overhang and drop the low end of the gutter to the very bottom of the fascia. If your roof has this problem it may be necessary to add additional downspouts along the gutter's run and/or to divide the total gutter run into shorter lengths.

Then re-start gutter sections higher on the fascia.

Some causes of improper gutter slope include:

Gutter "Overshoot" - Water Flows Over or Past Rather Than Into Roof Gutters

Gutter Mounting Position Affects Gutter Performance & Resistance to Snow & Ice Damage

Gutter location on House

The sketch at left shows optimum gutter placement at the building eaves to catch water spilling off of the roof. As you can see, the gutter location depends in part on roof pitch.

Proper gutter placement is especially important in freezing climates in order to reduce the tendency of snow and ice to "push" the gutters off of the building.

Gutter Overshoot from Too Much Shingle Overhang at the roof Eaves

Example of too much asphalt shingle overhang on a roof (C) Daniel Friedman

Gutter overshoot refers to water that runs down the roof and over or past the roof gutters rather than into them. Some common causes of gutter overshoot include:

Gutter and Downspout Details (C) Carson Dunlop Associates

The sketch above shows what happens when roof shingles extend too far past the edge of the roof deck and too far into the roof gutter. The sketch does not show what happens if the roof shingle projection past the roof deck is not supported by drip edge: with time the roof shingles curl down into the gutter itself, and sometimes crack or even break off at that point.

Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

Gutter and Downspout Details (C) Daniel Friedman

Gutter and Downspout Details (C) Daniel Friedman

Install a Gutter Defelector to Cure Gutter or Roof Valley Runoff Overshooting the Gutters

Photograph of Photograph of roof shingle mineral granules in the gutter due to hail damage

Our roof gutter deflector photos (above) show a deflector installed at the end of a roof valley (above left) and at a different home, evidence of spillage and splash-up below a roof valley due to gutter overshoot (above right).

Take a closer look at the gutters in our photo at left where a valley spillage gutter deflector is installed: notice all those mineral granules.

This roof had been damaged by hail. Our OPINION was that the extra loss of mineral granules meant that the roof would probably have a shorter remaining life than usual.

Here is another closeup photo of a gutter deflector installed below a roof valley.

Roof Gutter or Eaves Trough Inspection & Repair Articles


...

Continue reading at GUTTER DEFECTS, MORE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Suggested citation for this web page

GUTTER DEFECTS LIST at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to GUTTERS & DOWNSPOUTS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT