Sewer Line Replacement Procedure: piping or septic tank repairs
This article describes when, where, how, and why a sewer pipe or "drain line" is replaced.
The line which was replaced in this photo-illustrated case runs from the building exterior to a septic tank located downhill from the home. We present an actual case study, illustrated with photos of each step in the diagnosis and replacement of a blocked sewer line.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Later discoveries during excavation made us glad we'd decided to replace the entire drain line.
Not only was the sewer pipe broken in several other places, also we found and were able to repair a problematic leak at the entry of the drain pipe to the septic tank.
We found that the connection of the waste line to the septic tank had been leaking ground water into the septic tank in wet weather.
The nature of this into-septic tank leak problem was quite evident when it rained during our project as water ponded at the entry to the tank.
We confirmed that the tank had been flooded by opening the tank inspection cover at the intake baffle where we saw that sewage had flowed over the baffle top.
(Flooding a septic tank can result in early clogging and failure of the drain field.)
The "fix" in this case was a simple and expedient if crude concrete "seal" at the pipe entry to the septic tank to reduce the chances of water collecting and entering the tank at that point again.
The cost of this attempt to unblock a clogged building drain was several hundred dollars to pay the workers and for use of the power snake machine.
While it was disappointing to have spent this money only to discover that what was needed was a drain replacement, we considered it the fair cost for a confident diagnosis of what work was needed. In hindsight, we could have assumed that the drain replacement was needed based on the age of the home and gone directly to hiring the excavator, but most experts would consider that a rash step since there are plenty of instances of blocked drains that do not need to be replaced.
...
...
Continue reading at INSTALLING the NEW SEWER LINE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
MAKE OTHER SEPTIC REPAIRS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.