Chimney & flue sizing tables for venting multiple heating appliances thorugh a B-vent with double-wall B-vent connector between appliance and chimney.

Uniform Mechanical Code Tables plus commentary to assist in sizing metal or masonry chimneys according to chimney diameter, height, materials, and the input BTUH of the appliance(s) to be vented.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Sizing of Metal & Masonry Chimney Flues, Flues, Vents Table C-9-D

Table C-9-D (Excerpts): Multiple Appliance BTU Vent Capacity of Type B Double-Wall Vents where a Double Wall Metal B-Flue Vent Connector is Used Between the Appliance and the Chimney

Watch out: the first portion of Table C-9-D specifies the maximum input BTUH capacity of any individual heating appliance that is to be vented along with other appliances out through a single chimney. The Continuation of C-9-D-2 below gives the chimney specifications for the total input BTUH of all of the appliances, combined.

Total
Chimney/Vent
Height (ft)
Connector
Rise (ft)
over its run
Table of B-Vent
Diameter (inches) for a
Multiple Appliance Chimney
3 in.
4 in.
5 in.
6 in.
7 in.
8 in.

Maximum [Individual]
Appliance BTU
Input Rating
(thousands of BTUs)
 

6 ft.
1
26
46
72
104
142
185
2
31
55
86
124
168
220
3
35
62
96
139
189
248
 
8 ft
1
27
48
76
109
148
194
2
32
57
90
129
175
230
3
36
64
101
145
198
258
 
10 ft
1
28
50
78
113
154
200
2
33
59
93
134
182
238
3
37
67
104
150
205
268
 
15 ft.
1
30
53
83
120
163
214
2
35
63
99
142
193
253
3
40
71
111
160
218
286
 
20 ft.
1
31
56
87
125
171
224
2
37
66
104
149
202
265
3
42
74
116
168
228
300
 
30 ft.
1
33
59
93
134
182
238
2
39
70
110
158
215
282
3
44
79
124
178
242
317

 

Table C-9-D (Excerpts Continued): Multi-Appliance BTUH Venting Capacity of Type-B Double-Wall Vents [Chimneys] with Type-B flue vent connectors

This table gives the chimney specifications for the total input BTUH of all of the appliances combined and joined into a single vent when the flue is a Type-B double wall metal chimney and when the flue vent connector (between the appliance and the chimney entry point) is also a Type-B double wall unit.

Common [2 or more heating appliance] Vent Capacity in BTUH
Total Vent
[Chimney]
Height (feet)
Diameter (inches) of the Commmon Vent [Chimney]
             
3 in
4 in
5 in
6 in
7 in
8 in 
10 in
6
65
103
147
200
260
410
8
73
114
163
223
290
465
10
79
124
178
242
315
495
15
91
144
206
280
365
565
20
102
160
229
310
405
640
30
118
185
266
360
470
440
40
131
203
295
405
525
820

Guide to Chimney Sizing Tables for Venting Heating Appliances: Which Chimney Sizing Table to Use

Here is a quick guide to the UMC's chimney sizing & BTUH venting capacity tables when sizing a metal or masonry chimney diameter to match the total input BTUH of the heating appliances (boiler, furnace, water heater) being vented. Note that different chimney sizes are required for venting fireplaces and woodstoves.

Masonry fireplace chimney size requirements are at FIREPLACES & HEARTHS.

Chimney Type
Number of Appliances to be Vented

Metal B-Vent Chimney (Vent) 
Type of Flue Vent Connector:1

Single Appliance
Multiple Appliances
Which Chimney Flue / Vent Sizing Table to Use
Single Wall Flue Vent Connector

Table C-9-E
(two part table)

Double Wall B-vent Flue Vent Connector1
Table C-9-D
(two part table)
Masonry Chimney2
Which Chimney Flue / Vent Sizing Table to Use
Single Wall Flue Vent Connector
Table C-9-F
(two part table)
Minimum Input BTUH, Single appliance, natural gas, B-vent connector vs chimney height, size, & outdoor temperature  

Notes to the Table Above

1. A flue vent connector is the horizontal/sloped metal pipe connecting the heating appliance to the entry point of the chimney. Flue vent connectors and their materials, sizing requirements, & fire clearances are

at FLUE VENT CONNECTORS, HEATING EQUIPMENT

At double-wall B-vent chimneys the flue vent connector between the appliance and the chimney entry point may be single-wall metal flue vent connector or it may be a double-wall Type-B flue vent material.

2. At most masonry chimneys the flue vent connector or "stackpipe" or "smokepipe" is single wall metal, though for fire clearance needs it may be amended to use sections of insulated metal chimneys.

See CHIMNEY CROSS SECTION SHAPE EFFECTS for the effects of square vs round chimney sectional areas

Types of metal chimneys and their properties and fire clearances are at METAL CHIMNEYS & FLUES.


...

Continue reading at CHIMNEY FLUE SIZE SPECIFICATIONS_TABLE_C_9_E or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FLUE SIZE SPECIFICATIONS_TABLES C9D at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to CHIMNEYS & FLUES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT