InspectAPedia®   -   Search InspectApedia

Starting capacitors in place on an air conditioning compressor (C) InspectAPedia.comAir Conditioner / Heat Pump FAQs

Q&A on air conditioner & heat pump inspection, installation, troubleshooting
Repair procedures,
Where to get parts, manuals & codes for A/C or Heat Pump Units

Questions & answers on how to buy, diagnose, repair air conditioners & heat pumps:

This air conditioner & heat pump inspection, installation, diagnosis & repair FAQ series lists questions & answers sorted by major air conditioning or heat pump topic.

Page top photo: a pair of start/run capacitors on the outdoor compressor/condenser unit of an air conditioning system.

This article series describes how to inspect and repair all types of residential air conditioning systems (A/C systems). Information for home buyers, owners, and home inspectors about A/C or heat pump system problems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Air Conditioning or Heat Pump System FAQs Master List

The questions and answers immediately below were posted originally at AIR CONDITIONING & HEAT PUMP SYSTEMS - home. Be sure to see the recommended topics and articles given on that page.

Image: a Supco RLC051 "dry" trap for HVAC condensate lines can reduce clogging problems. We discuss this waterless trap as an alternative to P-traps in a reader Q&A below on this page.

Should I insulate or "sleeve" refrigerant lines run in building walls?

On residential construction, is the line-set/copper tubing/vapor and suction line, required to be sleeved when installed through a cinder block wall?

Mechanical code references pipe duct for installation in concrete floors, but does not specifically state when installed through walls and/or more specifically through block walls.

Allied guidelines for long line installation suggest a PVC sleeve but I cannot find specific reference or requirement for any. - On 2022-07-07 by RS1227

Reply by (mod) - Should You Sleeve the suction line passing through a block wall?

@RS1227,

Yes.

See details at REFRIGERANT PIPING INSULATION where you will find the following

Suction lines are cold – 40°F (4.4°C) SST – and cause condensation, even in conditioned spaces. In addition, any heat that enters the refrigerant adds to the superheat and reduces system efficiency.

For these reasons, suction lines should be insulated with a vapor proof insulation. This is a requirement of many building codes. Rubatex is the most common form of refrigerant line insulation.

Keep in mind that the local building code official is the final legal authority on code questions.

However that does not change what is good practice or best practice. That is, even if the local inspector doesn't require insulating of the suction line, it should still be done. - On 2022-07-07 by (mod) -

 

Condensate drain line makes a dripping sound in nearby drain line - why?

Why do I hear loud dripping noise in the drain pipe in laundry room when AC is on? - On 2022-04-23 by Cornelia

Reply by Inspectapedia Com Moderator

@ Cornelia, Perhaps A/C condensate is being sent into that drain line. It would be common to dispose of A/C condensate into a building drain. And when the unit is running it produces condensate at a slow enough rate that as that condensate drains out of the air handler into a drain, if the drain includes a vertical section the dripping condenste might be heard.

Watch out: check that the dripping noise that you're hearing is inside the building drain and not a condensate leak or pan overflow that could damage the building or lead to costly mold contamination.

A visual inspection of the air handler and its condensate drain where visible as well as ceilings or walls below that spot, looking for water stains, should be sufficient.

 

Worried that insulation lining rigid HVAC ducts will mean that the ducts can't be cleaned

I requested rigid ductwork in my house so that it could be cleaned. They are installing now and it appears that the ductwork is lined with some type of product?

How will I be able to clean? - On 2022-04-22 by Karen Durm:

Reply by Inspectapedia Com Moderator

@ Karen Durm

If your ductwork is lined with a fragile material such as fiberglass, its interior can not be cleaned mechanically such as by sending brushes or devices through the ductwork.

Doing so often damages the otherwise stable, coated surface of the insulation such that it sheds fiberglass into building air.

So I share your concern. Ask for HVAC ducts that use an external insulation.

 

Where can I find OEM performance data for my Lennox air conditdioner?

How can I get hold of OEM expanded performance data? The manufacturers websites seem to be password protected. Do all 5-ton AC units have much the same latent cooling capacity? - On 2022-02-12 by Trevor Williams

Reply by Inspectapedia Com Moderator

@ Trevor Williams

I'm in over my head trying to answer this question but thanks, it's important and interesting.

Older Lennox units that used copper coils may have seen more leakage from corrosion than newer ones (since 2014) that have, like other manufacturers, changed to aluminum. That may be a factor in the leakage your system experienced.

The Trane XR16 is one of the "lower end" (less costly) lines offered by that company and has a SEER around 16 or 17. The Trane XR16-4TTR6061B or 4TTR6060B are its 5-ton rated units rated at actually 60,000 btuh. The Trane XR16-4TTR6061C, also a nominal 5-ton unit actually has a little smaller cooling capacity-actual, of 57,500 btuh.

So if your Trane is a different model, nominally a 4-ton unit, it's not one of those above.
See this Trane example 5-ton unit energy guide for the Trane-XR16-4TTR6060B that is actually rated around 14 SEER. https://inspectapedia.com/aircond/Trane-XR16-4TTR6060.pdf

The Lennox HSXB15 series claim SEER between 12 and 15, varying among model sizes, with the -060 signifying a 5-ton unit. The fact that the energy ratings differ might be a clue that the actual field performance may vary, too, for two A/C units of equal ton-rating.

I will attach a chart, just an excerpt from a larger document with more data and not necessarily exactly your Lennox unit, but illustrating some of the variables in the actual cooling capacity of a given air conditioner. You'll see that the cooling capacity is affected by or varies, for the exact same unit in otherwise identical installations, based on changes in the entering air temperature, the air volume or flow rate through the system, and the outdoor air temperature entering the condensing coil.

Given that example it would be no surprise that two 5-ton units from two different manufacturers, sporting different engineering details, designs, specifications, may actually vary in their effective cooling capacity or, as your question puts it "cooling output". Details for your Lennox unit are

in LENNOX-HSBX-15-SPECIFICATIONS

Followup by Trevor Williams

Many thanks for the response. (Apologies: I meant ‘sensible’ cooling rather than latent cooling.) Here’s the larger issue that prompted my question.

We plan on replacing a 5-ton Lennox (HSXB15-060) with a 5-ton Trane XR16. The Lennox unit cooled 3200 sq ft without problems for 15 years but leaked 6 lbs of refrigerant last year.

Wrightsoft sizing calculations indicate that we need a unit delivering about 60,000 BTUh sensible cooling and 6,500 BTUh latent cooling (setpoint 77F). The Trane replacement delivers a little more than 40,000 sensible BTUh’s and so appears undersized. I assumed all 5-ton units delivered much the same cooling output.

If so, how come the Lennox worked so well? OR, does the 5-ton Lennox deliver more sensible cooling than a 5-ton Trane? Is there a lot of variation between nominally equivalent units in the same environment?

Reply by Inspectapedia Com Moderator (edited) - Not all air conditioner "tons of cooling capacity" ratings are equal

@ Trevor Williams

Latent cooling is in essence the energy required to remove moisture from indoor air - dehumidification. Asking if all 5-ton AC units will have the same latent cooling capacity is perhaps a little tricky.

On the face of it, 5 tons of cooling capacity, if we keep all building conditions the same (occupants, indoor humidity level, other sources of indoor moisture, air leakage etc.), ought to have the same latent cooling capacity.

OPINION: But I'm not so sure.

A simple change such as blower fan speed or even cooling coil design or how moisture is collected and removed in the air handler may cause variations in just how efficiently a given 5-ton cooling system dehumidifies indoor air.

And if the cooling capacity is over-sized for the building, the indoor air will be cooled, but it will not be successfully dehumidified.

For other readers

at DEFINITION of HEATING, COOLING & INSULATION TERMS

we provide definitions of sensible and latent heat and cooling, including

LATENT HEAT & LATENT COOLING

There we provide a more scholarly exposition and expert references you might want to review.

For example, we cite Shirey (2006) who points out that just how moisture is collected and removed from a cooling coil may affect re-entrainment of moisture back into indoor air between operating cycles of the equipment.

And I don't assume that all air handlers, cooling coils, and condensate collection and removal designs are identical across various 5-ton cooling system air handlers. We certainly see differences that result, in some cases, in moisture blowing off of the coil and into the ductwork (a candidate for re-humidification). Thank you for a helpful question.

 


What do you think about the requirement for P-traps on AC condensate drain lines?

Regarding p-traps for condensate lines, can you weigh in on your thoughts about this? - On 2021-07-14 by Sarah

On 2021-07-14 by Inspectapedia Com Moderator

@ Sarah
Interesting article and thank you for the question about using a check valve as an alternative to using a P-trap on an air conditioner or heat pump condensate line.

Let's not forget the reason for traps on condensate lines: to avoid sucking noxious gases up into the building air-supply; So we want to trap the condensate drain line at the air handler.

The author does some fun analysis of water evaporation rates and so that leads to a concern that the water in the trap dries and the trap fails; If there's no water in the trap I suspect the air handler isn't being run - so no condensate is being produced - so we're not particularly drawing noxious gases into the building air through its duct system until the system is back on - and then condensate is usually produced pretty quickly.

There are, of course, fancier trap alternatives that will block back-flowing gases using a flapper trap; For floor drains - a similar problem - we simply pour some mineral oil into the trap. I'll look at the article again in more detail.

For other readers who, like me, are reluctant to click on off-site links to whoknowswhere, you can also see this article at by Nicholas DesChamps here at

HVAC, CHECK VALVE ALTERNATIVE to P-TRAP for HVAC CONDENSATE [PDF] (2020) - Des Champs, Nicholas, H., Ph.D., P.E., Fellow ASHRAE, HPAC Engineering, eNewsletter, Web: hpac.com - retrieved 2022/07/23, original source: https://www.hpac.com/piping-pumping/article/21130312/time-to-reconsider-use-of-ptraps-for-condensate-removal

The alternative device described by Dr. Des Champs is, in essence, a ball type check valve intended to permit condensate to drain and to avoid a potential back-up of sewer gases into the HVAC system air distribution (to building occupants), as an alternative to the traditional water-filled P-trap that is designed for that purpose.

OPINION: We agree with Des Champs that there is a known problem with loss of the water seal in traditional traps used on HVACR condensate disposal lines.

Des Champs also cites other advantages of waterless trap alternatives such as avoidance of the risk of freeze-damage and of collection of sludge that can accumulate in and clog a plumbing trap. Those are genuine problems that are indeed well recognized in the industry, enough that there are A/C condensate trap cleanout kits and traps that are designed to be easier to clean and others designed to protect their water seal from loss.

It is worth noting that the article includes some interesting and useful analysis of the rate of loss of water from a plumbing trap - nice work.

It's worth noting, too, that the author's company, DesChamps Technologies, designs and sells the type of product touted by the author, and that's the idea.

We'd have liked the article to have made more clear that if your HVAC condensate is NOT connected to a plumbing vent or sewer line or drain without an air-gap - which by code it should not be anyway - then, where the condensate drain isn't directly connected to building drain piping, the possibility of back-drafting nasty sewer gases up into the air handler through the condensate drain is essentially nil or zero.

We'd also like to see more data on the ability of a ball-type check valve to resist clogging or sticking from dust, debris, or algae that may enter the device from the air handler's condensate pan. Other experts warn about this problem:

"The first and most effective step for avoiding valve failure is keeping the pipeline and valves clean and free of debris. This can be achieved by installing filters and covers where required. Regular flushing of the piping system can also be performed to remove settled debris and minimize the buildup of contaminants." - in "Thomasnet, PREVENTIVE MEASURES TO AVOID CHECK VALVE FAILURES, IN THE ESSENTIAL GUIDE TO PREVENTING CHECK VALVE FAILURE [PDF] (2018) Thomas Engineering, - retrieved 2022/07/23, original source: https://www.thomasnet.com/insights/guide-to-preventing-check-valve-failure/

Please see details about proper condensate drain installation, problems, and avoiding trouble in the article series beginning at

CONDENSATE HANDLING, HVAC - home

and be sure to see also

CONDENSATE DRAIN PROBLEMS

where we'll ultimately move this discussion. Thanks again for a helpful question.

Followup by Sarah

Thanks so much, Dan. Thanks for all your input. Addressing your points:

We have one air handler that serves both the heating and the cooling side.

The gas furnace is directly on top of the air handler and the AC cooling coils are on top of that. The furnace has a condensate trap that’s part of the condensate capture system in the furnace itself.

The condensate from the furnace collector box and trap empties into a condensate line which is common with the line from the AC unit.

Per info in the link we shared, the AC condensate line experiences positive air pressure because the air handler blows air into it, which we observe at the tap point on the line. That would seem to mitigate the potential for odors intruding into the HVAC from the floor drain where the line empties.

On the other hand, during seasons when the AC and furnace sometimes run in alternating cycles there’s an unpleasant odor coming from our vents.

We found that, after much trial and error and multiple visits w/HVAC techs, that we can reduce, if not completely eliminate this odor by making sure the condensate line is extremely clean. This suggests there are various junctures when the air pressure in the line is negative and drawing odors into the HVAC system.

Due to the observations about evaporating water in P-traps, we are wondering if the ball valve promoted in the white paper would be appropriate to our system and would appreciate your thoughts.

Reply by Inspectapedia Com Moderator - Take a look at the Supco type waterless condensate drain trap

@ Sarah
I want to say yes, or a chicken-hearted "yes if approved by your local plumbing inspector"; candidly: I don't have a sufficiently-clear understanding of your HVAC system nor just what units are producing condensate nor whether there is more than one condensate source (air conditioning vs. a condensing boiler?).

It certainly is easy enough to experiment with a temporary close-off of the existing condensate drain when you are in heating mode and assuming you are certain that there is no condensate to be disposed-of in that mode.

I'm unclear what "ball trap" you were considering.

But there are "waterless condensate traps" designed for your circumstance, like the SUPCO RLC051 that I show here, available from HVACR suppliers and approved for that use.

That ought to end the debate. And it ought to let you find out if the drain is truly the only odor source.

 

 

How do I diagnose & fix Roof Top A/C Condenser Vibrations

Roof Top A/C Condenser Vibrations

I live on the top floor of a 4 story 100 unit apartment building. There are 4 A/C condensers on my roof for the units below and at least two are creating an unbearable vibration and hum.

When the maintenance man went to install vibration pads under the units, I heard two very loud crashes and think he damaged the units even more as the vibrations are much worse. Its sounds like a train in my apartment and I feel strong vibrations when sitting or even in bed. I even have two sets of vibration pads for my bed but it still is annoying.

The mechanical contractors are coming for the third time tomorrow to look at the units but I dont have a lot of faith in them. Looking at there permit history they do mostly kitchen and bath remodels and plumbing and maybe one or 2 A/C installs. Bldg management refuses to hire anyone else.

From researching online I know there are many many possible fixes but I dont think these guys will be open to anything more complicated than more pads or a sound blanket.
Any advice? Another neighbor just went through this and basically gave up but I dont think they had it as bad as mine.

btw should these units be on their own styrofoam/concrete pad. They wont let me on the roof but the set up on my roof section was described as 4 condenser units with each set of two condensers on a pair of 2x6s.

There are cheap rubber antivibration pads under the four corners of the units and under the 2x6s. thanks - On 2021-07-11 by Ballen

Reply by (mod) - Diagnose & Solve Noisy Roof Top A/C Condenser Vibrations

HVAC system noises are easily transmitted into a building by metal ductwork, pipes, or even the roof structure itself that can act as a giant speaker cone.

To solve noisy rooftop HVAC units including hum and vibration noise the onsite technician needs to

First decide if noises or vibration are abnormal - if normal, use normal sound isolating measures such as padding

For abnormal noises or vibration, trace the problem to its source, such as

A failing bearing on a motor or blower fan

A failing motor

An unsafe electrical condition

Loose mechanical parts or sheet metal or even something as simple as an access door that's not latching

For details see, and give copies to your technician of the following:

 

Question: A/C unit blower motor spinning too slowly, low voltage?

CARLOS I SANCHEZ 4 July 2021

The blower motor on my rheem package unit is spinning very slowly and the my home is not getting any air circulation. I checked the contacting coils and got 120 on top and bottom but didnt get 24 volts in both the middle contacting coils. notice that the condenser was freezing up due to the fan not blowing as its suppose to. checked speed 1 and 5 and I was not getting 24 volts there as well. what could it be?

my rheem package blower motor spinning slowly and I am not getting any air circulation in my house and notice the u it freezing up in the coils and compressor. what could be wrong?

Moderator reply:

Loose connection, low supply voltage, failing motor, loose fan belt or pulley, or something else

Starting at

AIR HANDLER / BLOWER UNITS - home

you'll find a series of air handler / blower unit diagnostic steps

Also

See BLOWER FAN OPERATION & TESTING

See ELECTRIC MOTOR DIAGNOSTIC GUIDE

Question: a lot of condensate coming of condominium A/C - normal?

Marietta habbershaw 1 July 2021

My condo's a/c is dripping 5 gallons of water in 12 hours! Is this normal?

Also my downstairs is cool and upstairs is blazing hot! Az is no joke in the summer!! Where should I even start?

Moderator reply:

That might be normal depending on the total volume of area being cooled. You might compare your condensate rate with your neighbors who have similar size and similar cooling settings on their thermostats. If there's something unusual going on I would be looking for a water or moisture source in the building.

Reader follow-up: upstairs is not getting cooling

What about the upstairs feeling like a heaters on while downstairs is nice and cool?

Moderator reply:

When we try to answer questions like yours the stumbling block is that we don't know a thing about your building, size, construction, installed equipment, etc. so new data can always change the direction of our advice

If your upstairs is hot and downstairs is cool

- is there only one A/C system or are those separate units?

- If only one system, then the duct system is un-balanced, loose, blocked, disconnected

- If two systems, the upstairs one is not working

THEORETICAL EXAMPLE:

If the upstairs return duct system is open to and drawing in hot humid attic air then it'd overload the 2nd floor cooling system and as there's an infinite supply of outdoor hot humid air that'd produce a LOT of condensate

Reader follow-up:

Thank you, it's one old unit, about 1100 Sq ft condo. I'm now thinking my son put something in the vent because we can hear everything in the house from master bedroom. I'm going to use the snake camera and take a peek in the ducts!

Once again, thank you, it's awesome there's people like you out here helping us that are desperate to not call the expensive repair guys!

Moderator reply:

We're glad to assist
but
keep in mind that no one an be as clever by text as an onsite expert - there is always something that an experienced onsite technician will or ought to see that may not have occurred to a homeowner to mention.

Keep us posted; working together makes us smarter.

 

Question: - stains on A/C unit drip tray - are these a mold problem?

I keep trying to upload a photo from the rear edge of the drip pan tray when coils were replaced but it won't upload. It's a JPEG and according to the note that keeps popping up, this is one format that should work, but it doesn't. Any ideas how I can get a pic to you? - Anon: June 18, 2021

Moderator reply:

I'm not sure what happened, Annon, but I checked with the moderator page and I did not find your original message nor image waiting for approval.

In general the process is easy: type in the comment box, and click the image icon to add an image.

Then click the gray "Post as ..." button at bottom right of the comment window.

But in any case I'm sorry you're having trouble posting an image.

You can send email and images to us directly using an email that you will find at the page top or bottom contact link.

At ODORS in AIR HANDLERS & DUCT WORK

you will find our email discussion on tracking down ductwork odors and also your photo.

 

Question: track down source of A/C duct odors - deteriorated materials?

2021/06/04 Annon

I’ve posted about this problem in the past and writing an update in the hopes you can provide additional guidance.

A couple of years ago, during the seasonal transition from winter to spring when weather fluctuates and we move back and forth between heat and ac, a smell came up through the registers when we turned the ac on after it had been off for a few days when heat was used. The smell was like a sweaty locker room and only occurred when using the ac after the back and forth from ac to heat and ac.

We had multiple checks of our HVAC system by HVAC techs, senior techs, managers, and a manufacturer representative. No one was able to figure out what’s causing it.

We also consulted with our IAQ/mold expert who hypothesized there’s at least one place where water sits and something starts to grow (mold? bacteria? etc…). She also observed discoloration along the front edge of insulation which we removed, even though she couldn’t definitively say if it was mold.

Other than that, no one saw anything of concern. In fact, HVAC techs comment on how clean our system is. We also had our ducts cleaned a few years ago after we bought the house and were told our ducts were very clean.

When I posted about this a year or two ago, you suggested cleaning the coils, which we did using a product in a spray can that the HVAC tech said is approved for use on our system. After cleaning the coils, the odor was eliminated, but then it returned after we switch btwn ac and heat and then ac again.

Per your suggestions from last year, we’ve had the air handler inspected. Multiple times. No HVAC tech has ever seen anything of concern

. The blower fan has also been checked and it’s clean with no suspicious marks of any kind. We change our filter our regularly (more often than recommended because we’re mavens about indoor air quality).

The duct work has been cleaned, but I don’t think they used cameras to inspect. However, if there was mold contamination in the ductwork, why would the smell go away after we clean the coils? It’s hard to imagine that the spray cleaner would be strong enough when running through the system, including the ducts, to kill any mold, but maybe. Let me know your thoughts since cleaning the coils is new info since my last posting in 2020.

Of note, our furnace is gas and we don’t have a heat exchanger.

One HVAC tech said this shouldn’t happen w/a gas furnace because the heat should kill anything that starts to grow. Numerous furnace checks showed the heat reaching the requisite 127 degrees where the air leaves the furnace.

Also, we routinely check and clean the drainpipes and are confident they’re not the source of whatever is causing this odor.

The fact that we can’t smell the odor with the heat suggests that whatever the cause, the heat kills it, but then once the AC comes on, it’s reignited. To my mind, this suggests mold, which dies leaving spores behind that can come to life again once wet. And although “dead” they may still be releasing toxins.

Our IAQ person thinks that perhaps when the AC is running constantly in warm weather months, the condensation keeps things moving and there’s no time for water to sit, but when the system is turned off for a short while, water is collecting somewhere.

A couple of weeks ago, the HVAC company replaced the coils (which were relatively new from being purchased a couple of years ago).

When the coils were removed, there appeared to be efflorescence on some of the aluminum backing of the insulation in the casing.

We also observed a gray discoloration on some of the fins on the coils which you could only see from underneath once they were removed.

There was also tiny black spotting along the rim of the pan under the coils that faced into the casing (so unfortunately, w/o removing the coils, we can’t monitor that location right now). I tried to attach photos, but was not able to because apparently they're not in the right format (jpg).

At the same time the coils were replaced, we also had the induction motor and collection box in the furnace replaced. The reason for replacement was an old motor and the HVAC tech observed a crack in the collection box which he said is a common problem, while noting that water could leak out of the crack. And we could see that some water had dripped out of that part at some point as we observed water marks.

