Building Inspection, Diagnosis & Repair Info
Repair A/C or Heat Pump FAQs set #3a
Building Inspection, Diagnosis & Repair Info

Photograph of  This new compressor was placed directly against
a brick wall. One third of its condenser coil cooling ability was blocked. A/C & Heat Pump Repair FAQs-3a

Air Conditioning & Heat Pump Troubleshooting & Diagnosis FAQs about systems that won't start, won't stop, or won't cool or (for heat pumps) won't heat the building.

These questions & answers about fixing problems with air conditioners & heat pumps were posted originally on the air conditioning & heat pump home page.

Page top: a modern Carrier outdoor compressor/condenser unit.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Air Conditioning Systems & Equipment FAQs-3a

Flex duct in a horrible routing of excess lengths (C) Daniel FriedmanThese questions & answers about diagnosing trouble with air conditioners and head pumps were originally posted at AIR CONDITIONING & HEAT PUMP SYSTEMS

A good place to look for diagnostic procedures is DIAGNOSTIC GUIDE A/C or HEAT PUMP.

Also see this list of A/C & Heat Pump Diagnostic FAQs sorted by major topic at AIR CONDITIONING & HEAT PUMP SYSTEM FAQs

Photo: extra and unnecessary flex duct lengths snaking around and over one another in an attic may reduce the airflow rate through the duct system and so increase the heating or cooling system operating cost.

Article Contents

...

A/C or Heat Pump Not Cooling the Building FAQs

New Carrier A/C system provides cool air but our house isn't cool

We just spent $5200 for a new 5 ton Carrier AC for 1900 square foot house in Phoenix, AZ that was built in 1951. The first day the system cooled the house down with no problem. The second day the unit would not cool the house below 84 degrees which is unacceptable.

The licensed AC contractor has been out the past three days trying to get the system to cool the house down, and has even replaced various parts. Today they they checked the air coming out of the vent and it is 59 degrees, but it is still note the house down below 82 degrees and the motor runs continuously.

The AC contractor has given up and said he doesn't why the new unit won't cool the house and why it never cycles off. His solution is for us just to watch it!

The unit they replaced never had a problem cooling the house down and now I feel like for $5200 I should have an AC unit that will cool the house. What do you think is going on? On 2016-07-31 by Karen

Reply by (mod) -

Karen

First, in very hot Arizona weather when the A/C has been off for a time it could take hours to cool down the building again.

When there is a good temperature drop across the coil (as I think you have since you say it's 82 indoors but the cool air supply is at 59 degrees) the A/C system is probably working.

I'd call the installing company, speak with the service manager or owner, and politely, ask that they send an experienced, senior service technician to the home to determine what's wrong.

I'd expect the tech to confirm that the system is cooling properly, has a good temperature drop across the cooling coil, and that the duct system is not blocked, leaky, disconnected, etc.

Certainly one would expect an installing company to warrant their work including its performance to normal standards.

But we have no idea what's wrong: high heat gain, air leaks, duct defects, improper duct layout or design, improper sizing of the AC unit, improper refrigerant charge, a fan problem or what.

Also see LOST COOLING CAPACITY for more diagnosis and repair suggestions.

 

A/C runs, blows cool air, but never reaches the thermostat set temperature

Air conditioning turns on,blows cool air, but never reaches desired temp...what could be going on? We havent turned on the heat in 7 yes.

.usually run the air conditioning for about a week in the summer...we turned it on bout a week ago..worked fine.

Shut off during the day..ran it at night to sleep..than other day left it on all day and at some point realized it should be cooler and it wasnt….check settings, breakers...nothing wrong..what to do? On 2015-07-06 by Melissa

by (mod) - AC never reaches desired temperature

Melissa you need an on site service technician. Possible causes are a refrigerant leak, ice-blocked coil, crimped or damaged ductwork or other causes.

At ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

you'll find an article titled LOST COOLING CAPACITY

that can help you diagnose the problem.

by Melissa

Thank you..at least I have some direction to go..I will give my husband this info!

 

How long should it take an A/C system to get to the thermostat setting?

How much time does the AC system have to reach a degree below setting to be performing acceptable. On 2017-05-15 by Ken Stocke -

Reply by (mod) - acceptable time for A/C unit to reach thermostat set temperature

Ken

it's a perfectly-good question but not one I can answer. I think that if an A/C takes many hours to reach the set temperature in a building then on a still-hotter day it simply won't get there at all.

But the problem might not be the equipment itself. It could be undersized, have leaky ducts, be in a building that's not insulated, exposed to unusual solar gain, etc. So someone onsite needs to see what's going on.

More often HVAC guys talk about how long it takes the A/C system to drop the indoor temperature by 2 degrees: that avoids the capacity but not the open-window problem.

Rules of thumb for A/C performance:

Typically, in a properly-sized residential A/C system, assuming no stupid conditions like someone left the windows open, in 20 minutes a small room should be noticeably cooler, and in 3-4 hours the system should be able to drop the indoor temperature by about 10 degrees F.

More technical approach to AC cooling performance:

There are performance standards for A/C and heat pump systems. Typically those specify a given set of test conditions like:

Operating Condition A: 95°F outdoor air temperature, 80°F dry bulb/67°F wet bulb indoor coil air entering conditions. [Energy Star]

A useful standard is "ANSI/AHRI Standard 210/240 with Addenda 1 and 2 (formerly ARI Standard 210/240)" describing a four-hour test cycle.

Hou has written a theoretical paper on this that, if you can stand it, gives insight to why a simple answer like " it should take no more than 2 hours to cool down your room" are difficult: Development of HVAC System Performance Criteria Using
Factorial Design and DOE-2 simulation1 - http://oaktrust.library.tamu.edu/bitstream/handle/1969.1/6684/ESL-HH-96-05-22.pdf?sequence=4&isAllowed=y

TSI provides an HVAC ASSESSMENT HANDBOOK A PRACTICAL GUIDE TO PERFORMANCE MEASUREMENTS IN MECHANICAL HEATING,
VENTILATING, AND AIR CONDITIONING SYSTEMS - more focused on indoor air quality and what measurements are made such as of air velocity, % of fresh air, etc. - we don't get help with "how long should it take to cool my room"?
http://www.tsi.com/uploadedFiles/_Site_Root/Products/Literature/Handbooks/5001019C-HVAC-Handbook-2013-A4-web.pdf

 

Replaced Goodman A/C unit after refrigerant loss: not cooling: is it a refrigerant leak or a bad compressor?

Have Goodman home unit with R22 about ten years old. Compressor replaced 5 years, one month ago (out of warranty).

Evaporator core recently replaced due to leaks, and unit has not worked properly since providing minimal cooling.

With outside temperature of 95, have head pressure of 210 and suction pressure of 118.

Suction line is sweating at the core and outside but little cooling. I am being told that the compressor is bad.

Could something have happened during the evaporator core replacement to cause this, or could there be a problem with the new evaporator core.

As the homeowner I am suggesting evacuating and recharge but this may be a futile exercise. Other causes have been ruled out (i.e. airflow okay, no freezing up, etc.) - On 2011-06-04 by Pahugh

Reply by (mod) - pressure readings may indeed indicate that the compressor has lost an internal seal

Pahugh:

I'm not sure, but those pressure readings may indeed indicate that the compressor has lost an internal seal or has a bad internal valve.

Before replacing the compressor you need to ask what refrigerant was used to recharge your system when it was last repaired.

Watch out: And confirm that the refrigerant leak itself was repaired. Otherwise you could be replacing a compressor (very costly) when the actual problem is a refrigerant line or fitting leak.

Putting a new A/C refrigerant into an older unit that was designed for a different refrigerant wont' work properly.

 

Lennox A/C motor replaced, now won't cool adequately: Why?

I had Lennox coil (CH3349C with TXV) replaced with ADP/Armstrong (A60H210P196 with piston) coil. Ever since it has not worked properly, takes hours to cool, from 75 to 70 even late at night, when its not fighting the high outdoor temps in San Antonio.

The condenser is Carrier 24ABB448A3, its a 4 ton, and never had any issues with cooling the house - 2story, 3000sqft.
Most likely cause(s)?

1. Lack of TXV on new coil, since it was on the original Carrier/Lennox setup. (The label literally says TXV installed but the repair company can't explain why it was removed.)

2. Improperly sized piston

3. Coil - Condenser mismatch. I know there times where a coil upsize might be called for but wasn't before replacement. The condenser model doesn't show up on AHRI so I haven't been able to check compatibility, 4 ton condenser - 5 ton coil. Would the larger coil reduce CFM and require adjustment to the air handler?

Thanks for any feedback on likelihood of causes I listed or any other potential ones. - On 2020-08-13 by Mario

Reply by (mod) -

Mario

An air conditioner won't work without some sort of refrigerant metering device, either a TXV (Thermotatic expansion valve) or a capillary tube.

The A/C unit also won't "work" if it has lost its refrigerant charge due to a leak.

Followup by Mario

So a/c tech found a leak on the liquid line right before it went into the coil box.

All working now, but I'm worried about long term impact of using 5 ton coil with 4 ton condenser.

Not too happy about the piston vs TXV as far as efficiency but at this point I doubt I could get the home warranty company to swap it out. Thanks.

 

Payne HVAC system blows air but won't cool

Hi, I have a payne HVAC system. When I turn on the thermostat (it has a switch for heat and cold and another one for a fan) to either cool or heat the air blows but is neither hot nor cool (I also turn on the fan at the same time).

The unit on the roof does not engage, that is I hear no noise and the fan blade does not turn. What could be the problem? I preface that the unit is quite old, although I haven't used it much as I live in Los Angeles closer to the ocean. I would appreciate any ideas you might have. Thanks On 2021-04-17 by dali H

Rooftop Air Conditioning unit is not turning on

Hi, and thanks for answering. The thermostat works when turning the fan and the heat. I could not adjust the temperature lower than what it is inside. The override only works for adjusting the temp up. I therefore just tried the heat option. It turned on inside the house, but it only produced room temperature air.

I checked the unit on the rooftop and nothing was moving. I think the unit on the rooftop should be working even when turning the heat on, right? I looked at the fuses in the power box, or whatever that box attached to the unit on the roof is called, and they look a bit blackened.

Again I don't know if that could be the problem or not. Thanks again and have a good evening. - On 2021-04-18 by dali H

Reply (mod) -

@dali H ,

It sounds as if your rooftop unit is not turning on. I can't tell from your text if that's something as simple as a disconnected thermostat wire or whether there's a bad control or whether a motor or compressor has failed.

In the article index take a look at the link to

LOST COOLING

Where you will see some basic diagnostic steps many of which can be completed by homeowner.You could try changing the fuses but if they blow again then you've got a seized motor or a short circuit and you need to leave the circuit off

...

Air Conditioner / Heat Pump Won't Stop FAQs

Also see the diagnostic help at

BLOWER FAN WONT STOP - THERMOSTAT SWITCH

FURNACE or A/C BLOWER FAN WONT STOP - be sure that you check that article for help in diagnosing a furnace fan or blower that doesn't stop running.

My Air Conditioner won't turn OFF - what to do?

Carla said: My outside air unit will not turn off on its own.

I have to manually turn the breaker off to turn it off.

Does anyone know why or how I can fix it?

Reply:

Carla if your A/C won't turn off it could be that the thermostat is set to a temperature that the system cannot reach - due to lost cooling or due to a setting below the capability of the system.

If your A/C won't turn off even if you set the thermostat to a temperature that is above the current room temp, then the thermostat or an A/C control board or switch is bad and needs replacement - in that case you need a service call from a trained HVAC Technician.

See OPERATING TEMPERATURES HVAC and

also CONTROLS & SWITCHES, A/C - HEAT PUMP

 

Our outside A/C condenser unit never turns off

The outside unit of our air conditioner runs continually. We have to shut the power off to make it stop.

From inside our home it appears to be working fine and cools the house properly, with that one exception. We cannot afford to call someone out, is this something we could fix ourselves? Please help. On 2011-07-16 by Jan

Reply by (mod) -

Jan: I can't say what you can fix yourselves, but consider that the cost of running the A/C continuously unnecessarily may be more than the cost of a service call.

When the A/C won't turn off, is temperature indoors dropping BELOW what the thermostat is calling for?

If so then there is a thermostat or control board problem and you need a service call.

If the A/C keeps running but never reaches the set temperature of the thermostat first be sure that y our air filter is clean or just replace it and that you have good airflow. If you have good airflow but the air never cools you need a service call.

