A/C & Heat Pump Capillary Tube FAQs
Air conditioner & refrigeration equipment capillary tubes questions & answers.
This article series explains the function and installation of capillary tubes or "cap tubes" used to control or meter the release of refrigerant into the evaporator coil of an air conditioning or heat pump system, home refrigerator, freezer, dehumidifier, or other refrigeration equipment of up to 6 tons in cooling capacity. We define and explain the function, installation, servicing, and replacement procedures for capillary tubes.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Our page top sketch of common visibly detectable capillary tube defects is provided courtesy of Carson Dunlop Associates as is the cap tube explanation at left.
Hi, installed new compressor on my 4 ton air conditioner with 407c weighted charge system.
Low side and high side matches pressure on my gauge. System has refrigerant metering devices with 6 distributors capillary tube.
My problem is my compressor start freezing up as soonest start air conditioner and within 10 or 15 min compressor turn off but evoporater fan still on inside.
Need solutions asap On 2019-06-12 by chetanvvnagar
by (mod) -
That sounds like the thermostatic expansion valve is not adjusted properly and is passing too much refrigerant.
Watch out: that can damage or destroy the compressor motor.
Piston metering device on an R-22 system.
I have a piston metering device on an R-22 system. the high side pressure is good with very little change. The low side pressure hunts between 70 psig and 77 psig. On 2019-05-21 21:30:45.903487 by J
Reply by (mod) -
J
I'm unsure exactly which refrigerant metering device you're using. It's possible that the piston is jamming or icing. Are you seeing abnormal icing anywhere in the system?
Below is an example of a more-sophisticated capillary tube refrigerant control: York Part# S1-022-06844-051 as an example but we need more specifics.
Can I add a TXV ahead of the cap tube?
Hi, can I add a txv before the capillary tube? 1999 5 ton Payne split Recidential thank you. On 2018-05-11 by Leo
by (mod) - no
Leo
I don't think so. If the cap tube isn't working the thermostatic expansion valve is not going to fix the problem. It's an either-or type device.
hi sir, i have 3ton central split unit, and i want fix new capillary tube, please tell me which size and length i can use? On 2016-07-11 y siddiq -
by (mod) - don't do it yourself
Sid
Unless you're a trained HVAC repair person and have proper equipment, I doubt that you can successfully replace the capillary tube yourself.Doing so requires knowing how to remove refrigerant from the entire system without releasing any to the environment, cutting out the old cap tube, brazing in a new cap tube without blocking the tiny tube with excessive brazing compound or solder, installing a filter or two on the refrigerant line to capture any debris introduced into the system, pulling a vacuum on the system, checking for leaks and fixing any that are present, the installing a proper refrigerant charge and testing the system for proper operation.
So while you could match the diameter and length of an existing capillary tube by simply taking the old one to your HVAC supplier, that's not going to cut it.
Sorry.
I just replaced a compressor (R22 wet) and condenser unit on an old system. The coil has what I believe is cap tube metering.
The liquid line (3/8") enters a manifold of sorts which splits into four small line imediatly before the coil. The manifold as I call it can be dis-assembled (no I did not take it apart) it look like a couple of plumbing fitting.
The HVAC vendor I bought the condenser unit from said to release all the freon into the system. I think it has to be charged just right to get the high and low pressure correct.
The house is out in west texas so its difficult to get a tech (nearest) to drive 100 miles. Sound like I'm going to have to beg one to make the trip unless someone can help on line. Please advise and thank you. (May 8, 2012) Wayne
Reply:
Wayne I'm not certain I have a clear understanding - perhaps you could send us some sharp photos of the cap tube system you describe? Use the CONTACT US link found at page top or bottom of any of our web pages.
Often a cap tube is branched into several smaller distribution lines that meter refrigerant into different sections of a cooling coil - it's simply a means of efficient distribution to improve coil efficiency, and shouldn't affect the charge quantity.
(July 27, 2012) Anonymous said:
received a piston kit with the new ac condenser size 065 my a coil from another manufacture look to have a number 69 on it . Could this cause a problem with pressure or frost and are pistons interchangeable with different equipment makers
Reply:
Anon I may be missing something in your question or we are confused about why you are working with a piston kit.
An air conditioning system "piston kit" in my lingo refers to a piston and probably rings intended for use in rebuilding a compressor motor - not something we'd see on a residential cooling system (where techs replace the entire hermetically sealed compressor).
On some air conditioner compressor motors failures of the piston ring can lead to a compressor failure and damage to the piston cylinder wall. Rebuild kits can be similar to automobile engine rebuild kits - the cylinder is bored, smoothed and an oversized piston and ring kit are installed. Without a piston repair a commercial refrigeration compressor motor may be unable to develop full head pressure.
About interchangability, the answer may seem a bit obvious, but basically if the piston shape and measurements match the compressor motor design specs it's "interchangable". If not, not.
I've got frozen capillary tubes just beneath piston metering device. Can the orifice be plugged. The evaporator coil is warm. John (Feb 16, 2014)
Reply:
If the cap tube is ice covered I'd start by checking the refrigerant charge level.
Mar 31, 2014) doug said:
My fridge just isn't cooling great - okay, but not great. I pulled the plastic tubing off of my refrigerator capillary and there was a rough feel to the metal and what I think was a white substance on the tube, maybe some moisture. I'm not sure because I wasn't paying too close attention because I had not found this excellent article by then. Would those things I mentioned possible pertain to a leak in the capillary?
thanks.
Reply:
Doug,
Usually a leak in refrigerant piping will produce an oily substance (lubricant in the refrigerant oil), and further, if you had a leak in the piping most likely you'd lose all refrigerant and get no cooling at all.
Is it possible that the cap tube was intended to be in good thermal contact with another refrigerant tubing section and that the white substance you found was a thermal grease?
Last (for now) check the obvious things first: blocked air flow, wrong control settings, imablanced setting of controls for a freezer compartment vs. refrigeration compartment; or a stuck defrost timer;
(June 1, 2014) Anonymous said:
if capilary tube is choked ,then frost will form on sution pipe & then compresor will trip
Reply:
Thanks for the comment, anon, but I'm not quite sure I follow the reasoning for all cases. I think you mean that refrigerant flow is reduced but not stopped entirely. That condition can also occur with TEVs and indeed can look like low refrigerant - frosting at the cooling coil
(June 8, 2014) allen said:
whats the distance between tne tube and evaperatercoil?
(June 16, 2014) Patti Greenwood said:
As soon as our system kicks on, the capillary tubes frost over. Earlier in the day, the larger tubes were frozen over. The fins are near spotless clean as we had them cleaned about six months ago and we replace the filter monthly. What could be the problem?
Reply:
Patti
Some frost formation is normal; if however you are describing a change in how the system operates I suspect a refrigerant leak.
(july 14, 2014) anonymous said:
Sir. Could you please explain how condensation of the now heated freon gas takes place
Reply:
Anon,
At the outdoor compressor-condenser unit the returning freon is compressed to a high temperature high pressure gas. That gas is circulated through the outdoor condensing coil. Key is that the gas is at high temperature AND high pressure.
Blowing outdoor air over the outdoor condensing coil transfers heat from the gas to outdoor air, cooling the gas back to a liquid.
(July 26, 2014) Bill said:
Oustside compressor-condensor connected to the indoor gas furnace. It appears the de compressor had a burn-out. It was replaced with a new one. I had the system (circuit)flushed with nitrogen, vacuumed pumped and re-filled with coolant.
All pressures seem "OK" Systems runs fine but no refrigeration is present. The air coming out of the ducts at ambiant air temperature. What is the possible cause of this?
Reply:
Bill,
I'm not sure what you mean by "no refigeration is present" - you say the system runs fine. I think from the rest of your note you mean the system is not cooling.
If the system was properly charged with refrigerant and the compressor is indeed working and developinng proper pressures (which I doubt) then perhaps debris from the burned out compressor has clogged the refrigerant metering device.
A burnout filter should have been installed on both suction and supply sides. The system may need further cleaning and a TEV may need replacement.
Aug 2, 2014) Bill said:
Thanks for responding to my query. He is some additional information. Only a expantion device was present at the plenum coil. An TEV was installed. The circuit was put under vacuum ( down to 940 on the vacuum scale) and refilled with coolant. System was turned and running. The high pressure guage that was connected at the oustide unit was not showing more than a value of 50 when the technician was expexting about 100 ( not certain if this mean is in PSI) No refrigeration was present inside de plenum the air emperature being at ambiant (around 71f) Looks like something is "blocked".. Do you have an opinion?
(Sept 23, 2014) Daniel
I think it is important to note that we are talking about refrigerants here, not coolants, and not Freons.
Coolants don't change phase to do their job of transferring heat, the liquid coolant in your car's cooling system is a liquid and is supposed to stay a liquid.
Refrigerants do change phase, usually from a liquid to a gas and back again, but even the ice in a drink can be seen as a refrigerant since it is changing phases, from solid to liquid, to keep your drink cool.
Freons are certain refrigerants, usually CFCs (like R11, R12) and HCFCs (Like R22) made by DuPont Chemicals.
It is somewhat OK to call say R22 from any manufacturer Freon, it's the same as calling any adjustable locking pliers Vise-Grip whether or not they were made by Irwin.
What is not OK is to call refrigerants that DuPont has never called Freon by that name, for instance calling R134a a Freon is wrong, because DuPont calls it Suva.
Reply:
Excellently put, Daniel. I agree completely. However because many readers are not familiar with proper refrigerant terminology we find that people looking for information about refrigerants search on all sorts of words that we might agree are not quite correct. "Freon" has become about as generic and mis-used as "kleenex" for "tissues". Your note is helpful to readers who want to speak accurately, while keeping the word "freon" around helps people find it. I'll copy your comments into our text on refrigerants
(Nov 15, 2014) Anonymous said:
iam facenig frequent choking at the time deepfrezer gas charging of R-134 A What precautions i have to take
Reply:
Try charging from the low side using gas only.
...
...
Continue reading at CAPILLARY TUBES - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
CAPILLARY TUBE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.