Since the day they replaced the coils in mid-May, we’ve transitioned from ac to heat. Then yesterday, when we transitioned back to ac and the smell returned. So we cleaned the coils again and now the smell is gone.

We’re wondering if we should have the entire system taken apart in order to do a complete inspection. Perhaps the insulation is the source, though we can’t figure out how the insulation could get wet. But you never know if it was brought in with an area that was wet when it was installed. Who knows? That said, we can’t imagine how cleaning the coils which seems to have a beneficial effect, would impact insulation.

Related to things we’ve considered but seem unlikely is the line that’s the exhaust for the gas furnace. We tried looking down it from the outside, but since it turns, we can’t see very far and don’t have a camera. We could have our IAQ person put her camera down the line, but again, like the insulation, it’s hard to imagine how coil-cleaning would affect this component.

What would you suggest as a next step for this problem that seems to have everyone stumped?

Thank you for taking the time to read this length update and providing suggestions on what to do next.

Moderator reply: start with a duct inspection camera

before tearing anything apart why not have a camera inspection of the duct system?

Reader follow-up:

Yes, we're trying to find a reputable company to do that. Thank you. Meanwhile, our current HVAC provider is suggesting we coat the coils with epoxy and said they routinely do this in the south (I presume because of high humidity issues). Ever heard of that? They have no real scientific evidence to back up that approach and our gut reaction is not to go down that path.

Would be curious to hear your take on it. Also, a brief update: When we cleaned the condensate line last week the smell greatly improved. It's a bit odd because we, and the HVAC techs have done that in the past but it never seemed to help. We're also a bit mystified as to how something growing in that line (which we routinely clean) could pull back into the system as it seems like it should only exit, no?

Re: duct inspection. Our IAQ consultant said that when using borescopes (even high end ones) it's very difficult to be able to steady them well enough to focus on very small things. She doesn't anticipate any significant mold issue (if any at all), so it would mean very small close work and she's skeptical it would be helpful.

Also, just a reminder that when the smell is there (only during season transitions when we don't use the AC every day), it comes out of all the registers, which would suggest that if there were a problem in the ducts (or any other problem within the system) that it's something central, no? (I keep trying to upload a photo but it won't let me, even after I changed the file format to one of the required formats to upload. Very frustrating. FYI.)

Moderator reply:

The odor might be mold or it could be something else getting picked up in the return duct system or even near a return register .

But when cleaning the coil knocks down the odor that suggests an odor source in the system; when odors return the problem could be a new entrapment of odor materials (mold or ?) on the cooling coil from another source in the system, most-likely on the inlet side of the cooling coil: that means maybe looking with care at the return duct system, filters, etc.

I agree that borescopes give a very limited view of anything.

I wasn't suggesting a borescope.

If an inspection of the ductwork doesn't show anything suggestive but if as well not all areas are accessible and more so if the ducts are insulated on the duct interior it's worth a more-careful look before tearing things apart.

An inspection camera is a different device sent through ductwork, providing light and a wider view. These are widely used in HVAC ducts as well as in piping systems, but

Watch out: don't let anyone run a sewer line camera into your ductwork - it's the right kind of camera but if it's been in a sewer .... well you get the point.

And we're not looking for a few tiny particles - of anything - those would not be significant.

Reader follow-up:

Thank you. As always, your input is all very much appreciated and highly valued. We will pursue and focus as you've suggested. With gratitude.

 

Who pays for repairs if an underground AC line leaks?

In Florida...If an AC system line set is underground and leaks are detected, who is accountable for repairs? The homeowner or the builder? Possible cause is water in the pvc causing copper to erode? Thanks - On 2021-04-21 by Okeefe

Reply by (mod) -

@Okeefe,

That's an interesting legal question, not one I can answer (After hanlding a stream of court cases while in the Army I decided to quit law school early).

I pose that an attorney would look at the age of the installation, the original contracts for work, any warranty terms, and she'd also want an opinion from an independent expert on exactly what failure has occurred and on its cause. If someone caused damage by negligence you may have a case.

But my priority of attention would be on a proper diagnosis and repair of the leak.


Payne HVAC system blows air but won't cool

Hi, I have a payne HVAC system. When I turn on the thermostat (it has a switch for heat and cold and another one for a fan) to either cool or heat the air blows but is neither hot nor cool (I also turn on the fan at the same time).

The unit on the roof does not engage, that is I hear no noise and the fan blade does not turn. What could be the problem? I preface that the unit is quite old, although I haven't used it much as I live in Los Angeles closer to the ocean. I would appreciate any ideas you might have. Thanks On 2021-04-17 by dali H

Rooftop Air Conditioning unit is not turning on

Hi, and thanks for answering. The thermostat works when turning the fan and the heat. I could not adjust the temperature lower than what it is inside. The override only works for adjusting the temp up. I therefore just tried the heat option. It turned on inside the house, but it only produced room temperature air.

I checked the unit on the rooftop and nothing was moving. I think the unit on the rooftop should be working even when turning the heat on, right? I looked at the fuses in the power box, or whatever that box attached to the unit on the roof is called, and they look a bit blackened.

Again I don't know if that could be the problem or not. Thanks again and have a good evening. - On 2021-04-18 by dali H

Reply (mod) -

@dali H ,

It sounds as if your rooftop unit is not turning on. I can't tell from your text if that's something as simple as a disconnected thermostat wire or whether there's a bad control or whether a motor or compressor has failed.

In the article index take a look at the link to

LOST COOLING

Where you will see some basic diagnostic steps many of which can be completed by homeowner.You could try changing the fuses but if they blow again then you've got a seized motor or a short circuit and you need to leave the circuit off





Why does the fan keep running even when the unit is turned OFF?

Why does my fan keep running when the unit is turned off. - On 2021-01-17 by Dorothy Spencer

Reply by danjoefriedman (mod) - Why does my fan keep running when the unit is turned off

Dorothy

I think you're asking a question about a heating system not a more cooling system. It's normal for the blower fan to run for a brief time at the end of the heat cycle to purge the remaining heat in the air handler. That avoids the risk of overheating and cracking the heat exchanger which would make heater unsafe.

If you search this website for the phrase

Blower fan continues to run after a call for heat

Then you will see the details

Comment by Rachel:

RE-posted by Mod without advertisement

Rachel said:

@Dorothy Spencer, It may be the clutch bearing in the air conditioner pump is worn out. This part has not been replaced. The air conditioning pump needs to be replaced.

Reply by (mod) - Why does my fan keep running when the unit is turned off

Thank you for the post, Rachel

Dorothy:

If you are asking about the cooling fan in the outdoor compressor/condenser unit for your air conditioner or heat pump, see the diagnostic suggestions

at FAN, COMPRESSOR / CONDENSER UNIT DIAGNOSE & REPAIR

If you're discussing the indoor air handler fan ,take a look at the diagnostic suggestions

at A/C or FURNACE FAN WONT STOP

 

AC refrigerant leaks in winter are common? (Really?): the tech just added refrigerant - said bad Schrader valve

Bent AC refrigerant tubing (C) InspectApedia.comSystems leaking refrigerant over the winter is a common issue and most techs won't fix it because a recharge is a revenue generator and a easy service call.

The tech I called was here for 15 minutes and charged $400 to put in 6 pounds of R410A which had leaked out in about 6 months time.

So as soon as he left it kept leaking as before and by the end of the season it again needed charged.

Despite much bad information on youtube and the web, most leaks occur at the service valves.

This is because the schrader valve is dry rotted or was damaged during the install or servicing.

While replacing the high and low side valves would be the best fix, merely buying "o" ring service valve caps can slow or even stop small leaks.

The King valve caps can also leak and "O" rings can also be found for them.

My leak detector confirmed low and high side service valves leaking and after installing the "O" ring dust caps, the leak was no longer detectable and the system has been holding charge. - On 2021-03-19 by Jim Navotney

Reply by (mod) - Find and fix the refrigerant leak, don't just say "they all do that"

@Jim Navotney, thanks for the comment

I agree with you. With some service technicians will claim is that they have so much trouble finding and fixing the leak that their customers actually prefer the much lower charge of Simply delivering refrigerant periodically.

One could add to your comment that it is both illegal and an unfortunate contribution to environmental damage to keep leaking refrigerant into the atmosphere.

The correct fix, as you so emphatically state, is to find and fix the refrigerant leak.


I can't get my air conditioner to turn on

I recently moved to a home with an hvac heating and cooling setup, which ive never had the pleasure of having. anyways , all summer my air conditioner hasnt worked. the house sat empty for 2 years but the furnace works and kicks on . I have an air temp type central air conditioner that sits outside.

Im sure the weather may have something to do with it . ive tried the breakers, fuses, thermostat, checked all incoming electric and all are working.

It simply wont turn on, I know its not the fan because it turns and the bearings are good. on the control board mounted on the upper side of the unit , the led light is flashing 6 times, repeatedly. I troubleshooted online and it says it could be the blower motor amongst other diagnoses that we have tested. I also reset the system, breaker, thermostat and still nothing.

However, im not sure the air filter is clean , but ill check that next. does anyone have any suggestions or advice because I cant call a specialists because its wayyy too much money. has to be done by my husband and I . any help is appreciated ! thanks ! - On 2020-09-14 by amber mac

Reply by (mod) - be sure power is on, starting at the breaker or fuse panel and at the outside and inside service switches by the units

I'm so sorry Amber,

Generally you need a trained HVACR repair technician to fix an A/C unit if the obvious checks that can be done by a homeowner are fruitless.

Once you've confirmed that the power is on to the equipment and that the thermostat is set to COOL and is set to a temperature well below existing room temp, if the AC won't run a tech will need to check the control board, relays, and possibly refrigerant charge; that requires both training and special equipment.


What's the Residential air conditioning industry construction standard for the supply duct downstream (i.e. located after) a refrigerant coil

What is the residential air conditioning industry construction standard for the supply duct downstream (i.e. located after) a refrigerant coil. ?

If there are flex ducts that are installed on top of the refrigerant coil, wouldn't that be an inappropriate location to achieve full airflow from the cooling coil? Commercial air handling units have at least 12" - 18" from the fan discharge to the opening of the supply ductwork. - On 2020-10-11 by AlexEnergy5

Reply by (mod) -

DUCT SYSTEM DESIGN SIZE & DEFECTS - home - includes in the references section of each of the pages in that article series, citations of codes and standards.

You're right that good HVAC duct design usually provides an adequate main trunk to give velocity and volume to the conditioned air before it's branched off into individual distribution lines. hvacsales.com says that

"... the minimum recommended plenum size would be -- width: 2 x 16 or 32 inches; length: 1 x 36 or 36 inches wide. The depth of the plenum is always the same depth as the supply trunk."


 

 

What causes an A/C relay contactor to refuse to switch "ON"?

What is the cause of relay contact switch not coming on. It is new part, Could it be low on refrigerant? - On 2020-09-08 by Nabi

Reply by (mod) - Check for a loose wire, bad control board, improper wiring

Difficult to answer because I'm not sure which relay is giving you trouble. It could be an improper wiring problem or a control board problem or even wrong relay.

Unless yours A/C system sports extra controsl not normally found on residential cooling units, low refrigerant won't prevent the system from running - at least not until the compressor is damaged.

Contractor relay engages but condenser fan motor does not turn

I myself have the same issue my contractor does engage but my new condenser fan motor does not turn on the contactor is pushed in but nothing - On 2020-09-29 by Michael moreno -

Reply by (mod) -

Still that could be badly-burned contactor points that just make no electrical contact.

A service tech will check for power at the control board.




Lennox A/C motor replaced, now won't cool adequately: Why?

I had Lennox coil (CH3349C with TXV) replaced with ADP/Armstrong (A60H210P196 with piston) coil. Ever since it has not worked properly, takes hours to cool, from 75 to 70 even late at night, when its not fighting the high outdoor temps in San Antonio.

The condenser is Carrier 24ABB448A3, its a 4 ton, and never had any issues with cooling the house - 2story, 3000sqft.
Most likely cause(s)?

1. Lack of TXV on new coil, since it was on the original Carrier/Lennox setup. (The label literally says TXV installed but the repair company can't explain why it was removed.)

2. Improperly sized piston

3. Coil - Condenser mismatch. I know there times where a coil upsize might be called for but wasn't before replacement. The condenser model doesn't show up on AHRI so I haven't been able to check compatibility, 4 ton condenser - 5 ton coil. Would the larger coil reduce CFM and require adjustment to the air handler?

Thanks for any feedback on likelihood of causes I listed or any other potential ones. - On 2020-08-13 by Mario

Reply by (mod) -

Mario

An air conditioner won't work without some sort of refrigerant metering device, either a TXV (Thermotatic expansion valve) or a capillary tube.

The A/C unit also won't "work" if it has lost its refrigerant charge due to a leak.

Followup by Mario

So a/c tech found a leak on the liquid line right before it went into the coil box.

All working now, but I'm worried about long term impact of using 5 ton coil with 4 ton condenser.

Not too happy about the piston vs TXV as far as efficiency but at this point I doubt I could get the home warranty company to swap it out. Thanks.


My A/C refrigerant has a sour smell

Help, help, help (please). In May, I had to replace the compressor and air handler for my 20 year old high velocity AC system. They installed a variable stage Bosch and Unico air handler.

The ductwork remained the same. It's been a nightmare. I am getting a sour, acrid, vinegar like smell coming from the system. It's a heavy odor, it settles on everything and permeates bedding, clothing, paper products, towels.

It seems to be worse when the system first comes on, and when the variable compressor is running at a lower speed, and not quite as noticeable as when it's running full power. But as it cycles off and on I am getting full blasts of this horrible smell.

The contractor came out and cleaned the coils and checked the drainage, and everything looked fine, but the smell is still there. There is also an IWave air cleaner in place.

We tested removing it, it's not helping or hurting. Any ideas on what would be causing this? Would a duct cleaning help? Can you clean the small high velocity ducts? I would be so appreciate of any info. Thank you.

I'm starting to think this is a pinhole leak at the air handler coil, and what I am smelling is refrigerant. Any ideas? - On 2020-08-10 by Lynne

Reply by (mod) - refrigerant gases have no odor: look for a leak or contaminant in the air handler or ductwork

Lynne

Refrigerant is odorless. I'd look for an odor source near a return air inlet or for a spill or leak into the air handler or duct system

 

Is this stuff on my A/C air vents mold?

How do I tell if I am dealing with mold in air vents of home? - On 2020-08-02 by Chesley

Reply by (mod) -

That looks like several kinds of mold growth - seriously contaminated and badly in need of cleaning.

See SPLIT SYSTEM AC MOLD CONTAMINATION REMOVAL


Old RUUD air conditioner condenser unit won't run: diagnostic tricks

I have a very old (>27 years) RUUD a/c with an emerson 1/3 HP 4-wire PSC motor. A few days ago I noticed the fan was not running outside. Fan would not spin easily with a stick with power on or off. Decided fan motor must be bad.

Took it out, still wired. Upside down, spun it easily by hand. Put circuit breaker back on; fan motor humming loudly; so decided motor OK, but start capacitor was bad. Got one next day and reassembled. No improvement.

Pulled fan motor out of cage again. Still wired, upside down on top of unit.

Now with power on, I COULD spin it up and it seemed to operate OK. Tried putting it back right way. Now, nothing. Checked circuit breaker again.

Two pole 60 amp Square D; one side open in either position (I remember replacing circuit breaker about 25 years ago).

Had to order, so another day gone. Got it yesterday. Now fan started itself when AC powered (but still upside down on top of unit), so I figured it was fixed with new capacitor.

Reassembled, fan now in correct position. Back to not starting itself, plus powered fan difficult to turn again, humming loudly. Started checking all wiring, turning fan over, etc. Managed to pull couple wires loose.

\(Previously, they didn't seem to match all the on-line help about how to wire.) Think I got all back where they had been when it was working in past, but not positive.

Long story shortened -- fan works way it should when it is upside down; sounds like it is fighting with itself when right side up.

What gives? Also, noticed a little up-down play in shaft, but none side to side. - On 2020-07-19 by elrod

Reply by (mod) - diagnostic steps lead to bad fan motor or bearings

Elrod

That's an interesting and helpful series of diagnostic steps you tried. I suspect that the fan bearings are shot, so when the motor is in proper position the shaft is binding.

Followup by Elrod

Thanks, I had two other opinions this morning that offered the same thoughts, because of the vertical play. Except one thought it was probably electrical (position relative to brushes) and not mechanical (binding) because the effect was worse when under power.

I might keep the motor and eventually do a post-mortem autopsy on it to find out for sure (but this is definitely low priority for the near future).

Either way, the consensus seems to be the motor has reached its EOL, being more expensive to rebuild than to replace.

Now, if I can just be successful in removing the STUCK fan blade from the shaft (even a gear puller didn't help, was just bending the fan flange our of flat -- I see more work ahead of me for that).

My appreciation for your taking the time. Maybe several of us learned from this. Stay safe.

Reply by (mod) -

Elrod,

That post mortem would be both interesting and helpful to others, so if you do it, please tell me what you find.

1yr old Bryant Central air making loud piston noise

Bad central air compressor installation (C) InspectApedia.com Reader

I have a very intermittent issue. About every 2 weeks, and all 4 times it's occurred it was during the hottest part of the day.

Turning it off waiting a few minutes and back on resolves the noise for a few more weeks.

I let it make the noise for a minute without shutting it off and video taped it.

I don't want to skew your diagnosis but I would be remiss if I didn't explain one thing.

The installer did one of the worst installs I've ever seen and I got very angry and made the owner of the company come over and re-install it correctly.

The initial install had the unit turned the wrong way.

Pipes away from the house and exposed and prone to lawn care damage. And it was tight against the house blocking one side airflow. Here is a picture of the bad install.

When they re-installed it.

They mounted it up on rails and away from the house. Here is what it looks like now.

Compressor condenser reinstalled off ground (C) InspectApedia.com reader

Much better. And plenty of airflow and correct orentation. However.......

The low pressure pipe has a bend in it rather than going straight into the house. This was due to the bad initial install.

My dad said the bend could be be resulting in oil in the bend and blocking the flow? Again I don't want to diagnose for you. But it could be a critical to the reason.

Here is a picture level on from the ground so you can see the bend.

Refrigerant piping crimp and rout question (C) InspectApedia.com reader

Than you for any help you can provide. - On 2020-06-28 by Anon

Reply by (mod) - possible refrigerant line crimps & connection defects?

If the refrigerant tubing is bent enough to be damaged, creating a stress point, it may break - leading of course to a system failure;

If it's bent enough to be significantly obstructed, I'd agree with your Dad that on the suction line we might trap oil.

I can't say how severe the damage is from your photo.

In general we want some slack, a loop or more, on both the high and low refrigerant piping lines at the compressor, as a vibration isolator and to avoid damage and leaks that will be caused by even the slightest movement in the unit.

So having a curve or bend is by no means a mistake per-se. In fact the original "bad" installation had, from what I can see, better refrigerant line routing and connection than in your "improved" photo.

I'm including an excerpt of your photo here to invite other readers to comment.

Indeed on looking more closely, the larger diameter joint looks iffy and the smaller line is rather crimped.

Might want to replace those - it's not cheap to do; you'd have to have to evacuate the system, modify the piping, then recharge the system.


How do I find out what kind of capacitor is used on my A/C unit fan?

Need to know what type of compressor, fan capacitor is used. Unit installed 02/1989 - On 2020-06-22 by Wayne

Reply by (mod) -

Wayne

Please see

CAPACITOR SIZE DETERMINATION for ELECTRIC MOTORS

And you will see some tables giving typical capacitor values that we might use as a starting point if we have no data about a motor


Can a Goodman AVPTC49c14 be installed in a doublewide mobile home"

Can a Goodman AVPTC49c14 be installed in a doublewide mobile home. - On 2020-06-11 by LISA

If so would anything have to be modified?

Reply by (mod) - check the manual: it MUST say "approved for mobile home use" or "approved for manufactured home use"

If a heater is not listed and approved for mobile home installation, modifying it would be unsafe.


My Air conditioner indicates low refrigerant pressure but I measured it as OK

HI,got an AC thats indicating low pressure as an alarm after every 12 hrs,when I use the pressure gauge to measure the temperature its ok. - On 2020-05-04 by BEN

Reply by (mod) -

Ben

A pressure gauge measures pressure, not temperature, so I'm confused. Sorry.

Also, depending on where one measures pressure, HI or LO side, we get different readings and conditions.

Low pressure alarm may be on the suction side - for example.

Finally: Watch out about working on your AC system if you're not trained - losing refrigerant or contaminating the system are risks.


Franklin A/C unit won't cool

Our 4 ton Franklin Model ASTP47C14BA A.C unit quit cooling.. It is only five months old The fan runs and the controls work. Suggestions? On 2020-04-26 by David Heckman

Reply by (mod) - what to check first

David

In our LOST COOLING CAPACITY article in

the ARTICLE INDEX you'll see some easy diagnostic steps that are a good place to start.

We want to check out some obvious things (like is electrical power lost?) before calling for repair.

 

Can I install a larger fan motor on my air conditioner to fix a fan problem?

Can a larger fan motor (1075 1/2 hp) be used to replace this 1/3 hp 825 . I serm to be having problems with fan.

If motor is bad. I may need it replaced. The service co. Has the larger motor avail. Or I need to order one.

The 825 is less common and I may have an isdue waiting to get that esp. Now n amazon will be halting shipping. - On 2020-04-13 by karmika1586

Reply by (mod) - don't try that without proper diagnosis first

Karm

Watch out: I would not try to fix a fan no-start problem with a larger fan motor, because the underlying problem remains. I'd look for the trouble source:

  • bad wiring
  • bad control or control relay
  • bad start/run cap (or mistake when installing new one)
  • failing fan motor
  • low voltage

and other diagnostics in the articles I suggested.

 

How to diagnose an HVAC unit fanthat won't start

5ton trane condenser. Fan motor is intermittent. Condensor short cycles because fan doesnt start. Can be pushed to run.

Recently put new thermostat. Wired like old one which was instslled with old unit. Not sure if there was a heat pump. ..but this unit has heat pump. Red wire to R & JUMP PIN to RH. Is this a problem with internal circuit board in condensor/ heat pump. And causing conflict in signals? Just had service to condensor.

Oiled/ lubed fan shaft bearing - fan is still squeaking on start up. Til it warms up a bit

Put in new capacitor. As well as new thermostat. What else could be causing intermittent issues with fan.

Rough starts /push blades to start after its off for awhile. Can run fine 1-2days ( hi80°s) then fan fails AGAIN? AC been on for 1 mo.

These issues been going on 2 wks. Even after the new parts. Never sure if fan will start - On 2020-04-13 by Anonymous

On 2020-04-13 - by (mod) -

Anon:

Here are three HVAC fan diagnosis and repair articles that will guide you through diagnosing and fixing an intermittent condenser fan problem with intermittent fan failures.

Before getting too detailed, check for

- a loose or corroded wiring connection

- a bad fan control relay

then see the diagnostic suggestions at

FAN, COMPRESSOR / CONDENSER UNIT
and

ELECTRIC MOTOR DIAGNOSTIC GUIDE

and also, though it's for the indoor handler, see the additional fan diagnosis at

FAN WON'T START

Let me know what you find as that may permit further suggestions and also may help other readers.


Amana RHD60A2A heat pumps keep tripping the breaker

This is 2020. We have a 1996 Amana HUAC system. Last summer running the AC it began popping the circuit breaker once a day or so.

Re-set and all was fine for a day until it popped again. We had service in and he replaced the condenser and at my request, installed a starter kit.

That almost ended the problem but not quite. So on a hunch, I set the electronic thermostat to wait 500 seconds before re-powering the AC after it shut off, adding about 150 seconds to the old setting.

So far, that worked. Maybe someone can explain why, and if something else needs replacing? And maybe someone can tell me who re-builds Amana RHD60A2A heat pumps? 2020 is the last year for legal freon, and there's no way we can afford to replace this system. We're pensioners on a shoestring. Re-build or find a less used model is all we can do. - On 2020-01-24 by Reybo -

Reply by (mod) - Amana RHD60A2A heat pump rebuild?

Reybo

What was included in "replaced the condenser" ? The whole condenser unit? That would have meant a new compressor, fan, condensing coil & controls.

So we'd not expect a new system to trip the breaker if the setup is properly wired and fused. And you'd not install a starter kit on a new AC compressor motor.

On the other hand if you're using an old compressor motor and it's tripping the breaker, a hard start kit might get it going for a time but you've already been warned that the compressor is at or near the e nd of its life.

Indeed commercial compressor motors are often re-built.

But nobody rebuilds residential A/C or heat pump compressor motors. The compressor is in a hermetically sealed can and is not repairable.

You might find a used unit but I'd be pretty reluctant to try that. Few people will remove and salvage an old A/C or heat pump that's still working acceptably, so a used residential compressor on the market is risking having to do the job over multiple times- at a cost greater than having replaced the unit with a new one in the first place.

 

AC keeps blowing fuses

My 3A fuse keeps blowing when turn AC on? - On 2019-06-07 by Rich

Reply by (mod)

Watch out: Rich; when a fuse keeps blowing there is either a short circuit or a seized motor that's drawing so much current that the fuse blows or circuit breaker trips - to prevent a fire.

Leave the A/C off and call for repair.


Possible contaminants when brazing refrigerant lines?

What would be the expected result of brazing on the liquid line connection while the system is charged with R410?

Contractor claims he pumped out the refrigerant and replaced it, but I doubt that he did so.

Five years later the filters are so clogged the hot gas off the muffler is at 80*F (shows a 40*F temperature drop across the muffler). Was this predictable, and if so, what could have been done to prevent it? - On 2019-01-28 by Fred G

Reply by (mod) - Good practice when brazing A/C refrigerant piping includes the following:

Fred

Good practice when brazing A/C refrigerant piping includes

1. evacuate the system and pull a vacuum

2. do the brazing

3. evacuate and pull a vacuum again

4. Install a filter dryer on the suction line, possibly two.

5. Change out that filter dryer after a year

Debris from oxidized copper and flux inside the braze is unavoidable, so those steps are important.


Heat pump trips circuit breaker

Problem is that I have an ac heat pump system with Outside condenser and Inside air handler. Once I lower the room thermostat to call for cooling (lower than the room temperature) the breaker for the unit on the main box trips and shuts down. - On 2015-06-16 by Rafael Pagan

Reply by (mod) -

Sounds like an overcurrent such as from a failing compressor or relay.

Watch out: leave power off to avoid risking a fire, then call an HVAC service tech for proper diagnosis and repair of the system.


Rusty bad ductwork blamed for failure to cool some rooms: what's the fix?

Badly rusted HVAC ductwork (C) InspectApedia.com Josh

Went into crawl space to investigate cause for two hot rooms. I found it.

Main supply duct has at least two large leaks and is quite rusty. I’m guessing the ducts weren’t replaced when the system was updated from swamp cooler.

The supply trunk that main sits on is sagging from weight as well. How do I fix this? New main supply and replace rusted trunks? - On 2018-12-16 by Josh

Reply by (mod) - Replace badly-rusted metal HVAC ductwork

Josh If my HVAC system had ducts in such poor condition, I'd replace them.

And I'd want to find and fix the sources of crawl space moisture to reduct the mold and other damage risks therein.

Followup by Josh

Thanks Dan, I work in the plumbing department of a MEP company.

Hoping the boys in AC can help me out as I have no clue about duct work.

Reply by (mod) -

Ok Josh. Keep me posted. Also I'd like to see photos of the duct interior.



Blower won't turn off

My blower will not shut off. Should I change the blower relay, or the "high speed" blower relay? - On 2018-12-12 by Jonathan wilson

Reply by (mod) - diagnose the problem before changing out the relay

Jonathan,

Before replacing any parts you might want to take a look at the diagnostic suggestions found in our article titled

Blower fan won't stop

That you can find in the ARTICLE INDEX on this page.


Where is a heat pump usually placed?

Where would a heat pump usually be located ? On 2018-11-27 by Anonymous

Reply by (mod) -

Anon

Heat pump system consists of two major assemblies

Outdoors a compressor condenser unit and

indoors is an air handler that also contains a coil that either heat or cools air blowing across it depending on whether you are in heating mode or cooling mode.

The exact placement depends on the site (outdoors we like to put the compressor/condenser in a side or back yard) and the building size, shape, and cooling requirements (we might locate the air handler in an attic or in a basement).

 

Is there an ambient temp safety sensor to protect the compressor in cold weather?

Do any AC systems have an ambient temp safety sensor that wont allow to compressor to turn on below a preset outside temperature? - On 2018-11-10 by robinsoninspections @gmail.com

Reply by (mod) - Yes, for example the SUPCO freeze protection switch, opens at 35 degF.

SUPCO Sealed Units Part Company Freeze Protection Controller 35 degF retails for about $20. USD. -  shown at Inspectapedia.com (we do not sell anything) and available from HVACR suppliers or from SUPCORob

Heat pumps use outdoor temperature sensors for several purposes including switching the compressor motor OFF and switching to backup heat mode if outdoor temperature falls below the safe (or efficient) operating temperature of the unit (typically around 25-30 degF for most units).

An air conditioner unit, that is one that ONLY provides cooling, again depending on age and model, may NOT have any such outdoor temperature controllers.

Such units should be left turned off in winter.

If some fool tries to turn on the air conditioning at the indoor thermostat and if the outdoor unit runs in freezing weather it might be damaged by liquid refrigerant slugging in the compressor.

THose AC units do often include a crankcase heater to prevent liquid refrigerant slugging; that's why we leave power to the unit ON for 24 hours before actually asking the compressor motor to run at lower outdoor temperatures.

There are also "freeze protection kits" from Amana, Goodman, Supco, and others that provide an outdoor temperature sensor and that prevent the compressor from running at low outdoor temperatures.

Those can be retro-fitted to an A/C (i.e. not a heat pump) if needed. There are similar protection devices that can be fitted at the indoor coil to detect coil icing or freezing in that location, like the Amana FSK-01A kit.

