Building Inspection, Diagnosis & Repair Info

Photograph of attic air conditioning air handler, condensate drips on floor Air Handler Repair FAQs

  • POST a QUESTION or COMMENT about how to diagnose & repair problems with the air handler or blower unit / fan assembly in a warm air furnace or air conditioning system

FAQs about Indoor air handler or blower unit for A/C or heat pump or furnace systems:

Q&A on AHU or air handler unit / blower unit troubleshooting and repairs.

This article series explains how to inspect & repair the indoor components of air conditioners and heat pumps: the air conditioning system indoor air handler units, blower units, or AHU's, (also called fan coil units) including the air conditioner blower fan, the indoor cooling coil or "evaporator coil", air conditioning system filters, and the causes, cures, and prevention of air handler leaks that lead to rust, damage, and mold contamination in the air conditioning system.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Air Handler / Blower Unit Diagnostic FAQs

Photograph of toxic mold growth on a squirrel cage air conditioner blower fan unit

These questions & answers about the indoor air handler fan / blower unit were posted originally

at AIR HANDLER / BLOWER UNITS - home. Be sure to see the diagnostic and repair advice that begins there.

The FAQs on this page pertain to the blower fan found in the indoor air handler or "blower unit" used to provide forced cool or warm air conditioning and/or heating in buildings.

...

Interesting AHU Blower Unit FAQs

Can a mouse in the air handler damage the blower fan?

Is it possible for a mouse to get into the air handler and cause the fan motor to get off balance and stop working?

Ours started making a loud noise and our ac tech says a mouse must have got in it and caused the fan to get off balance which caused the problem. I find it hard to believe that could happen. On 2018-05-26 by Steve

by (mod) - Yes, off-balance fan cage damages fan bearings

Steve

Yes indeed, though it's a heck of a ride for the mouse.

Once the blower and air handler unit AHU have been cleaned and perhaps sanitized, I'd check the motor bearings. If the blower fan was off balance enough it could have damaged the bearings.

 

Air handler control board fuses blown

Blown fuses (3A) on the air handler control board? Carrier Model CD3BXA036000AAAA made in 1995 repeatedly blows the fuse on the control board. I replaced the thermostat, disconnected one of the wires to the blower motor, but still have the problem.

The Red LED light on the board begins to flash after the fuse has blown. Any suggestions would be appreciated, I have limited electrical knowledge, but I do have a voltage meter and can generally troubleshoot or component replace. Thanks (May 18, 2014) Gary Matthias

Reply:

Blown fuses on a control board often take you to a faulty control or control board itself; check the obvious: loose or damaged wires; hard-starting motors, burnt relays, contacts.

 

What is the air handler door safety switch voltage?

on the air handler door safety switch , would like to know what volts is suppling the switch and where thanks. 1 Nov 2014 Anonymous

Reply: proper blower door safety switch voltage, installation, replacement, repair

Anon,

Usually a furnace or air handler blower door safety switch carries 120 volts. The switch is connected in series between a relay in the air handler that operates the blower fan and a terminal on a control circuit board in the unit. The switch is not powered independently. It's power comes through the circuit board.

You'll be able to see this by following wires from the blower door safety switch back into the air handler.

WATCH OUT for dangerous shock hazards. Be sure all power to equipment is off before touching any switches, wiring, etc.

Replacement blower door switches are easily obtained for your air handler by brand and model via your local HVAC supplier, from the manufacturer, or often online. Some safety switches will work properly on several air handler brands and models.

I add that the blower door switch is an important safety feature that helps avoid chock or chopped-off fingers or worse. Be sure that your replacement switch is properly mounted so as to be reliably operated by the blower compartment door(s) - the switch opens- cuts off power - when the door is opened, and is depressed in to close and permit power to the blower when the door is properly closed.

Be sure that your replacement switch is properly mounted so as to be reliably operated by the blower compartment door(s) - the switch opens- cuts off power - when the door is opened, and is depressed in to close and permit power to the blower when the door is properly closed.

See BLOWER DOOR SWITCHES found also

at A/C - HEAT PUMP CONTROLS & SWITCHES

 

How to seal attic air handler leaks

If a air handler is installed in the attic, should the unit be sealed so it doesn't suck in dust particles from attic insulation? Should an HVAC company inspect attic blown in insulation if the house was built before 1975? (Feb 20, 2015) Valerie

Reply:

Valerie,

as long as there is adequate return air being taken from the occupied space of the home, the air handler ought not be pulling dust from the attic. Ask your HVAC techs to confirm that return air is adequate .

You can also inspect the air handler interior for presence of attic insulation dust.

But yes I'd use foil tape to seal any leaks.

 

Is it economical to replace air handler parts or not?

Anonymous said:

Is it worth replacing the metering device coil of the air handler vs replacing

Reply:

Anon

Replacing the air conditioner or heat pump refrigerant metering device usually means replacing a capillary tube or thermostatic expansion valve (TEV).

That's a discrete part that's reasonable to replace rather than replacing the whole system provided the rest of the system is in good condition.

So in sum, it depends on the equipment age and condition. What does your HVAC service tech say?

 

Question: track down source of moisture, rust, corrosion in air handler

I have Unico mini-duct system in my attic. Every winter, the fan motor and shaft accumulate rust. I live in a very cold climate in winter (Vermont). Last year, I had the motor replaced and this spring, there was rust on the motor again (no visible rust last Fall when I closed the unit up for the winter). - JL 2021/07/01

...

My technician agreed to problem cannot be caused by the dryer venting back up into the attic.

The Unico system is pretty air tight due to it being a high velocity system.

He also did not think the two outlets that I never open would be the source of condensation for the winter months. Nor did he think running the fan in October just before I close it up could cause excess moisture to accumulate since the air is pretty dry in Vermont (low humidity) in October.

So we still have a mystery. He said the unit was completely dry inside today despite the fact it was hot and very humid here yesterday. - JL

So we still have a mystery. Thanks for your suggestions and comments though. If we ever figure this out, I’ll let you know.

Moderator reply: sources of water in the duct system

Thanks for the follow-up, do keep us posted, as what you find will certainly help other people too.

In investigating, start at the point of most-concern such as rust or corrosion, and follow the water or water indicators, stains, signs, rust patterns, etc.

See our full conversation now found

at WET CORRODED DUCT WORK

Where do I get a wiring diagram pdf for a York Air Hander Unit?

Hi, I´m working in a small project, but I need the diagram pdf for an Air Handling Unit (heating)
the model that I could find is:
YORK
MODEL G+FD060S24A
SERIAL NUMBER: EGHS622778
5005 YORK DRIVE

If you can provide me with this information, I´ll be so grateful
Thanks On 2020-04-25 by JOSUE ROJAS

Solution by (mod) - York HVAC Manual

Josue

See if this manual helps you out

https://inspectapedia.com/aircond/Unitary-York-Manual-036-21002-001-b-0600.pdf


as from a quick look at the equipment table that guide, now from Unitary Products, includes your York MODEL G+FD060S24A

Can the air handler blower unit's cooling coil be replaced?

Can the coils in the air handler be replaced or do you need to replace the whole unit? On 2020-02-19 by lowell

Answer by (mod) - yes but check the cost

Yes, an evaporator coil in the indoor air handler can be replaced.

But particularly if your air conditioner or heat pump is an older unit or one likely to be facing other repairs soon, I would compare the cost of the replacement job to the cost of whole unit replacement.

...





ADVERTISEMENT





...

Continue reading at AIR HANDLER / BLOWER UNITS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see AIR HANDLER / BLOWER UNIT FAQs-2 - intermittent fan operation or fan noise questions and answers about air handler units.

Or see these

Recommended Articles

Suggested citation for this web page

AIR HANDLER / BLOWER UNIT FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT