Wet Corroded Air Duct FAQsQuestions & answers about how to diagnose and fix rusty, wet, or corroded air ducts in HVAC systems. What are the hazards, where does the water come from, what cleanup is needed, and how do we prevent this problem in the future?
This article series describes causes, health concerns, & repairs to correct wet or corroded heating & cooling ducts.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions and answers about the causes, dangers-of and cures for rusty or wet air ducts and registers were posted originally
at WET CORRODED DUCT WORK - be sure to check out the diagnostic suggestions on that page.
Went into crawl space to investigate cause for two hot rooms. I found it.
Main supply duct has at least two large leaks and is quite rusty. I’m guessing the ducts weren’t replaced when the system was updated from swamp cooler.
The supply trunk that main sits on is sagging from weight as well. How do I fix this? New main supply and replace rusted trunks? - On 2018-12-16 by Josh
Reply by (mod) - Replace badly-rusted metal HVAC ductwork
Josh If my HVAC system had ducts in such poor condition, I'd replace them.
And I'd want to find and fix the sources of crawl space moisture to reduct the mold and other damage risks therein.
Followup by Josh
Thanks Dan, I work in the plumbing department of a MEP company.
Hoping the boys in AC can help me out as I have no clue about duct work.
Reply by (mod) -
Ok Josh. Keep me posted. Also I'd like to see photos of the duct interior.
We see corrosion at the ends of many of our HVAC ducts where they end at the registers. The amount of rust is not massive - more like drops/splotches. We ran our camera down each duct in question to see how far the rust went and it was only at the very end points where the registers are.
We assume something may have spilled over during construction. In any case, is there cause for concern for this level of corrosion? Of note, the ductwork in our unfinished basement is pristine. There is no evidence of any issues there.
Additional info: My husband just told me one of the ducts (laundry room) has corrosion that's more of a patch in terms of the area (vs small splothces) that's about 5" in diameter). And, in that duct, when he ran the camera down, although the rust didn't continue, he could see marks like staining for another 18" where some liquid had obviously run. On 2024-05-19 by Sarah -
by InspectApedia Publisher
@Sarah,
It may be that all you need to do is clean the areas of corrosion and spray a reasonably secure sealant on the rusted surface.
But it was certainly help me form an opinion if I could see some photos of the damage. You can post one photo per comment so use more comments if you have more photos and that will let me make further suggestions.
Daniel
by Sarah
@InspectApedia Publisher, Thank you very much. I'm going to send two pics: one that's the lightest amount of corrosion in the stack head and one with the most. I'd also be interested to know of any product you could recommend we could use as a sealant over the rusted areas.
I'm very sensitive to VOC's so wouldn't want to introduce something that will smell nasty. If I didn't use a sealant, what would be the downside to leaving things as they are?
Here's the second photo, which is an example of the most impacted stack head.
by InspectApedia Publisher
@Sarah,
First let's put an important safety question to bed.
Please confirm that we are talking about duct work, that is the metal large diameter tubing that delivers heated air to rooms in your home or returns cool air back to a furnace.
We need to be sure that we are not discussing a fluent connector that vents exhaust gases from combustion into a chimney or ultimately to outdoors.
Concern is that if you had a hole like that in a chimney or flue vent connector it's dangerous, risking carbon monoxide or other hazards that an extreme cases can even be fatal.
In contrast if the holes are simply induct work then what we are facing is an inefficiency from air leaks and possibly a concern for moisture induced problems elsewhere in the system..
Next I want to be sure that the location of these leaks, assuming they are induct work, is nowhere near the furnace or air handler itself. That's because leaks at the air handler could cause costly and dangerous damage to the heat exchanger in that device.
So tell me where these are in your home.
Finally, at least for the moment, I'm seeing more than simple superficial rust. I'm seeing rust perforation. That tells me this is an old and long-standing problem.It also means that nearby sections of the sheet metal that form your ductwork are probably fragile from corrosion even if they haven't yet become perforated. In a case like this the most effective repair, particularly if the duct work is accessible, it's just simply replace it with new sections of metal ductwork.
I don't think it would be useful to try to spray it or use another sealant.
A temporary measure, which I emphasize is only temporary, Voice spraying or painting anything at all and instead simply uses some metal tape to cover the perforated or damaged duct sections on its exterior, or if those aren't accessible possibly with a bit of preliminary cleaning you could get the tape to stick on the inside of the duct.
You'll find that the metal tape, which is basically an adhesive coated aluminum with a peel off layer, is very sticky and will adhere well to metal ductwork.by Sarah
@InspectApedia Publisher, Thank you so much for your prompt and thorough reply. To answer your questions: Yes, this is duct work. No, it's a fluent connector. The corrosion is not holes. The exterior of the duct work is intact and looks pristine.
The locations are not near the air handler. They're at the opposite end of the system. Nothing is perforated. I see in the second photo there's a black spot that looks like it is, but it isn't. Again, there is no corrosion on the exterior of any of the duct work at all. The corrosion appears to be superficial and located at the stack heads / end of each duct at the floor registers.
by InspectApedia Publisher
@Sarah,
Ok, on that case just clean the surfaces. Simple damp wiping is fine.
How long will it take mobile home flexible plastic under the home ductwork to rot if left lying on the ground? On 2022-04-05 by David Robinson -
by Inspectapedia Com Moderator
@David Robinson,
I want to be helpful but I'm not sure what material we're discussing. Plastic flex-duct or a plastic vapor barrier under the mobile home on the ground, or plastic stapled up underneath a mobile home - stapled to its under-side ?
In any event plastic doesn't actually "rot " - as that's an organic process. Leaves and wood rot.
But plastic will deteriorate, become brittle, and begin to fall apart - with age, exposure to sunlight, and over a longer period if protected from the weather.
There are also some brands of flex duct that disintegrate because of defective product - discussed at this website.Watch out: however for rodent damage to flex duct left unprotected on or close to ground, as well as for water entry and contamiantion through holes or tears in that ductwork.
I noticed rust on the ceiling AC/heat duct registers this summer. Most rust on the kitchen register. Less rust noticed on the 2 bathroom duct registers. This is a one story house. the bedrooms also have less rust. I keep the largest master bedroom register closed all the time.
I mentioned the problem to my HVAC service tech and he stated it was condensation, but failed to offer a solution. The office staff stated it was not anything to be worried about. However, I've lived in several homes over the years and I have never had rust spots on duct registers.
After reading your advice on several posts should I seek an inspection from a professional duct cleaning company and fire my HVAC servicing company? On 2022-01-21 by Charlotte M
- H
by Inspectapedia Com Moderator
@Charlotte M,
I agree with your HVAC service tech that the most-likely cause of rusty metal HVAC ducts is condensation, though on a few occasions we've found roof leaks and even plumbing leaks that sent water into the ductwork causing the same rust damage.
You don't give country and city of location: some areas such as warm humid coastal areas cause a much bigger load on your system's ability to dehumidify indoor air. An over-sized cooling unit may also fail to dehumidify properly.
You might check your home to be sure there are no sources of unusual indoor moisture and also ask your service tech if she agrees that your system is dehumidifying indoor air properly during humid weather.
I discovered that a bedroom vent on an outside wall which is buried in a slab was full of sand. I vacuumed it out and found that it was plugged for at least two feet. No heat is coming through the duct so it may be clogged further down.
My vacuum hose was only about six feet long on a 20 foot run that ends in a crawlspace where it connects to the rest of the duct-work leading to the furnace plenum. The pipe must be collapsed or rusted out somewhere along the run and sand has gotten in where it was possibly carried along by airflow until it clogged the pipe?
The other less desirable answer is that rodents such as chipmunks have gotten into the ducts through the hole and moved sand to the end to clog that vent? I say this because we have chipmunks under our slab (including the garage which is in front of the bedroom).
I have seen piles of sand on my sill plate in the crawlspace next to the slab where they are presumably excavating burrows and depositing it there (which is another major problem all on it's own).
So my questions is how to restore the duct to workable condition. It is a straight 20 foot run that I have access to from the crawlspace. It is five inch pipe so my thought was to sleeve it by feeding through a 4 inch pipe to the vent.
This will require me to first clean all of the sand out of the existing duct and get a better inspection camera through to see if this is possible. I was thinking of heavier gauge rolled galvanized such as the snap lock pipe from Nordfab or some other manufacturer or heavier gauge aluminum pipe that won't rust.
I could re-rout a new vent through the attic but that would require going from the plenum up through the wall of the garage and into the attic. A total run of about 60 feet or more. The other option would be to just fill the duct with foam and add a baseboard electric heater. Any thoughts or suggestions? On 2022-01-06 by Robin -
Reply by Inspectapedia Com Moderator
@Robin,
Please read our advice at
SLAB DUCTWORK
then don't hesitate to ask follow-up questions if needed.In sum we suggest abandoning in-slab HVAC ducts as almost always problem prone; above grade any contaminated metal ducts that are not so damaged as to need replacement can simply be cleaned and sanitized by your duct cleaning company.
My dining room ceiling started to show wet spots, after ruling out a pluming leak, we discovered the duct work was covered in condensation, dripping down causing the staining. After taking down more areas, its clear the problem has been there for a while.
We did replace our 20 year old a/c unit a few years back. How long would a problem like this take to show up. There is actually a hole where the duct is "rotted" out. Will wrapping the ductwork stop help? (the black tape is where the hole was on the left, and the seam was a little open on the right.
On 2021-09-15 by Jeannette -
by inspectapedia.com.moderator
@Jeannette,
I might "bandage" duct leak points as a temporary repair, but leaving water inside the ductwork, even if I stopped the leak for now, isn't going to stop further rust, nor future perforations and leaks, nor will it avoid a risk of mold contamination in the duct system.
So we need to diagnose the cause.
If the ducts are rusted through they should be replaced.
When ducts are wet and corroded the cause is usually one of those listed on the page above - such as missing insulation, or condensate being splashed into the duct system from the cooling unit's fan or clogged overflowing condensate pan and drain at the air handler.
Details are at WET CORRODED DUCT WORK
Here's the most recent chaos at my house(I'm renting) but I'm trying not to be too pushy with my landlord because he lost his job at the start of the Pandemic and he's been struggling too...
But what concerns me most, is the widespread areas of dark-green and blackened (once pink) insulation.
My husband and I have a 3 year old daughter living in this home - though she's been with grandma since the ceiling came down. On 2021-07-09 by Heidi Smith -
by danjoefriedman (mod)
@Heidi Smith,
I'm re-posting your photo with what I think are the right annotations identifying HVAC supply-air ducts, return plenum and duct,
and I can but comment on what we can see in this photo:
Observations:
1. The return duct is severely rusted, risking mold contamination in the air handler and ductwork or other pathogens and IAQ hazards (bacteria, allergens);
2. Your comment and the photo suggest that enough water collected in the duct system to wet nearby building materials: insulation, drywall or other ceiling coverings, wood framing; this is the likely cause a ceiling collapse; indeed we see what look like leak stains ob framing below that rusty return duct opening.
3. Proper repair will require at least the following steps:
- identify and fix the moisture source in the HVAC system or at some other building leak(s) if that was the source of water in the duct system
- inspect the air handler and ductwork for debris, other water damage, contamination, and clean ducts that can be cleaned; some of the duct should probably be replaced; and some types of duct such as fiberglass-insulating-board or insulation-lined would be replaced as those cannot be effectively cleaned
The air handler may need to professionally cleaned as well;
- remove all building insulation and drywall and other ceiling materials that were wet as those risk ongoing mold growth and they cannot be cleaned;
- inspect remaining ceiling to assure that it is un-damaged and not at risk of further collapse: a ceiling collapse not only makes a mess, it can injure someone
- If wall-to-wall carpet below this ceiling collapse was wet it probably needs to be replaced along with its padding
- Follow the water! If water also entered the walls then those wall cavities need to be inspected for mold
- clean all exposed surfaces and be sure all demolition is complete and all leaks fixed and all ductwork repair complete before restoring the ceilings;
- Don't do a half-way job or the risk is doubling the cost by having to do the entire job over again later if the original cleanup was insufficient as leaving wet or moldy drywall in a building leaves a growing mold contamination area.
- if inspection finds more than 30 sq.ft. of contiguous moldy material, then professional mold cleaning help would be needed; smaller moldy areas are normally handled by a handyman or HVAC contractor
4. Some insulation stains are caused by air bypass leaks and do not represent a hazard:
see INSULATION STAINS - AIR BYPASS LEAKS
Some insulation is naturally dark green - depending on brand and in that case would not, in and of itself, be a hazard; we could not make out "green insulation" in your photo;
See FIBERGLASS INSULATION IDENTIFICATION & PROPERTIES - inspectapedia.com/insulation/Fiberglass_Insulation_Identification.php
Watch out: you don't give your country and city nor climate so we don't know what use you're making - or not - of this HVAC system and its ductwork, but if the system is mold- or other-contaminated it could be a health hazard to building occupants, particularly those who are elderly, infant, immune-compromised, asthmatic, allergic, etc.
Keep us posted, and post additional photos, comments, questions as needed.
I have Unico mini-duct system in my attic. Every winter, the fan motor and shaft accumulate rust. I live in a very cold climate in winter (Vermont). Last year, I had the motor replaced and this spring, there was rust on the motor again (no visible rust last Fall when I closed the unit up for the winter). I had the New England Unico rep at my house when we closed up the unit for winter to ensure it was properly winterized.
Specifically, the plugs were put into all the outlets and a piece of insulation board wrapped inside a plastic garbage bag was placed tightly into the air return. In addition, I had an additional 18 inches of cellulose blown into the attic last fall and the attic entrance / jacob’s ladder was sealed up properly and a new roof put on (both last Fall).
The condensate drain used to drain into the sewer vent but that was moved last summer to instead drain to the outside of the house directly via a PVC drain pipe. Note there is just a small v-shaped trap on that PVC drain but my contractor thinks that is fine given it drains to the outside.
So, the current theory is the rust is occurring due to moisture in the attic in the winter, but there are no other signs of moisture in the attic. The laundry room is almost directly below the attic A/C unit and the dryer vents to that outside wall.
A friend suggested that dryer vent could be blowing warm air that rises up into the soffit vents and finds its way into the attic, but I think this is not likely the problem given I have no other signs of moisture in the attic plus the fact that the A/C unit is pretty tightly sealed up itself to avoid leaking air when it is operating. JL 2021/07/01
Moderator reply: track down source of moisture, rust, corrosion in air handler
From your description of near-heroic measures to try to close off your attic duct system in winter one might guess that you've had reason to be concerned for moisture or ice accumulation in ductwork in the past.
What you've been doing sounds reasonable to me.
But I've also seen that the natural wish of warm air to rise into cool spaces means that even the smallest air leak into the duct system from anywhere will invite moist air and condensation and thus moisture collection during cold weather.
Because the ductwork is out of use there's no air circulation through the A/C system so no moisture removal; so any moisture accumluates, and can be corrosive.
I've even seen so much moisture accumulate in attic ducts as to form thick ice that later melts and shows up as a "leak" that has been mistaken for roof leaks.
If air is leaking directly into the duct system from anywhere in the warmed building during winter, that could explain why you see duct or attic AHU moisture signs but not other moisture or condensation signs in the rest of the attic.
Your friend's idea about the dryer vent is interesting and helpful as a model: look for sources of warm air leakage into the duct system from anywhere in the building.
Two articles you'll want to review are
WET CORRODED DUCT WORK -- I will copy our discussion to that article and will welcome your further comments, questions, suggestions here or there.
Reader follow-up:
Thanks for the reply.
I have had some condensation in past years around the air outlets (I.e. on the ceiling around the outlets) during very cold spells. That is one reason I had more insulation put in the attic last Fall when the roof was being replaced. Now most of the ducts in the attic are buried in insulation. No issues like that this past winter after adding the insulation.
The most likely place I can think of where air from the heated part of the house would be the return. Can you think of any special material the return should be made of or method of sealing (beyond what I’m doing)?
Regarding the condensate drain, do you think I need a bigger drain with antifreeze in it during the winter to keep air from getting into the unit in winter? Keep in mind it is currently just a small V-shaped PVC trap that drains outside.
One last question: is it possible the corrosion actually occurs during the summer/fall when the unit is operating but doesn’t turn into visible rust over time (e.g. winter)?
Thanks again! - JL
Moderator reply: special material the return should be made of
RE your question:
Can you think of any special material the return should be made of or method of sealing (beyond what I’m doing)?
-- If you are sealing the return duct at its inlet grille then that is normally sufficient; but you might want to inspect the duct system to be sure there are no obvious air leaks into it from elsewhere.
-- Something sounds wrong about all of this: when we close off duct inlets and outlets we should be closing off any significant air drafts into the ductwork during the off-season; So I keep thinking we're missing a significant airflow passage.
Regarding the condensate drain, do you think I need a bigger drain with antifreeze in it during the winter to keep air from getting into the unit in winter? Keep in mind it is currently just a small V-shaped PVC trap that drains outside.
-- The condensate drain trap may indeed dry out over winter; you could try mineral oil in the trap when the system is shut off - less of a contaminant than antifreeze;
One last question: is it possible the corrosion actually occurs during the summer/fall when the unit is operating but doesn’t turn into visible rust over time (e.g. winter)?
-- It is certainly possible that moisture is accumulating in the duct system during the in-use season and lying there corroding-away over the winter; It's common for water to blow off of the cooling coil into the supply ducts from that point onwards.
-- Sags in ductwork also pool condensate;
Reader follow-up:
Thanks for all the info. Your last point made me ponder something everyone has said should not be an issue but let me run it by you: I have 2 outlets over my 2-story foyer that require an extension ladder to plug / unplug so I stopped opening them several years ago.
Do you think it is possible that because the air isn't moving through those lines (remember this is a Unico high velocity mini-duct system) that there could be condensation sitting in those lines that could find its way back to the blower fan in the winter? FYI: I typically run the blower fan (i.e. not calling for cooling) for at least 24 hours before closing up the system for winter.
This is usually in October when the nights are cool and I'm no longer using the system daily for cooling. Could that be leading to warm moist air in the ducts that later causes the rusting on the blower fan once I close the system for winter?
My technician is supposed to come to replace the blower fan and motor today so I'll run some of these ideas by him as well. - JL
Moderator reply:
I'll be very interested in your report of what your on-site service tech has to say, as nobody can see as much by text and web posts;
But in general, for an outdoor receptacle to be responsible for rust and moisture in an HVAC duct system you'd have to have a pretty unusual circumstance in which sufficient volume of humid outdoor air is somehow conducted from an electrical box or the cutout opening for the box into the duct system. There should be no direct path through which that's possible. Visual inspection still is sensible.
Reader follow-up:
My technician agreed to problem cannot be caused by the dryer venting back up into the attic. The Unico system is pretty air tight due to it being a high velocity system.
He also did not think the two outlets that I never open would be the source of condensation for the winter months. Nor did he think running the fan in October just before I close it up could cause excess moisture to accumulate since the air is pretty dry in Vermont (low humidity) in October. So we still have a mystery. He said the unit was completely dry inside today despite the fact it was hot and very humid here yesterday. - JL
So we still have a mystery. Thanks for your suggestions and comments though. If we ever figure this out, I’ll let you know.
Moderator reply:
Thanks for the follow-up, do keep us posted, as what you find will certainly help other people too.
In investigating, start at the point of most-concern such as rust or corrosion, and follow the water or water indicators, stains, signs, rust patterns, etc.
I just posted about rust in a vent with plastic lined duct, but wanted to share other images for context
I am purchasing a condo and see that there is corrosion in the first floor vents. One is worse than the rest (photos attached- 2 of the bad one and one of another). I've been reading this thread and see the recommendation to investigate any rust or corrosion.
When I look at what these vent attaches to, I see what looks like something lined with black plastic. I would like to know 1) What kind of duct is this and is there still a concern for rust in the vents? 2) would you still recommend a scope of the vents, and 3) does this vent need to be treated in anyway?
The hardwood floors were recently redone and there was concern that product spill in the vents caused the corrosion, but the flooring company says that is impossible. Could this be caused by that?
by (mod) - evaluate rust in metal HVAC ducts & registersRust-
Anna
Your original photo (further below) shows rust in the heating or AC duct register boxes that in turn are connected to plastic flex duct.The second photo shows trivial rust; the first image you posted shows more rust and may be a concern - look for a spill or a leak source.
Those stains suggest there has been water in the ductwork - risking hidden mold or bacterial health concerns.
All my air returns look like this and rotted sheetrock behind them. White film and mites all over my home.

On 2019-12-08 by pantherprincess555 -
by (mod)
Panther
I can't say from the photo whether that's normal dirt in older HVAC returns and ducts or rather water damage and mold; if the drywall is damaged look carefully to see if it is from water damage, mechanical damage, or simply the effects of rough cuts made during installation.
Gypsum board doesn't literally "rot" (as might wood) but it can be water damaged and become soft.
In your photo I don't see water stains. That would be a useful diagnostic clue.
The ducts going in to the furnace was dripping and sweating an air conditioner tech said it was because there should be a vent in the duct work that is coming out of the furnace that is running across the ceiling in the same room.
So he put a hole in the duct, which did stop it from dripping. Should there be a hold in it? Is this correct? My furnace is very old. On 2019-08-24 by Linda -
by (mod) - venting to fix a ductwork condensation problem? Really?
Linda
I want to help but am totally baffled by the question and by what the service tech told you. I have not idea why there should be a "vent" cut into ductwork - it sounds very odd to me and is by no means a common, standard, or recommended practice.
Ducts "going in to a furnace", would mean that these are the air return ducts bringing building air into the air handler to be heated (in heat mode) or cooled in air conditioning mode.
Sources of water in ductwork are discussed in the article above; some examples (not an exhaustive list) of causes of water or condensate in or on air conditioning or heating ductwork include:
If there is water inside the duct work it may be due to improper condensate drainage from the air conditioner.
Condensation might also appear on air conditioning SUPPLY ducts (leaving the air handler after the air conditioning cooling coil has cooled air therein) if the ducts are not properly insulated.
On occasion condensate may blow off of the cooling coil and into the supply air plenum or ductwork.
Rarely there are also external sources of water inside ductwork such as a plumbing leak that drips onto and into ductwork or
finally, ducts that run in floor slabs below grade, into which ground water leaks.
I have a condo that the garage is below the living space. My tenant noticed there is mold on the garage ceiling.
One of the neighbors said they had the same problem and she had it fixed. She was told it was condensation in the ductwork. Water was damaging the drywall and leaking downward.
Of course, mine is worse. What is causing this? Could this be a problem in the construction? The units may be about 10 years old. - Carol 6/20/12
Reply:
Carol from the very limited information your note alone I can't be confident in a "guess" at what the problem is in your home and can only answer in general. An A/C duct that is not insulated is more likely to produce condensation inside the ductwork than otherwise, especially in humid weather.
Such condensate, if it collects in the ductwork where it does not belong, instead of in the air handler where it is drained away, can wet duct insulation (if there is some), and can leak onto or into building surfaces.
Moldy drywall is best removed and replaced, allowing you also to check to be sure the wall cavity was not also wet (and moldy).
Ask your HVAC service company to inspect the ductwork, fix the cause of condensation, help you decide if the interior of the ductwork needs cleaning AND IF it can be cleaned at all (fiberglass duct interiors don't tolerate cleaning). WHen that problem is cured, then address the rest of the building.
Watch out: mold can grow to problematic levels in fiberglass insulation in or on wet or previously wet HVAC ducts even when the ducts look clean to the naked eye. An explanation of this problem is
I was told products such as clorox, scented candles and sprays cause corrosion to air and heating lines. Is this true? - June Walker 10/2/11
Reply:
June, it's true that in areas where high levels of chlorine gas are present, such as around indoor swimming pools, corrosion of metal HVAC ducts and even evaporator coils can be a serious problem.
Scented candles? I am very doubtful that in normal use you could put enough corrosive material into the air to affect the ductwork. But indeed use of scented candles can be an indoor air quality problem source for some people such as asthmatics, and the soot deposition on indoor surfaces can be a cosmetic problem as well.
Is it ok for a window unit to stay on cooling for 30+ minutes or will this break the unit, see its above 96 degrees all the time outside so its hot hot and since I cleaned the evaporator coils & moved thermostat accidentally
I swear it doesn't cut off & on like before but I just don't want damage to unit and also coils were dirty before so maybe that's why it cycled quicker then anyway please help - Christie 7/25/12
Reply:
Christie,
Under normal conditions (that is for example no abnormal electrical voltage levels, proper wiring and installation) a window air conditioner could run continuously, 24-hours a day, without damage to the equipment itself. Of course if the air filter becomes debris-clogged and is not cleaned the system efficiency and effectiveness will decrease, and of course your electric bill will reflect that continued operation.
See WINDOW / WALL AIR CONDITIONERS for details.
Hello, we just had our evaporator coil replaced yesterday and the technicians had to alter the ductwork to put the coil in.
After the work was done, the technicians confirmed that the AC system was cooling properly. After they left, I went to our basement where our HVAC unit is located and found that there was air leaking from the duct joints where they had put the new coil in.
Thinking that the leakage did not seem normal and might compromise the cooling, I called him to ask about this. He said that they had deliberately not sealed it completely to prevent the system from "sweating" too much. Not knowing any better, I had to accept what he told me. I would like to get your opinion on this issue.
Please do let me know if this will compromise the system efficiency or if this will truly prevent the system from sweating and therefore we should do nothing. (Sept 29, 2015) Jyotika Bahree
Reply:
Water found inside the ductwork risks unhealthy mold contamination and other damage too.
First we need to understand where the water is coming from; then we'll know how to fix the problem.
Look for
1. missing duct insulation
2. condensate blowing off of the cooling coil into ducts near the air handler
My evaporative cooler or condenser and coils need cleaning from debris from gas powered leaf blowers next door twice a week.
I should get my rental payments waived till the slumlord faces her responsibility, she just don't want to pay professional costs.
These apartments should be condemned built in 1949, the slum Lord told us not to lick the paint, it's full of lead, rusty water pipes, mold.
I need the Environmental Protection Agency to test these apartments, they are hazard to our health, and inhabitable to live a healthy living conditions
There's mold, rust,lead and possibly asbestos thru out even the tile floor and the air feels humid, the AC is potentially not giving out cool air as time goes by we have a slum Lord that refuses to hire a professional bonded and licenced, they use exfelons to do the handiwork, and refuses to exterminate by professionals but uses the cheapest extermination using claydirt making your apartment dirty around the base iarda and window sills
My apartment below the ceiling is cracking and buckling from the ceiling to the base board On 2019-07-15 by Shirley - T
by (mod) - how to report unsafe building conditions and what to do about them
Shirley
Bottom line: If your apartment is unsafe / unhealthy and the management is not addressing the situation you may need to ask for help from your local health department. Depending on where you live there may be a local emergency number you can call, such as, in New York City, dial 311 to report unsafe building conditions.I understand that it's easier to say "move out" than to do so and to pay for it.
Unfortunately the US E.P.A. isn't likely to offer you direct on-site help with testing or other advice.
The EPA advises you to notify your landlord of these unsafe conditions; I add that you'll need to do so both orally and in writing, and keep records of the notification you've given.
See our detailed advice
at MOLD SAFETY ADVICE for TENANTS
Here is the US EPA's HOMEOWNER’S AND RENTER’S GUIDE TO MOLD CLEANUP AFTER DISASTERS [PDF]
The U.S. CDC offers these simple US CDD's 8 TIPS to CLEAN UP MOLD [PDF] that in my OPINON are fine but drastically incomplete. For example there's no mention of the importance of finding and fixing the source of water or moisture.
The New York City DOB (Department of Buildings) provided this DOB ADVISES NEW YORKERS AFTER HISTORIC CITYWIDE FLOODING [Web page] that does offer advice for both occupants and for building landlords too. Quoting:
All New Yorkers are encouraged to call 311 to report any unsafe building conditions in their neighborhood. Call 911 for emergencies. For more information about building safety, please visit the Department’s website at www.nyc.gov/buildings.
I was going through an article on your site on '' Return Air HVAC improvement Guide.''
But my question now is; What are the effects of a corroded return air duct in an air conditioning system? On 2019-04-21 by Anonymous -
Moderator reply:
To ask about the effects of corroded return air ductwork in an A/C system is, I agree, a reasonable question in concept but unfortunately one that nevertheless cannot be answered usefully when we have not a shred of information about the air conditioning system, ducts, condtion, contamination, amount of corrosion or rust, its cause, possible pathogens in the moisture that caused it, air movement, type of building, other building conditions that impact the effects, and quite a few other questions.
To give a general ' "it's ok" or "it's dangerous" answer would have no useful reliability.
For example, sewage water leaking from an overhead sewer line into an air conditioning duct system is unsafe regardless of whether or not the duct is visibly rusty.
In sum, superficial or small amounts of corrosion or rust in an A/C or heating system air supply OR return duct may be of itself inconsequential though even then the cause of the corrosion should be considered and probably fixed - such as condensate blow-off or missing duct insulation.
But extensive corrosion inside HVAC ducts might indicate not only that the system is itself damaged and leaky (increasing operating costs and decreasing building comfort) but it might also mean that pathogens such as bacteria or mold are being blown through the system and onto occupants.
How long does it take for rust to form in ac ducks and is it hazardous to my health. I'm immune compromised.
My complex is 30 years old I can see the rust on the a/c grates in the apartment. What should I do? On 2018-10-03 by Fay
by (mod) - How long does it take for rust to form in ac ducts
Rust can form on iron and some steel surface in days or longer, depending on the materials involved and site conditions.
It's less the rust, and more mold, bacterua, or viruses in damp ir wet conditions, that you would want to investigate.
Mine are leaking water also, how do I clean air handler? On 2017-07-13 by Anonymous -
by (mod)
Anon
In general water leaking out of HVAC air ducts is coming from
- condensate blow-off of the cooling coil, possibly requiring fan adjustments, a replacement of a baffle that a tech left out near the squirrel cage fan - or perhaps a baffle that was installed in the wrong location
- condensate accumulating downstream in ductwork perhaps because of missing insulation or air leaks into return ducting
Anon:
Cleaning an air handler might be considered at more than one level of work:
1. change dirty air filters regularly, usually monthly
2. remove any obvious clods of debris you can reach without disassembly - be sure power is OFF or you could be injured
3. hire a pro who removes the blower assembly, cleans it, lubricates it, cleans out the entire return air compartment, then rebuilds the system
Details are at BLOWER FAN ASSEMBLY CLEANING https://inspectapedia.com/aircond/Air-Handler-Blower-Cleaning.php
4. Cleaning a dirt-blocked cooling coil in the air handler is described at DIRTY COIL CLEANING PROCEDURES https://inspectapedia.com/aircond/Cooling_Coil_Cleaning.php
When I turn on my central a/c for the first time in the spring there's brown residue that comes out of the ducts.
The a/c company claims its rust from the ducts in the humid hot attic space they want to install a UV light claiming this will take care of the situation . I'm not buying it!
I feel like I'm getting scammed. Any input would be appreciated On 2016-08-06 by dave -
by (mod) That's questionable advbice
A UV light will not do the least thing about drying out wet or rusty metal ductwork;
IF and I empahsize IF the light were strong enough and the airflow slow enough, a UV light might kill some microorganisms that may be found in indoor air or in wet or damp ductwork.
Watch out: It sounds to me that the vendor is proposing to use a tool that they know and sell rather than that the problem is being properly addressed.
In general it's better (safer and more-effective) to diagnose and fix the cause of a duct contamination problem than it is to simply try to treat the symptom.
I suggest a duct inspection to find and fix the cause of the moisture problem, and perhaps duct replacement of rusted sections.
...
...
Continue reading at WET CORRODED DUCT WORK - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WET CORRODED DUCT WORK FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.