Shown above SUPCO freeze protection switch, opens at 35 degF.


When is a refrigerant line supposed to be cool or cold?

Discharge line cold - is that OK? On 2018-08-25 by Arbbie

Reply by (mod) -

Abbie, it is normal for the suction line to be cold. If the high pressure refrigerant line is cool or cold and your system is a heat pump in heating mode, that would also be normal.

 

Goodman condenser unit, fan won't run unless you push it.

Goodman condenser unit, fan won't run unless you push it. I put a new 35/5 capactor on and same problem. I then put a new fan motor with separate capacitor on and it does same thing.

Voltage at cut off box is 246 and same at main contactor. With contactor engaged in have same voltage . Compressor starts and runs great. Fan motor is 2 wires to line and 2 brown wires to new capacitor. I even tried another new capacitor with the new motor. Help ! - On 2018-08-05 by Dwight

Reply by (mod) - signs of a bad motor start capacitor or bad electrical connection

Usually that signifies a bad start cap or a bad start cap wire or connecto


Debris coming out of HVAC vents after ceiling leak

Insulation or ceiling tile blowing out of AC supply registers (C) InspectApedia..com PattiMy ceiling has been leaking for 3-4 months.

Housing Authority said they patched it.

Now when my air conditioner blows threw vents, pieces of ceiling tile, ( insulation) comes out & is blacken - On 2018-06-22 by Patti

Reply by (mod) -

Patti

I can't make an assessment from your note and photo, but certainly from what you describe there could be a risk that the air conditioning system is mold-contaminated and certainly there is damage somewhere if it's spitting out debris.

A more subtle but more dangerous problem can occur if debris is drawn right into the air handler or blower assembly where it could cause a jam-up, a blower motor overheat, and then a building fire.

You might pass on your concerns to your housing authority, in writing.

 

My air conditioner takes too long to cool down my condo. Why?

My HVAC is around 15 years old. I have lived in my condo for 3 years now, so I wasn't living here when it was installed. It always reached the set AC temperature within a few minutes and I always leave the thermostat on "auto".

Recently it started taking hours to reach the set temperature and until it reaches that temperature, it doesn't turn off and on even though it's set on auto. It does run cold though. I also recently had the capacitor replaced. I asked the technician who replaced the capacitor why it's doing that, but he just said I need a new HVAC and couldn't tell me why it's doing that.

Do you happen to have any idea why it's taking so long to reach the set temperature? I don't want to have it replaced until it stops working altogether. On 2018-06-06 by Jill

Reply by (mod) -

I would start at LOST COOLING CAPACITY

https://inspectapedia.com/aircond/Air_Conditioner_Diagnosis.php

for help in diagnosing and repairing the trouble ypu describe

Check air flow and temperaturee drop across the cooling coil.

Followup by Jill

And I just used the word "compressor" as being the problem when it could be the motor or something else (I read several things about it, but since I can't get on the roof, I can't check those things).

At this point, I just basically would like an opinion on whether or not I should continue to run it on auto until I have to have it replaced or would just letting it run continuously extend its life any? Thanks.

Thanks for the suggestion, but I don't know how to check things myself and part of it is on the roof, so if I decide to use the AC until it breaks down completely and I have to get a new one, am I better off leaving it on auto or just let it run all the time as far as if the compressor happens to be failing goes?

I say that because now it seems to be having more trouble starting up after it has been off between cycles.

Reply by (mod) -

Right - not even the service techs use consistent language. And yes, stay off the roof.

Check for reduced air flow at the supply registers

Check then for a dirty air filter

Check then for blocked, disconnected air ducts


How can I tell that my HVAC contractor actually cleaned the cooling coils?

How do I know my contractor cleaned the coils with no power source electrical plug - On 2018-06-02 by marie

Reply by (mod) -

Marie

I can't say, in part because I don't know what coils, indoors or out, were cleaned nor by what methods.

If there is a removable panel you can look at the coils in the air handler and outside you can look directly at the coils on the condenser unit to see if they're blocked by debris.

But I note that electrical power is not necessary for some coil cleaning operations. The technician uses a foaming cleaner spray and cleans up the liquid that collects in the drip pan below.


There's Ice all over my ourdoor and indoor air conditioner equipment: what do I do?

My Ac unit imdoors and outdoors is completey frozen what should I do besides turn unit off? - On 2018-05-20 by Sarah Derrington

I had outside Guardian AC installed to replace the old one, now it has frozen up twice. What could be the problem? - On 2018-06-19 by Dianna

Reply by (mod) -

Sarah: Call for repair. The problem may be something as simple as obstructed airflow through the outdoor unit but it also could be a problem with a refrigerant control valve or low refrigerant .

Dianna: Low refrigerant, or malfunctioning thermal static expansion valve or something else

Can't cool the upstairs in our home

Last year I bought a 2 story home with 2 hvac units. The upstairs has 2 12x16 bedrooms on each end of a open balcony overlooking our living room that is open with 20ft high vaulted ceilings.

The upstairs unit has a 12x12 cold air return grill on the living room about the height between the floor joist with a bedroom closet on the other side which 12x12 return air grille in the ceiling and access to the attic where the air handler is located.

It stays extremely hot upstairs in the bedrooms. Even though the ac runs constantly it's so hot and stuffy in the rooms. Is their anything I can do to help lower the temperature during the summer? - On 2018-05-15 by Andy

Reply by (mod) -

I would start with some on-site help from an HP AC duct installer or designer. It sounds as if the return air may be inadequate.


Is it okay if the condensate line is connected to the plumbing drain vent pipe?

Is it okay if the condensate line is connected to the plumbing drain vent pipe? We came to know about this in our inspection.

We got one house inspected and we saw that the condensate line is connected to plumbing drain - On 2016-11-03 by Kanchan

Rely by (mod) - No: sewer gas hazards may be caused by that connection

Kanchan see CONDENSATE DRAIN CONNECTED TO VENT PIPE

and you'll see there are sewer gas and other hazards.

 

Thank you to our readers for their generous comments

Trung Tâm Kỹ Thuật Điện Lạnh Sudiho said:

Thank you very much for your post, this is very useful for me! We are providing the air conditioner repair service in Hanoi-Vietnam \

Thanks to your blog that I was able to understand more about the air conditioner heat pump inspect and repair.

Thank you very much! Looking forward to such blog posts! On 2018-09-12

Jack said:

Thank you for a very useful article. I'm afraid to repair the air conditioner myself, so it's better to ask for help from specialists

I had a bad experience trying to repair AC myself. I repaired it, but after a while it broke down anew, and it was not possible to repair it and it was necessary to change it completely.

If you are not sure what you can fix, better find a contractor.

Well, now they can be ordered anywhere, even on the Internet you can choose by the price and reviews. - On 2018-04-12

Jack said:

Reply by (mod) -

Jack

A homeowner can sometimes find and fix certain problems with air conditioners and heat pumps such as a blocked or dirty air filter or can diagnose others such as leaky, damaged ductwork.

But work that involves more complex diagnosis of a compressor motor, refrigerant metering devices, finding refrigerant leaks, or charging a system require special training and equipment.

That's also the case for installing new air conditioning equipment excepting portable systems such as a window A/C that is simply brought home, installed in a window with proper support, and plugged-in.


...

Continue reading at AIR CONDITIONING & HEAT PUMP SYSTEMS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see AIR CONDITIONING & HEAT PUMP SYSTEM FAQs-2 - more-recent Q&A about troubleshooting and fixing an air conditioner or heat pump

Or see these

Recommended Articles

Suggested citation for this web page

AIR CONDITIONING & HEAT PUMP SYSTEM FAQs - HVAC inspection, installation, diagnosis & repair Q&A provided free at InspectApedia.com or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT