Building Inspection, Diagnosis & Repair Info

Heating & Cooling Blower Assembly (C) Carson Dunlop Associates HVAC Blower Fan Control FAQs

HVAC blower fan testing & diagnosis FAQs:

Questions & answers on diagnosing and repairing HVAC blower fans in the air handler.

This article series explains how to inspect and test a heating or air conditioning indoor air handler blower fan that is not working. We also discuss fan fan squeaks and noises. The blower fan assembly is the green component in the page top illustration from Carson Dunlop Associates The Illustrated Home.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Heating or Air Conditioner / Heat Pump Blower Fan Testing & Diagnostic FAQs

Air handler blower assembly(C) Daniel Friedman

The questions and answers discussed below were posted originally

at BLOWER FAN OPERATION & TESTING - please be sure to read that collection of diagnosis and repair steps.

The blower fan is located inside a horizontal air conditioning unit in many home air conditioning systems, especially when the air handler is located in an attic or crawl area.

 

Blower won't run on Rheem Centurion Split System

I have a Rheem Centurion II AC/Heat split unit and my blower wont run.

I replace 24V power supply about 3 months ago because thermostat quit working, fixed that. Now that blower stopped running, I've replaced blower motor, capacitor, and control board and it still wont run. What else is there to check/replace? On 2022-12-22 by Jamie

by InspectApedia (Editor) - Rheem Centurion II AC/Heat split unit blower won't run

@Jamie,

Check the air handler access cover door interlock switch.

by Jamie

@InspectApedia (Editor), As far as I can tell, its working. I hold it in when I'm inspecting things and everything appears to work except the blower. Gas blower and system seems to start but won't continue because blower isn't running. Have 2 green lights on the control board that come on.

by InspectApedia (Editor) - check that voltage is being delivered to the blower

@Jamie,

You checked that voltage is being delivered to the blower, right? With all that new stuff I'd then suspect that either we've missed a control that's keeping the blower off or a wiring error.

The fan limit switch has to be wired right and working
If the fuel is gas and there's a spill switch that has to be working and not tripped, etc.

You can leave the thermostat out of the equation by removing the tt wires at the air handler and jumpering the 2 T T terminals - that's what the thermostat does on a call for heat.

Then step through all of the diagnostic checkpoints

first at BLOWER FAN WONT START

then if necessary, also see

NO HEAT - FURNACE.

 

I can't find the fan limit switch on my air handler.

I cannot find the fan limit switch.

The plenum is above the blower and does not have an access panel. I assume it would be located in a position to gain access.

My air handling unit has the blower motor and control board/transformer above the evaporator and the plenum is above that level. On 2017-05-11 by Dan C

by (mod)

See our article series FAN LIMIT SWITCH to see locations and sppearance

by Dan C

I am very sure this system has no fan limit switch. The schematic does not show a limit switch.

The fan connects directly into the control board. I believe it is controlled by a P&B relay on the control board. The system will work properly most of the time after power down. I have also removed the G wire from the thermostat at the control board and it continues to run.

by (mod) diagnosing an air handler that does not use a fan limit switch

Dan C:

Air Handlers that use a gas or oil fired heat source would use a fan limit control switch.

An Electric heating system used as backup for heat pump would not require that control.

If that's your situation then I suspect there is a corroded electrical connection or a bad control board or relay in your air handler.

 

Can I turn off our attic air handler fan and still have air conditioning?

My fan in the attic runs continuously as it is for the heat. If I turn the breaker to off will it hurt the AC unit? On 2016-03-28 by Anonymous

by (mod) - probably not

If your same attic blower assembly is used for cooling, distributing cool air to the building interior, the A/C won't work with the blower turned off.

And if you called for cooling, it's possible that the cooling coil in the air handler would quickly ice-up as no air would move across it.

Can't run blower fan continuously without air the A/C cooling system running too

I recently had my blower motor replaced and my AC is working great but now when I just want to turn on my fan to circulate air, it blows ice cold AC air.

Did wires get crossed on my furnace contol board? Any suggestions on a fix? On 2015-09-23 by Pjespo

by (mod)

The thermostat's FAN ON switch should only turn on the fan so long as the thermostat temperature setting (in cooling mode) is above the room temperature.

If that's not happening I suspect a wiring or control board or relay defect.

 

Air flow pulsates at the supply registers: why?

Air movement speed from grilles is not stable-pulsation. What is possible reason? 2015-09-14 by Garri

by (mod)

Garri

First take a look at the blower fan operation for

- voltage variation

- loose wiring

- a defective control that is cycling the fan on and off intermittently

- loose belt on a belt driven fan

- loose pulley on a belt driven fan

- failing blower motor or blower assembly bearing

 

Thank you to our readers for their generous comments

LS 3845 said: it was a good read i can use the tips every day (Apr 28, 2011)


...





ADVERTISEMENT





...

Continue reading at BLOWER FAN OPERATION & TESTING - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see BLOWER FAN OPERATION & TESTING FAQs-2, more diagnostic questions & answers.

Or see these

Recommended Articles

Suggested citation for this web page

BLOWER FAN OPERATION & TESTING FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING FURNACES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT