Heat Pump outdoor unit defrost cycle repair questions & answers.

This article series discuss the reasons for, duration of, and control of the defrost cycle at the outdoor compressor/condenser/fan unit of a heat pump when in heating mode.

Page top photo: the snow cover itself is not a functional issue for the equipment, but the placement of the condenser unit just a few inches from the building wall may be an operating issue by restricting air flow around and through the unit.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





HVAC Compressor/Condenser Unit Frost, Ice & Defrost Cycle FAQs

Note: these heat pump defrost cycle Q&A were posted originally

at HEAT PUMP OUTDOOR UNIT DEFROST CYCLE - be sure to see the repair advice at that page.

Smoke coming out of outside condenser unit - in defrost mode?

The fan on my outside heat pump wont run for a few minutes. Smoke or humidity is coming from unit when this is happening.

The indoor heat unit is running but coils are cold as if in A/C mode.

After a few minutes the fan outside comes on and all is well inside and out. Is this normal? On 2018-12-19 by Ms. Dil

Reply by danjoefriedman (mod) - smoke indicates possible fire risk and need for repair

Ms. Dill

Watch out: IF you see actual smoke at the outdoor unit that sounds as if there is an electrical failure and possibly even a fire risk at your outside compressor/condenser unit.

THEN eave power to the unit OFF and call for repair.

IF on the other hand the unit is simply going through a defrost cycle that might keep the compressor from running for a time.

Outside condenser fan turns on several times per hour even when no heat is blowing inside - Explain the Defrost Cycle

Heater on heat pump works. But, the outside fan turns on several times per hour even when no heat is blowing inside. Is this normal? 2018-11-05 by Aaron

Reply: Why and when a heat pump goes into a defrost cycle when in heating mode

Aaron;

When your heat pump is in heating the outdoor unit (compressor condenser) is extracting heat from (even chilly) outdoor air.

The outdoor unit fan runs, air moves across the outdoor coil, heat is absorbed from outdoor air into the coil and into the refrigerant inside the coil where ultimately that heat is delivered indoors through the indoor air handler.

Why does ice form on the outdoor coil?

In heating mode, as heat is extracted from the outdoor coil its surface becomes colder than the outdoor air temperature and can drop below freezing. Then moisture in outdoor air freezes on the coil surface.

Why is a heat pump defrost cycle needed?

Ice on the outdoor coil blocks air flow across the coil; with no air flow, no heat can be extracted from the outdoor air and worse, the compressor motor itself could be damaged.

So periodically the outdoor unit will go through a defrost cycle. A control board in the outdoor unit is the control over when a defrost cycle occurs.

Just how often a defrost cycle will occur is determined either by a timer on the outdoor unit’s control board (when in heating mode) or by sensors that some heat pumps may use to detect the presence of ice on the coil.

Depending on your heat pump brand and model - thus the heat pump's design - the outdoor unit in heating mode will run a defrost cycle as often as once every 30-35 minutes OR (on some more sophisticated designs) the heat pump may only run a defrost cycle if sensors tell it that the outdoor coil is iced over.

Factors that affect the frequency of a heat pump (in heating mode) outdoor defrost cycle include:

- the heating load - amount of heat being delivered indoors

- the compressor and control design (timer versus ice sensors)

- outdoor temperature (closer to freezing, more frequent defrosting needed)

- outdoor humidity (more humidity, faster ice formation, more frequent defrost needed)

What happens at the outdoor heat pump unit during the heat pump defrost cycle?

Usual design:

The compressor motor will continue to run - compressing and thus warming refrigerant in the system.

The outdoor fan will stop until the ice has melted away.

In some designs both the compressor and the fan may stop and electric heaters may be used to perform the necessary defrost.

When does the defrost cycle stop (for a heat pump in heating mode)

The defrost cycle will typically stop after about ten minutes maximum, and often sooner.

The defrost cycle will stop when temperature sensors at the outdoor unit detect that the coil’s temperature is high enough that no ice would be expected to remain on the unit.

Watch out: do not turn off your heat pump if it’s in the middle of a defrost cycle, or if you must turn it off, leave it off for at least 30 minutes to avoid damaging the compressor motor.

What happens at the indoor air handler during the heat pump defrost cycle?

During a heat pump in heating mode defrost cycle the indoor air handler will normally stop blowing air into the occupied space - that's because the system is not receiving heat and the designer doesn't want to blow cool or cold air onto occupants.

Indoors at the air handler or on some systems right at the thermostat a colored or blinking indicator light may tell occupants that the delivery of heat has stopped for a few minutes to permit a defrost cycle.

Abnormal Outdoor Heat Pump Unit Fan-On Cycles

If your thermostat does not call for heat for an hour or more (perhaps because the indoor thermostat is satisfied) I would not expect the outdoor unit to require more than one additional defrost cycles and I'd not expect the outdoor compressor/condenser fan to continue to cycle.

So if that's happening I suspect a temperature sensor or a condenser/unit control board error that's worth a service call.

If the outdoor unit is defrosting too frequently (at intervals of less than 30 minutes) something is wrong.

If at the same outdoor temperature that frequent defrost cycle has occurred since original installation, the unit may be under-sized and unable to provide the amount of heat being asked of it.

If the indoor air handler air filters or blower fan are dirty then the indoor air flow and heat delivery are reduced and the heat pump may be over-taxed (as it can’t satisfy the thermostat).

If the coil in the indoor air handler is dirty that too blocks air flow, reduces heat delivery, and over-taxes the heat pump.

Also check this article

SHORT CYCLING AC COMPRESSOR 

Steps to diagnose Carrier heat pump not cooling: defrost cycle problem

Carrier heat pump system data tag (C) InspectApedia.com LynndThis question pertains to a Carrier heat pump, 25HCD348A00310.

We have had a long ordeal of inexplicable problems and sky-high electric bills despite the fact that the unit was under five years old when we moved in.

During a housing inspection — summer of 2017 — the unit was found to be operating on fan but not blowing cold air. HVAC tech rearranged location in breaker panel and removed some clogged filter material a prior owner had placed behind the intake and the system began operating normally.

Upon moving in a couple months later, we inherited a box of paperwork from the previous (elderly) owner suggesting the homeowner had been charged repeatedly for service calls involving swapping out thermostats beginning within a year of the installation.

In 2018, our first full summer in our 1400sq home, our electric bills went through the roof despite the fact that the house is insulated and has newer windows (double pane).

After much Google searching I suspected the heat strips were running with the AC but it took TWO YEARS of paying almost a grand a month in summer before the HVAC tech took a closer look at the thermostat wiring.

(We got the sense that it was not possible to readily tell that the heat strips were operating in cooling mode. In any case this was the same owner-operator that had performed our pre-sale HVAC inspection.)

The first time we had the tech out on a service call was winter 2018 — before we had reason to suspect our electric bills would be so high the following summer.

Tech found that the unit (indoor section) was fitted with a higher-rated fuse (we speculate this was a work-around given to the prior owner to keep it from blowing).

Replaced fuse and everything was back up and running.

However, a day later the fuse and the transformer blew.

Tech replaced those parts and tested continuity, claimed everything read correctly. He did not find any issue with the wiring, either, so he replaced fuse again.

Ran okay until winter 2019 when the same situation occurred This time he replaced another part involved in the thermostat call for the unit to switch on (there was again snow on the ground and apparently it was sticking).

Replaced this part (sorry don't recall the name) and installed another fuse.

Ran until winter 2021 when it "died" again on the coldest night of winter (snow again on ground). Tech then tested the blower/fan/relay and found it to be operational. Replaced the fuse and it began running again.

When he went to put the panel back on the outdoor unit, it shorted again. Tech reported the wiring looked okay (no breaks) but cut the ends and reconnected just to be sure the connections were tight. (Speculated that vibration from the outdoor unit may have caused the wiring to short.)

Questioned the tech as to the repeated bills associated with paying to replace fuses every year but he essentially shrugged his shoulders.

This time, however, he left two spare fuses behind. Got another six weeks of use from the system without issue before the system died again, this time in 90 degree Spring weather. (All previous instances were in very cold weather.)

Spouse popped in one of the two spare fuses the tech left behind but after running normally for about 20 seconds the fuse tripped again. No sign of icing on the outdoor unit. No visible blockages.

As an aside: Tech was asked by myself on his prior call ~6 weeks ago if he checked refrigerant levels and admitted he did not because checking them would allow some of the refrigerant to escape. Said he put his tool on the line and it was sufficiently cold that he didn't think that was necessary. Was that method of verifying that there is enough refrigerant circulating adequate or should he be doing more?

I reminded the tech of a conversation I had had with him the year before when I related that I had come across a report online — which unfortunately I lost track of — in which it was suggested that Carrier had an issue with some of their control boards causing intermittent low voltage issues.

Asked him to check with Carrier to see if the board itself needs to be replaced — but he did not follow through on that request prior to the fuse tripping again the other day.

We're back to Square One and concerned that the tech isn't doing anything more than metering for 24volts. Might there be another way of identifying a short (a tool he should have or that we should inquire about)?

We are at wits-end with this. Spouse works in IT and can swap out boards on his own with no issue but the question is which board?

Last night I pulled the trigger on an aftermarket defrost control board on the guess that it might be operating improperly because our electric bills are still excessive in the summer (~$700) despite having the supplemental heat strips rewired.

My thinking is that an intermittent fault with the defrost board could be calling for it to defrost even in warm weather, which could conceivably explain why our electric bills in the summer did not drop as much as expected after replacing the thermostat wiring to address the heat strip wiring problem.

Am I on to something? If so, did I order the correct part # HK32EA007 (found on Amazon)?

Lastly: At one point about a year ago our HVAC tech suggested we replace our thermostat but we found it difficult to believe that would be necessary.

We didn't like the one that was installed when we moved in so the one he was suggesting we replace was not even a year old (Emerson UP310).

Our STAT replacement in 2018 came after a long-line of consecutive STAT replacements by the prior owner.

We are supposedly dealing with a master tech (business owner), yet my impression is that that rather than go through the entire troubleshooting necessary to diagnose a low voltage short, the HVAC techs who have come to our address current and former have simply cut corners by putting in replacement fuses and/or by recommending the customer replace the STAT. As a result, I tend to be skeptical that the thermostat is the culprit.

Should I replace the thermostat anyhow?

Ultimately our fear is that if these fuses keep tripping a more expensive component will be damaged. Is that a valid concern?

Any suggestions on where to go from here would be IMMENSELY appreciated. Thank you. On 2022-04-09 by LYNND

Reply by Inspectapedia Com Moderator

@LYNND,

What a remarkable, long, and painful Diagnostics Saga for your Carrier heat pump system.

You raise a number of diagnostic questions that are perfectly reasonable but I don't hear any more story that anyone has checked them. Even the question of the heat strips remains unclear from the narrative.

Give me the number of people who been to your site over such a long time I don't think we can be smarter just based on a text description.

A couple of remarque's might help get going on sorting this out.

It's common for a service tech to simply try replacing a simple part with the hope that that will fix the problem rather than going through a lengthy diagnostic routine, partly because it's the least expensive first thing to try. But certainly you don't want to keep replacing parts and certainly not replacing fuses nor over fusing equipment.

I would expect someone to use some test equipment like a DMM or vom to look at the current draw when the system is running.

Talk to the service manager and review the case history briefly and ask that she send an experienced senior service technician to sort out this problem. And ask the tech to review the repair history.

by LYNND

@Inspectapedia Com Moderator,

Thank you for the quick reply. My spouse is about to inspect the wiring for himself rather than take the word of the tech that nothing appears to be wrong with it.

We have only had two companies out since 2017, the first assigned to us by the home warranty company. (That HVAC provider seemed unfamiliar with Carrier and refused to check any electrical issues even though our reason for calling them out was for the high electric bills after closing on the house in summer 2017.

That service provider claimed the refrigerant was about ~3% low but in the time it took to go in the house to get my checkbook they claimed to have recharged it. They also claimed that the refrigerant being slightly low was NOT an indication of a leak because it wasn't low enough.

Needless to say I didn't have that company out again because I don't know if they actually put any refrigerant in the system or not. It took me less than five minutes to go get my checkbook and they said it was done. I never saw for myself what they did.)

Other service calls were associated with the prior owner but appeared to involve repeatedly replacing the thermostat. We only know that because there were so many receipts and tickets for installation.

We have had the same owner/operator tech out for all the calls involving the fuses (same guy who did our HVAC inspection). Prior to buying the house we also had a dedicated electrical inspection but none of these issues presented themselves up front.

It has been a learning curve to say the least. We see the meter come out and the owner-operator test for proper voltages but to our knowledge he hasn't used any specialty tools intended to isolate low voltage situations.

We can't continue to randomly pay to replace parts (with the markup) so it seemed fairly harmless to try replacing the board since the defrost boards aren't all that expensive. (We can always send it back if the tech actually rules it out when he shows up later today to revisit the recurrence of blown fuses.)

Overall, what do you think about my though process on the defrost board? If it were improperly going into defrost regardless of weather could that explain why the drop on the electric bill after re-running the wiring to the STAT has only fallen by about $100 from ~$900 during the summer.

Everything I have read on heat pumps suggests that the higher electrical cost should take place in winter, when the supplemental heat strips kick in, not summer — so the fact that our bills are highest in summer inferred (to me) that the heat strips were running. But I, too, was unclear on why the tech we had out — can't go any higher than him because he is the business owner — was not able to identify the wiring problem sooner.

Is it conceivable that a faulty defrost board would run up the electric bill by calling for defrost even in hot weather?

Thank you for suggestion the names of the tools. That was a big question — was our tech even showing up with the correct tools (other than an OHM meter) to properly isolate a short?

by Inspectapedia Com Moderator - Carrier heat pump system diagnostics

@LYNND,

Let's be sure we are not confusing the backup heat system, which in your case is probably electric, and which should only run in winter, with heater strips that might be used in the defrost cycle on the outdoor coil on a heat pump.

So the indoor coil may be defrosted at a different time and using different heaters from The Outdoor Equipment.

Bottom line is it sounds as if you need service from a Carrier-trained service technician.

Icing at the compressor; compressor not turning on?

The outside unit of the heat pump is icing up on the compressor.- Steve

My fan in my house goes on but my compressor unit does not all the electric seems to be fine . Could it be my thermostat? - Sam

the accu very heat,although it is new gen. clean,2Tr LS-60psi & HS-100psi, - Anon 8/6/11

Reply:

Steve: icing at the compressor/condenser sounds like a refrigerant charger or refrigerant metering problem.

Sam: if your thermostat turns on the air handler but the compressor/condenser does not run, the problem is not the thermostat.

Check out the diagnostic suggestiosn beginning at LOST COOLING CAPACITY

Anon: those pressures look kind of low, no?

What does your HVAC tech say about normal for that system?

 

My air conditioner compressor blew, the new system is icing up, what's going on?

I am a 100% service-connected disabled veteran who just spent over $3700. to replace a 4 ton trane xr12 air conditioner condenser and coil. My old condenser compressor blew up and the HVAC guy said it wasn't worth replacing since the unit was a 9 yr old r-22 system.

He talked me into a new trane xr13, 4 ton, r-410 condenser and a 5 ton evaporative coil for an extra $400. saying I'd get 10% more cooling capacity than the 4 ton coil. this was 5 weeks ago. three techs have been here since trying to figure out why the evaporative coil keeps icing up.

the best cooling we get with the thermostat set at 72 degrees is only 15 degrees cooler than it is outside.this is with the front panel off the furnace.

With the panel in place, in 2 or 3 days the coil turns into a block of ice. even with the panel off, as the day wears on and the outside temperature drops, the inside temperature increases. right now, the thermostat is at 72, it's10:15 p.m. it's 73 degrees outside and 76 degrees inside.

The HVAC guys tried to blame my ductwork as unable to handle the airflow, then inadequate air returns, then too small a hole (10x12) above the coil going to the plenum. all solutions of course would require a 2nd mortgage.

My response was . BULL. It's something they did wrong because before the compressor blew, if the outside temperature was 100 degrees, inside it was 78 degrees.(with the thermostat set at 72.

Not once in 9 years did it ice up or did I ever have to remove the front panel of the furnace to increase the airflow., It has to be one or both of the things they installed, like maybe a defective evaporator coil. Do you have any suggestions? Thanks - B.H.

Reply:

Cooling coil icing can be due to an improper refrigerant charge, inadequate air flow across the cooling coil, or a problem with a refrigerant metering device (or something else we haven't thought-of).

Your HVAC guys might be right that your old duct system is not moving enough air across the coil, allowing it to ice up, but if that's the problem I'd ask them why they didn't think of that before selling you that extra big evaporative coil in the air handler.

In a good-working air conditioner or heat pump system the components need to be in balance: compressor/condenser, air handler/evaporator, and ductwork.

If we hold off on the blame game for a bit, let's see if you can increase the airflow across the coil.

Often I find on older cooling systems that the return air opening was too small or the connections from return register to the air handler small or cramped or twisty.

A very crude "test" that I do NOT RECOMMEND for more than a few minutes of test operation is to see if the coil ices up if someone leaves the air handler blower compartment door off - to maximize the return air opening.

Take a look under DUCT SYSTEM DESIGN SIZE & DEFECTS for the article

RETURN AIR REGISTERS & DUCTS,

and also take a look at COOLING COIL or EVAPORATOR COIL

and at the article:

FROST BUILD-UP on AIR CONDITIONER COILS for more help.

Finally, at RETROFIT SIZING for A/C or HEAT PUMPS we touch on the importance of balancing the system components during a retrofit or upgrade of an air conditioner or heat pump system.

Let us know what you find - we'll both learn something.

 

There's Ice all over my outdoor and indoor air conditioner equipment: what do I do?

My Ac unit imdoors and outdoors is completey frozen what should I do besides turn unit off? - On 2018-05-20 by Sarah Derrington

I had outside Guardian AC installed to replace the old one, now it has frozen up twice. What could be the problem? - On 2018-06-19 by Dianna

Reply by (mod) -

Sarah: Call for repair. The problem may be something as simple as obstructed airflow through the outdoor unit but it also could be a problem with a refrigerant control valve or low refrigerant .

Dianna: Low refrigerant, or malfunctioning thermal static expansion valve or something else

 

Water at the base of the compressor

Is it normal for there to be water coming out of the base of my compressor? Anonymous

Reply:

Anon

Water at the outdoor compressor condenser is probably coming from melting ice or frost. If you see cycles of significant ice or frost build-up the refrigerant charge or metering may be incorrect and I'd ask for a check by an HVAC tech.

 

Trane A/C Condenser Unit Won't Defrost in Cold Weather

My trane air conditioner won't go into defrost mode while its cold outside. The coils freeze up and once I spray it with water then the defrost mode kicks in.. Any idea what's wrong? On 2016-01-24 by Megan

Reply by (mod) -

Megan it's possible that the heater band intended to be used for defrost is not working on the compressor. But low refrigerant can also cause coil icing.

 

Compressor Defrost Heater Failed: do I need to replace it?

My heater thingy to heat the oil in the compressor died. Is it necessary to replace it as I have one guy who says yes and another one says no. I have a Trane heat pump - On 2015-10-14 by Judy

Reply by (mod) -

IF your system is a heat pump then it is designed to operate in cold weather to produce heat as well as cooling in warm weather.

In that case if you permit the system to run in cold or freezing weather, and if your heater thingy is not working, liquid refrigerant can enter the compressor piston when the motor runsd. The result is a ruined compressor and a very expensive repair.

Yes your heater thingy needs to work.

 

Condenser Unit is not defrosting and ices up

I replaced my condenser fan motor this summer. Now that winter is here I noticed my unit is not defrosting as it should and ices up. Couple things I noted. The fan is running in the right direction.

The fan does shutdown when the condenser unit shuts down, The fan continues to run during the defrost cycle and I am not sure if this is correct. Should the fan be off on the defrost cycle? What would be the cause to it continuing to run? 2017-02-05 by Stewart

Reply:

Stewart,

Normally on a heat pump in winter in heating mode, indeed ice can form on the outdoor coil and will require defrosting, handled automatically - especially when outdoor temperatures are close to freezing.

You should observe the following if the system is working normally:

- inside the heat will stop, or will switch to backup heat mode; most units have a signal or indicator light indicating defrost cycle mode

- outside the fan stops and the compressor is running.

Details are at HEAT PUMP OUTDOOR UNIT DEFROST CYCLE

But the requirement to go through a defrost cycle depends on outdoor temperature and humidity. So your system may not need to be defrosting as often as you think. Articles I've read on this suggest that typically you won't see a defrost cycle more often than about every half hour or 35 minutes.

If the inside indicators are defrost mode then yes I think the fan should stop - there could be a control board or fan relay control problem or an outdoor temperature sensor failure.

Watch out: as a general note for other readers, don't turn off the system in the middle of a defrost cycle - let it complete the defrost cycle or you may damage the equipment when it's re-started.

Temperzone, a New Zealand company I admire, has a nice article on the defrost cycle - at http://www.temperzone.co.nz/FAQ/Understanding-Defrost-Cycle/

Defrost cycle not working on outside condenser

My outside condensing unit has been missing the defrost cycle recently. Now, it will go into defrost cycle but will not return back to normal operation. On 2012-11-28 by David -

Reply by (mod) -

David,
That sounds like a bad defrost cycle relay switch or a bad control board.

Lennox heat pump without a defrost cycle: stuck contactor.

I have a very old Lenox heat pump system. The "contractor" said it is 40 years old.

He mentions it needs a new Defrost Control Board (problem is the condenser fan always runs). I went snooping around the unit and could not find a board.

It appears to be a direct 220V connection too condenser unit; capacitors and simple contactor.

I found the contactor to be stuck.

I freed it up and all seems fine. I will replace contactor. Is it possible that this old lennox heat pump does not have a defrost control board or should I keep looking? Can it be in the air handler?? Thanks. On 2012-10-07 by Jim

Reply by (mod) -

Jim
Not every unit uses a defrost cycle. If we had the model and serial number we might be able to looknup the unit specs.

Ask your service tech to replace the bad contactor and you may be good to go.

Condenser Unit Fan Runs during Defrost Mode

My outside unit fan keeps running in defrost. This is a new 3-ton system. I am pretty sure that when it calls for defrost the outside fan should not be running. On 2022-03-22 by Gregg Nemec

by Inspectapedia Com Moderator - outdoor fan should stop during defrost mode

@Gregg Nemec,

Details on the condenser unit (outdoor unit) defrost cycle are above on this page;

Indeed on a heat pump unit in heating mode as frost may form on the outside coil, the unit will periodically switch to "cooling" mode to defrost the coil (cooling mode will cause the coil to warm up). In this mode the outdoor fan should stop - at least on all the units we've examined/read-about/etc.

But give the brand and model and let's confirm that with the manufacturer of your specific unit.

A/C temperature much cooler after our heat pump defrost cycle

I have a Carrier heat pump with hk32ea001 defrost board in Venice, FL. After a defrost cycle the air duct temperature is 10 degree F cooler than before and remains there for a long time.

I suspect the reversing valve may be leaking across. I would like to experiment with deleting the defrost cycle. Can I do this by not selecting a defrost interval on the board ie disconnecting the time select jumper wire? On 2021-11-29 by Marty

Reply by Inspectapedia Com Moderator

@Marty,

I don't know the jumpers on that control board, though doubtless they're detailed in the Carrier manual.

But I'm confused. Given that air temperature is lower after a defrost cycle, isn't that telling us that the defrost cycle is both normal and needed? Why would we want to turn it off, blocking our coil with ice?

Power outage may have caused defrost cycle control board damage

So had power outage that lasted about 40 hours. After power back on I turned heat back on. Now the outdoor unit sounds and acts like going into very quick 3-5second defrost cycles.

It will do this about 10 times quickly back to back then start running normal. I get the air brake sound and fan outside will stop during entire session of cycle. Even kind of sounds like air brake sound at indoor blower unit. On 2020-11-03 by Philip

by danjoefriedman (mod) -

Philip

It's possible that a power surge has damaged the control board

...





ADVERTISEMENT





...

Continue reading at HEAT PUMP OUTDOOR UNIT DEFROST CYCLE - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

COMPRESSOR / CONDENSER UNIT FROST & ICE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.