Building Inspection, Diagnosis & Repair Info

Photograph of client using tissue to look for air conditioning air flow A/C Dehumidification Basic FAQs

FAQs on how to diagnose & fix indoor humidity or dehumidification problems with air conditioners.

This article series explains the causes & cures of an air conditioning system that is not adequately dehumidifying or removing moisture from building air.

This is part of our series on how to diagnose an air conditioner or heat pump that's not working properly.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Air Conditioning System Dehumidification Basics Q&A

Sketch explaining that oversized air conditioners are a mistake (C) Carson Dunlop Associates

These questions & answers about the basics of how to dehumidify indoor air were posted originally at x - be sure to review that article too.

Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

Question: My Air Conditioner won't turn off - what to do?

Carla said: My outside air unit will not turn off on its own. I have to manually turn the breaker off to turn it off. Does anyone know why or how I can fix it?

Reply:

Carla if your A/C won't turn off it could be that the thermostat is set to a temperature that the system cannot reach - due to lost cooling or due to a setting below the capability of the system.

If your A/C won't turn off even if you set the thermostat to a temperature that is above the current room temp, then the thermostat or an A/C control board or switch is bad and needs replacement - in that case you need a service call from a trained HVAC Technician.

See OPERATING TEMPERATURES HVAC and

also CONTROLS & SWITCHES, A/C - HEAT PUMP

 

Question: Why is my A/C not producing enough cool air?

A/C not producing enough cool air - I had my air conditioning system gassed up last week - $210. ! The unit is not producing enough cold air. The unit is set on 72 and does great at nights but during the day where the temp. outside is reaching mid 90"s it's getting up to 80 in the house. Is my duct work screwed up? How do you repair trailer metal ducting? - Amanda

90 degrees outside and 83 inside with thermometer at 76. Cools off to 76 when sun starts to go down and house then gets cold. New capacitor and condensor just put in. Help. - Ginny 5/17/12

Reply:

Amanda: if your system is not cooling there could be any of a number of problems - see the article above as a place to start. If your basic complaint is that the A/C temperature at the supply registers is cool enough but the volume of air flow is too weak, we'd start by:

  • Install a new clean air filter
  • Check that the air supply registers are open
  • Check that ductwork has not become disconnected or crimped or crushed
  • See DUCT SYSTEM DESIGN SIZE & DEFECTS where we list quite a few steps in diagnosing poor air flow out of an HVAC duct system

Weak air conditioner air flow - is there a relationship between refrigerant charge level and weak cool air flow rate?

Les said: Weak air conditioner air flow: Our A/C was serviced two months ago and the repairman said it had a leak. $400 later it was recharged with coolant and now the ac is doing the same thing. Very little pressure coming out of vents and no cold air coming out. Does anyone know what I can do for the weekend? It is stifling!

See A/C AIR DUCT PROBLEMS

DanJoeFriedman (mod) said:

Les: A leak that was fixed by a re-charge is not as good a repair as a leak that was fixed by finding and fixing the leak - you'll just have to keep adding refrigerant.

But weak air flow out of the vents would not be due to a refrigerant leak; more likely a clogged filter or crushed or disconnected ductwork, or a blower fan problem.

Weak air Flow traced to Clogged Air Filters: Can Clogged Air Filters Affect the Room Thermostat?

If air conditioner filters are clogged will it cause the thermostat to shut off? (May 13, 2011) Jim

Reply:

Jim: clogged A/C filters won't cause a room thermostat to shut off. The thermostat responds to room temperature. However clogged A/C filters that reduce air flow, cause coil frosting, or otherwise reduce or stop the flow of cool air into the room where the thermostat is located would mean that the thermostat would remain "un-satisfied" and should mean that the thermostat says "on" - continuing to call for cooling.

See AIR FILTERS for HVAC SYSTEMS

Air Filters & Cooling System Amperage Draw: Could Removing the Air Filters Cause the Electric Motor in the Air Handler to Draw Higher Amps?

Question: got one for you. i put an ammeter on my air handler and it read 8.25 amps, I removed the filters and it went up to 9.75 lmao at the situation the amperage should have gone down. what gives here

Reply: causes of variations in electric motor efficiency and current draw measured in amps

Lost: this amps variation is beyond my expertise, but in general reducing the load on an electric motor will show up as lower amps or current draw, not higher amps. Here are two interesting explanations of amps or current variations on an electric motor that I found when researching the question:

1. Voltage variations and current draw at electric motors: If your supply voltage is varying from your power company that can show up as higher amps draw on the motor (though it's a suspicious coincidence to see it exactly when you removed the filters and supposedly reduced the load on the motor).

Quoting from motorsanddrives [dot] com: "The effect of low voltage on electric motors is pretty widely known and ...

The amount of power the motor draws is roughly related to the voltage times current (amps). Thus, when voltage gets low, the current must get higher to provide the same ... To summarize the situation, low voltage can cause high currents"

2. Load variations and electric motor efficiency: A second possible source of seeing higher amps or current draw on your blower motor when you pulled out the air filters and thus reduced the load on the blower motor might be illuminated by this

U.S. DOE pamphlet "Determining Electric Motor Load and Efficiency" -

Quoting: "Most electric motors are designed to run at 50% to 100% of rated load. Maximum efficiency is usually near 75% of rated load. Thus, a 10-horsepower (hp) motor has an acceptable load range of 5 to 10 hp; peak efficiency is at 7.5 hp. A motor’s efficiency tends to decrease dramatically below about 50% load."

Question: what causes warm suction lines in an air conditioner or heat pump system? Warm A/C suction line (should be cold) and zone control dampers that stopped working

JMONTE said: warm A/C suction line question: After my condenser is turned on for about 4 minutes the suction line starts to get warm to the touch. can you tell me what the problem may be

Reply:

JMONTE: If the HVAC suction line gets warm, you may be out of refrigerant, or the system may be running in heating mode if it's a heat pump.

See OPERATING TEMPERATURES HVAC.

Becky, If a motorized HVAC zone control damper is not opening or closing, most likely the motor has failed, or the thermostat that operates that zone control is off or set in an incorrect position.

See ZONE DAMPER CONTROLS

Becky said: motorized air conditioning zone dampers not working

My house has "zone" control with dampeners to close off the upstairs over the garage room unless that thermostat is on - the room is not cooling. I have located the damper under the house. What are some causes for the damper not opening and how to repair them? condensation, motor to damper? silicon glued properly?

...





ADVERTISEMENT





...

Continue reading at DEHUMIDIFICATION BASICS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see

Or see these

Recommended Articles

Suggested citation for this web page

DEHUMIDIFICATION BASIC FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT