Thermostat Switch Setting FAQs
Questions & answers on how to set the room thermostat switches:
Frequently-asked questions & answers about how to set the various switches and controls on a room heating or air conditioning thermostat.
This article series explains the use, setting, and adjustment of the FAN On-Off and MAN-AUTO switches on room thermostats.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Recently-posted questions & answers about the settings of external switches on a room thermostat, posted originally
at THERMOSTAT SWITCHES, EXTERNAL
...
My thermostat has two bulbs of Mercury in it.
My heat does not come on at all.
I have a Carrier heat pump thermostat. It is not working at all.
It will not turn on at all. It was working yesterday morning when I left for work. When I came on yesterday evening it was not working. On 2017-11-29 by Melanie -
Reply by Mod
Melanie, and other readers,
First check that your thermostat is set to HEAT mode and that the temperature setting is above the current room temperature shown on the thermostat's thermometer.
Then if your heat still doesn't come on, check out the following "no heat" diagnostic procedures - choosing depending on the kind of heat you have in your home
- NO HEAT - BOILER - hot water heat, baseboards, radiators, steam heat, hot water radiant heat
- NO HEAT - FURNACE - forced hot air heat
- HEAT PUMPS - heat pumps as primary heating system - or see LOST COOLING CAPACITY (the heat pump won't run)
- BACKUP HEAT for HEAT PUMPS - back up heat for a heat pump system
My heat won't turn on when its on AUTO mode. - John 10/30/11
I have a 2 zone oil fired boiler, central heat/air. The 1st floor stat operates heat/air, fan comes on, everything ok. 2nd fl, when turning stat to heat, fan comes on but boiler doesn't come on. - Walt, Tunkhannock, PA, 5/13/2012
Reply:
John
Start at
Also see
When I leave my mode on heat, but fan on auto, the heat doesn't come on. When I put the fan on and heat on, then the heat comes on. For AC, it works on both on and auto. On 2017-11-26 by Calvin -
Reply by (mod)
Calvin,
Are you sure if the heat is actually coming on or could it be that you're just feeling air movement from the fan being on?
Please check out the diagnostic and repair suggestions found
...
My heat switch is off but heat is still coming out the tFitlrs as it's on 90 degrees what do I do to turn it off if switch is broken - On 2017-11-23 by Anonymous-
Reply by (mod)
Anon
Using the InspectApedia search box to look for "heat won't stop" we find THERMOSTAT WON'T TURN OFF -
which contains diagnostic suggestions; please start there.
Or just go to the power switch for your furnace and turn it OFF.Also see COOL OFF HEAT THERMOSTAT SWITCH
I set the lever to "off", but still the heating wont go off. Before the heating was on and at AUTO and it was not turning off after a while and then getting on again automatically like it should. - Sarah 2/9/2012
Reply:
Sarah,
If your home has more than one heating zone, another thermostat could be calling for heat;
If your home has only a single heating zone, then I suspect thermostat wiring has shorted together or the thermostat is not working properly.
For now, turn off power at the switch for your heater and call a service technician.
See the diagnostics at
Also see
I had my outside unit (electricity only) disconnected before winter started by the furnace man so as to run just the inside furnace. (older Lennox) This is due to a fault on the circuit board causing the defrost cycle to keep running (defrosting) while in heating mode.
Otherwise the furnace works, but you just have to turn it off when it starts defrosting unlike the cooling which always works fine even still. But of course I can't use it while disconnected. It only took the furnace guy a few minutes to disconnect it. Right now I can't afford to pay him to come out and turn it back on.
I would like to turn it back on myself. How would I do this? Eventually of course I will have to replace the outside unit because they say it's to old (1975) and no parts. On 2017-05-20 by zak -
Reply by (mod) -
Zak:
I am uncertain just what equipment you have installed.It SOUNDS as if you're talking about a heat pump system whose outdoor compressor/condenser unit doesn't work so you want to run just your inside backup heat system.
If an outdoor unit is OFF then the whole refrigerant cycling system is OFF and you're relying on backup heat: I don't understand what defrosting in heating mode would be needed.
One could jury-rig a switch to interrupt power to an electric heater, but I can't recommend such an attempt, in part because I don't understand the problem and in greater part because fooling around with the wiring by someone not fully trained/informed could kill somebody.
...
The a.c.fan is it to be on auto or on ? On 2017-08-29 by Dean
Reply by (mod) -
Dean,
Set the fan switch to Auto. If you set the fan switch to on it will run continuously.See the instructions and diagnostics at
When turn unit to auto won't turn on but when turn fan on will come on On 2017-03-22 by D C Henderson -
Reply by (mod) -
DC
That's because (perhaps) the FAN ON switch simply forces the fan on regardless of heating or cooling system temperature.
That is, your heater or air conditioner still isn't turning on.
If you've lost heat search InspectApedia for NO HEAT FURNACE using the search box just above to see helpful diagnostic and repair stepsSee the instructions and diagnostics at
I have central air and heat and the heat works fine and blows perfectly but the fan will not turn on and the air conditioner wont turn on. I recently replaced the thermostat. do you think it could be faulty? - Warren Wirth 7/12/11
Reply:
Warren: first be sure that your new TT is in COOL mode and then try the fan in ON position to see if you can force it to run - if so move the switch to AUTO. Set the TT below room temp;
If nothing is happening I'd double check the thermostat wiring and confirm that there is voltage on the TT wires too - if the wires were shorted during installation you could have blown the transformer.
Also see
I have a Goodman AC and gas furnace. Lately I noticed that the fan will come on without the temperature on the thermostat calling for AC
The fan will come on for about 2mins and shut off.
Then about 15-20mins later do the same thing. No AC just fan. And it will do the same without the thermostat being connected
Any clues as to what might be the issue?
Thanks for your help - Al at alsblackvw@yahoo.com, 8/27/12
Reply:
Al, while some systems include a defrost cycle that can run a fan without a thermostat calling for heat, I wouldn't expect that to happen every 15-20 minutes when the system is not in use. I suspect a wiring or control board problem.
See the explanation and advice
...
How do u switch from heating to cooling inside the unit itself On 2017-05-03 by Dewey haney
Reply by (mod) -
Dewey
When you change a thermostat from HEAT to COOL mode, it will switch a second pair of wires that in turn operate the appropriate relays in your air conditioning air handler/compressor/condenser units.See COOL OFF HEAT THERMOSTAT SWITCH
You should not have to change anything inside the furnace unit itself.
is my ac condenser blower supposed to run when my thermostat is in heat mode On 2017-02-26 by Anonymous -
Reply by (mod) -
If your system is a heat pump and is in HEAT mode and if the outdoor temperature is not so low that the heat pump can't produce heat without switching to your backup heat, then, yes the outdoor compressor/condenser unit including the compressor motor and the fan motor should run.
Hello, my AC was switched on to the run side, instead of auto side.... it was on like that for maybe 1 week or more... will that cause the unit to run out of coolant faster, and cause my electric bill to increase tremendously? On 2017-02-22 by Susann -
Reply by (mod) Air conditioners do not "run out of coolant"
Susann,
No. Air conditioners do not "run out of coolant" - refrigerant used in air conditioners and heat pumps is a sealed system and never needs replacement unless
1. there is a leak (that must be found and fixed)
or
2. the system refrigerant piping has to be cut open for other reasons, such as replacement of a compressor or expansion valve.
Reply by (mod)
How odd. You're not sleep-thermostat-adjusting, right?
Check for a programmable automatic setback on your thermostat.
If your thermostat doesn't have that feature then
I'd replace the TT batteries.If that makes no difference, I'd be looking for
- a bad or loose wiring connection - possible
- a failing control board, switch, or relay in the air conditioning system
- a bad thermostat itself
But more details would be helpful: is the TT display going blank or what?
Is there any evidence that your system is not working properly: such as reduced air flow from a blocked or iced up cooling coil?
What do you do if the wall unit blanks out and you can't see the temperature etc and can't see the buttons to program anything?? Does this open and maybe need a battery? Thank you On 2015-07-07 by Anonymous
Reply by (mod)
Replace dead batteries in the thermostat.
If that does not work,
Check that electrical power is on at the air conditioner or heater controlled by the thermostat.
Check that the transformer powering the thermostat circuit is working.
Check that the wiring to the thermostat is intact.
We have an old Carrier Nova air conditioner that stopped working.
An aircond mechanic fiddled about for ages and ended up changing the control switch to an LE75 Temperature Control.
It now works but only heats or cools by about plus or minus 2 degrees Celsius.
As well there is only one fan speed (low) The others won't pull in but I can hear them trying.
The mechanic won't come back and others throw their hands in the air as they don't know where to start.
Any suggestions about how to tackle this problem?
Many thanks,
Peter
Sydney, Australia - 6/10/11Reply:
Peter, I'd start with the diagnostic suggestions found
at DIAGNOSTIC GUIDE A/C or HEAT PUMP
Sorry to read about such aggravation but at this point you need a service call from an experienced tech. Call someone else, talk about your concerns with the service manager, don't bad-mouth the prior tech or the new ones may figure you're hard to work for.
Just explain that prior attempts to get things running didn't work and that tech gave up. Keep us posted.
Reader Follow-Up:
Hi,
Thanks for your reply,
To refine my question. ..where is the best place to start to look to get the
fan operating at full speed?
Cheers and thanks.
PeterReply:
For a single-speed fan, Peter, at the Thermostat turn the FAN ON switch to ON to see the fan run; Or on some air handlers that combine heating and cooling there should be a fan limit switch that may include a white knob that can be pulled our pushed to turn on the fan.
On a system that has a dual speed fan, I find that if the thermostat SET temperature is significantly below the current room temperature the control board in the HVAC air handler will step up the fan to its faster speed.
...
How do u change the Thermostat for it too blow cooler Air. - Christie 7/5/12
Reply: you can't do that at the thermostat
Christie, you've asked a helpful question - let's clear up some confusion about wall thermostats: the thermostat is not an accelerator - it doesn't make the air conditioner run faster or slower, nor warmer or cooler. Nope. The thermostat is basically an "ON-OFF" switch that turns the air conditioner ON or OFF in response to room temperature.
First make sure your thermostat is the one that controls your air conditioner. In some homes different or separate thermostats control heating and cooling. If you are at the air conditioner thermostat be sure it is set in COOL mode; typically the fan switch is set to AUTO.Then set the desired temperature to a number lower than room temperature and your A/C should operate. If at that point equipment does not turn on there is a problem to troubleshoot - but first let's summarize:
So if you SET the thermostat to call for a temperature lower than the actual room temperature, the A/C will run until the room temperature drops to the SET number.
Now if the A/C runs forever and never cools the room down to the SET temperature then either the SET number is lower than the capability of the air conditioning system (say setting the temp to 60 °F when it's 110 outside at a home that has a lot of heat gain)
Or
The air conditioner needs repair.
Before calling the repairman check for
- a dirty air filter or closed air supply registers - both of which reduce the cool air flow
And if you click on "Air Conditioning" in the links across the top of this page, then on the left side of that web page you'll see an article titled "LOST COOLING CAPACITY" that offers some homeowner diagnostic steps that can help figure out why the air conditioning system is not cooling as well as you'd like.
My apartment manager has shut off the heat in our building and is transitioning to A/C (only one works at a time).
They sent out an email stating "we have shut the heat down and now have to let the lines rest and come to temperature before we can start the AC."
I've never heard of lines "needing to rest" before using the air conditioner (I'm from the south but I moved to New England this year)
Is there something different about A/C units here that makes this necessary? Does this sound legitimate, or is the manager pulling our chains? - On 2017-05-19 by Anonymous
Reply by (mod) - 24 hours would be more than enough to swap between heating/cooling modes,
Typically 24 hours would be more than enough to swap between heating/cooling modes, and even then the problem being avoided would be avoiding turning on an air conditioner or heat pump in cold weather.
I have a two story house with dual units. No one uses the upstairs while my daughter is in college.
I turned the thermostat way down in the winter, and way up in the summer, so that I'm not heating and cooling an entire floor of a house that isn't used.
I was told by a friend that this is really bad on my unit, which is relatively new, is this true?
Do I need to go back to the four degree difference between the two units? On 2016-12-05 by Anonymous -
Reply by (mod) - Yes
No you do not. An air conditioning system should not be damaged by leaving it turned off or set to temperatures reducing its run-time.
My heat pump will not come on in heat mode. I can't hear any kind of buzzing at the outdoor unit either. The system works fine in A/C mode. The auxillary heat works as well, but the outside unit will not come on for heat. On 2016-01-04 by Brian
Reply by (mod) -
Brian
If the thermostat is properly set and outdoor temperatures are not lower than its operating range, the heat pump should be working (if it is a heat pump and not just an AC unit).Keep in mind that a thermostat may say "HEAT" mode but if the unit installed is just an A/C unit some other heater has to be switching on - such as a separate furnace, boiler, or backup heating system.
If your system is truly a heat pump and it won't heat and the thermostat settings are correct and if outdoor temperatures are not below the heat pump's operating range, I expect your service tech will check for a bad outdoor temperature sensor, control, or relay.See COOL OFF HEAT, Thermostat Switch to be sure you're using the proper settings and that the thermostat is wired properly.
Heat pump wont blow out any heat. But it works on air conditioninbg and dry (fan only). But in "heat" mode we get no heat. - On 2016-11-13 by rhonda
Suggestion by (mod) -
Rhonda,
If you're sure that your system is indeed a heat pump, not a straight air conditioner, and if you're sure that the thermostat is calling for heat, then either there is a control problem or relay problem in the heat pump unit or the outdoor temperature is low enough that your system wants to run on backup heat and it's the backup heat that's not working.See BACKUP HEAT for HEAT PUMPS to read details.
...
Continue reading at THERMOSTAT SWITCHES, EXTERNAL or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see THERMOSTAT SWITCH FAQs-2 - more-recent questions and answers about the switch settings on a room thermostat.
Or see these
THERMOSTAT SWITCH FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about finding, using, diagnosing, repairing, or replacing water pressure gauges on private well systems.
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.