A/C Condenser Unit Won't Shut Off

I have an outside unit that wont shut off without tripping the breaker. A friend suspected the thermostat so I replaced it, but it didnt solve the problem. Any suggestions?

The inside fan kicks on and off within the set temp range, the outside motor just keeps going. Thanks for any help. On 2012-07-17 by Tim

by Bobcat

@Tim

Is this a heat Pump or Straight AC? A heat Pump uses a circut board to control the outside fan, and a straight AC should operate the fan when ever the compressor runs( cooling ). I will try to help - Bobcat HVAC service technician - On 2012-07-18

by (mod) -

Bobcat, thanks for helping out.

Tim:

regarding "I have an outside unit that wont shut off without tripping the breaker. "

- if the indoor air temp never reaches the set temp on the thermostat the system will just keep running - so if that's the case we need to determine why the indoor cooling isn't satisfying the thermostat.

- if you turn the thermostat setting "up" to be sure that the indoor air temp is below the set temp on the cooling thermostat - that is, the thermostat is satisfied, and then

if the equipment still never stops running, I suspect a bad control board or relay switch - and it's certainly time to call an HVAC/R service tech.

 

Question: our A/C unit keeps on cooling and won't shut off

For some reason, our dual zone unit keeps cooling the downstairs zone to well below the set temperature -- when set at 79, very cold air is still blowing though the thermostat reads 71. Cold air still blows even with both thermostats turned to "OFF."

Not sure what is causing this, but I am sure it's gonna cost me $700/month if I can't get the air to shut off.

Any thoughts would be greatly appreciated! - EL 6/25/12

Reply: when the indoor air handler for air conditioning won't stop check:

EL,

  • check first for crossed or bad thermostat wires

If your A/C won't turn off even if you set the thermostat to a temperature that is above the current room temp, then the thermostat or an A/C control board or switch is bad and needs replacement - in that case you need a service call from a trained HVAC Technician.

Here are more diagnosis and repair procedures:

For air conditioners that "won't stop running" or "won't shut off" you will then want to see these articles:

If the outside compressor/condenser unit stops running but the indoor air handler blower fan won't turn off, see

Also see 

 

When my A/C is off I still Feel Cold Air Coming out of the Vents

Why when my air is off is there still cold air coming through the vents. In between cycles On 2016-03-17 by candy

Reply by (mod) -

Candy:

Don't get confused between the outdoor compressor/condenser unit and the indoor air handler unit operation. If the outdoor compressor/condenser unit stops but you still feel air coming out of your supply registers it's probable that the indoor air handler blower fan is still running.

That can happen, for example, if someone used a switch at the thermostat or at the fan limit control in the air handler to put the blower fan into continuous ON mode.

Check that the indoor air handler blower fan is really OFF.

See

If it is and you feel a draft at the supply registers I suspect that there is an opening in the ductwork OR air is circulating by convection through the system, entering at an air return register. If the problem is serious, ask your HVAC company about an automatic duct damper.

Question: My central air conditioner won't turn off

My central unit will not turn off. The temp in the house is 92 degrees and I have set the thermostat to 78, but it will not cool the house and will not turn off. Do I need to add freon in the unit?

Also, I flushed the unit with bleach to clean the pipes out and the air conditioner cooled the house for about 4 to 5 hours only. After that it will not turn off or cool the house. What can I do before calling a technican? Thanks - Ossie 6/8/11

Reply:

I'm not clear where you used bleach but it doesn't sound like a good idea.

Before calling a technician check your air filters and check for duct work damage, leaks, crushing, etc. See the article linked to at the ARTICLE INDEX the bottom of this article and

titled LOST COOLING CAPACITY for detailed diagnostic help for an air conditioner that is not working.

Question: My central air conditioner never shuts off

help,help. i have no problems with the air being cool. the unit will just not shut off unless i shut it off - Anon 7/3/11

Reply:

An A/C unit that is providing adequately cooled air at the supply registers but still won't shut off is either never satisfying the room thermostat or there is a problem with the thermostat or the control board. Or there's another problem we haven't thought of. I'd first check to see if the thermostat shows that the room temperature is at or below the set temperature. It it is, I'd call a service tech.

If the room temperature never reaches the set temperature then either the set temperature is lower than your system can deliver, or there is a problem to find and fix, such as a blocked air flow (dirty air filter or fan).

...

A/C or Heat Pump Won't Run at Night

A/C will run during the day but not at night

Why is it that my AC runs just fine during the day, but will not run at night? It's very hot outside, even at night.

Every night I wake up soaked with sweat, and I have to run the floor fan on me, just to try and keep cool.

This same thing happened when I lived in an apartment. I've tried to lower the temp, but then the thing will just keep running and running until I have to get up and turn it back up.

And no, it's not hot flashes. My husband gets hot too...(: 2016-06-01 by Kare

Reply by (mod) -

Since it's usually cooler at night, even if you kept your thermostat at the same setting day and night, the A/C system would have to work less hard at night, so if the problem were an inability to keep up with the cooling load that ought to be happening in the daytime.

But it's possible that a control that tries to run a defrost cycle (after a hard day's cooling work) is malfunctioning and so the system shuts down at the end of that hard work daytime cycle.

Your A/C system needs service. I suspect a control board problem.

...

Heat Pump / Aux Heat Insufficient to Heat the Building

Weak airflow in heating mode isn't giving enough heat

I've just moved into a house where there seems to be very little air flow from the ducted heating.

Heating only occurs for a short period and then cool air seems to flow out. I had a service technician come out and he said the compressor is getting too hot a tripping out.

He said that maybe there is a problem with air flow or pressures.

To me it's obvious that there is at least an air flow problem so after he left I climbed into the roof and found that the ducting pipework does basically a 180 degree turn around a truss brace.

The ducting there almost seems to have collapsed in on itself. To me it seems clear that this is most likely be restricting the air flow. Would this in turn be causing the compressor to trip out? On 2011-08-17 by Craig

Reply by (mod) -

Craig

Provided that the air flow is weak in both heating and cooling mode, you will want to first check your filter, air handler and duct system for blockages, leaks, mistakes.

For that, see

DIRTY AIR FILTER PROBLEMS

and

DUCT SYSTEM DESIGN SIZE & DEFECTS - home

 

Heat pump can't keep up, aux heat is on, compressor is stuck in "defrost" mode.

My heat pump compressor is running but won't keep up indoor temp so aux heat is on. Compressor seems to be cycling to 'defrost' mode very often although there is no ice buildup.

Temps have been within the range that system normally maintains indoor temp with out aux heating. Thoughts plese? - On 2016-01-25 by BC

Reply by (mod): bad relay or control board?

If the outdoor unit is stuck in defrost mode I suspect a control board or relay failure. It's time to call for service.

If your AUX heat is insufficient to keep your building warm it may be that it's not working properly. For example, electric backup heat often contains multiple electric heating elements, some of which could be "off".

It's also possible that the outdoor temperature is high enough that the heat pump should be able to provide some indoor heat so not all the AUX heat is switched "on", but because it's stuck in "defrost" mode it's not providing that heat.

...

A/C or Heat Pump Runs but Doesn't Provide Cool Air FAQs

My A/C Unit Blows Warm Air, I'm doing some of the repair and it's not going well

My A/C unit is blowing warm air. The repairman added a pound of freon and recommended I add a stop leak additive to the system. I added it but the air still wasn't as cool as it should be. He came back out, said I had "low head pressure" and may need new TXV if adding more freon didn't help.

It didn't, so I called him out to replace the txv and he found the A-coil was extremely dirty. He cleaned it as well as he could with my vacuum and said He could cut it out, acid bathe it and reinstall for around $550 or I could try cleaning it myself with coil cleaner

I opted to try it myself. After he left, I noticed the condensor fan outside only runs for about 15 minutes then shuts off. I have to turn off the system and let it set for 30 minutes or so before trying again but it still shuts down.

With the thermostat set to 73 degrees, it's running closer to 80 (I had to buy a window unit to survive our 100 degree days). Any ideas? On 2015-07-20 by A/C issues-blowing warm air

Reply by (mod) -

A/C

I'm nervous about the prospect of the "stop leak" product clogging up the thermostatic expansion valve (TXV). Of course if it does clog up the valve then that's nice for the service company.

Watch out: if you're not trained on HVAC repair and if you don't have the proper charging equipment, there's risk that you contaminate the system and cause damage.

Followup by A/C - system was barely cooling - added refrigerant

Last summer, the system wasn't cooling. The repairman added 2 lbs of refrigerant and everything was okay. This summer, again, the system wasn't cooling. Serviceman came out, added a pound of refrigerant and said I should put in the AC Leak freeze because it shouldn't have lost a pound. I added it but am still having issues.

When I say "With the thermostat set to 73 degrees, it's running closer to 80..." I mean the thermostat registers 80 degrees. Sorry for the confusion. The coil is getting mildly cool as well as the outside line.

The system is barely cooling and the outside (condensor) fan runs for about 15 minutes then shuts off. It used to run as long as the inside blower was running. I'm not sure what else to try but I'm getting tired of paying the service guy $100+ every week with no change.

Reply by (mod) -

Now AC, continuing the diagnostic suggestion:

You say your system runs but is not producing cool air - "With the thermostat set to 73 degrees, it's running closer to 80 (I had to buy a window unit to survive our 100 degree days)."

If you mean that air delivered from the supply registers is at 80F then the system is not cooling. If the compressor is working and the refrigerant charge is correct you should feel cool or cold suction lines at the compressor and you should be able to measure a temperature drop across the evaporator (cooling) coil at the air handler.

If the cooling coil is not getting cold then most likely there is a problem with the charge or the refrigerant metering device.

See REFRIGERANT LEAK SEALANT USE

for a discussion of using leak sealants

Adding 2 lbs of refrigerant means your system was probably close to empty.

Even on a large system holding 5-8 pounds of refrigerant, that's still a pretty big leak. A pound a year is a big refrigerant leak for any A/C or heat pump system.

Normally a refrigeration system loses ZERO refrigerant. The charge is permanent unless there is a leak.

A dirty evaporator (cooling) coil will also reduce the cooling out put of a system because it blocks air flow. You may find the cooling coil also ices over because of the reduced air flow across it.

To distinguish between low refrigerant and a dirty coil (or dirty air filter or other duct defect) for the homeowner is relatively simple. If the air flow at your supply registers is weak I suspect one of the latter issues. If the air flow is strong but the air is not cool I suspect low refrigerant or a TEV that's not metering refrigerant properly.

At AIR CONDITIONER TEMPERATURE MEASUREMENT  we describe how to measure A/C temperatures for diagnostic purposes.

At AIR CONDITIONER TEMPERATURES we give typical A/C system temperatures you should find.

If your A/C system can't get the indoor temp below 80, unless you've got windows and doors open or some unusual heat gain situation, your A/C system is not working.

Watch out: If your system is leaking refrigerant as it seems to be from your description, especially where the leak is a significant one, you need to have a the leak point found and fixed. Don't just keep adding refrigerant: that's pouring your money as well as environmental contaminants into the atmosphere.

Followup by ac

The specs for my unit says unit charge is 7 pounds 3 ounces. The filter was slightly dirty but the coil was definitely clogged.

Once it was vacuumed off (still needs some cleaning) the air flow out of the vents increased quite a bit but it is still not cool air and doesn't explain the condensor fan stopping. The cooling coil is definitely not icing over-it barely gets cool and no windows or doors open.

Reply by (mod) -

The condensor fan runs or not under control of the compressor/condenser control board and switches. If the compressor is not running the condenser fan will stop. If the compressor fan is running without the fan then indeed a repair is needed.

If your system outdoor and indoor units run and blows out of supply vents but is only warm then no coolant is entering the cooling coil. That's a charge or a refrigerant metering device problem (most likely).

A service tech will check high and low side pressures and may need to adjust, clean or replace the thermostatic expansion valve if the charge is proper.

...





ADVERTISEMENT





...

Continue reading  at DIAGNOSTIC GUIDE A/C or HEAT PUMP or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see this AIR CONDITIONING & HEAT PUMP SYSTEM FAQs INDEX Q&A on air conditioners or heat pumps that won't turn on or won't run properly.

Or see these

HVAC repair guides

Suggested citation for this web page

REPAIR & DIAGNOSTIC FAQs for A/C-#3 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT