Water Pump & Water Tank Manuals
Download water pump & irrigation pump & pump control manuals as well as water storage tank manuals in free PDF format.
Here we list and provide download links for installation, operation, & repair guides for various types of water pumps, tanks & controls used on wells & irrigation systems or for water pressure boosting systems.
This article series describes how to diagnose and repair all types of well water pump problems and includes questions and answers from and to homeowners who lost well water pressure. We outline how to diagnose and fix bad water pressure (and link to articles in greater depth).
We describe tracing a water pressure problem to the pump pressure control switch or to a bad water pressure tank (and what to do about it).
And we list common water quantity (run out of water) or flow (pressure) problems and solutions Page top illustration of a water pump, tank, controls & water well is used with permission of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
ADVERTISEMENT
Water Tank, Pump & Irrigation Pump Installation, Operation, Repair Manuals, Contacts
Here are free PDF downloads and contact information for water pump, well pump, and irrigation pump manufacturers giving pump properties, selection guides, installation, operation, troubleshooting & repair guides.
These manuals by the pump manufacturers or suppliers are provided complete; we have compressed some large PDF files for faster loading - with no loss of image nor data quality.
Shown here: a series of Goulds residential water pumps. [Click to enlarge any image]
InspectAPedia is an independent publisher of building, environmental, and forensic inspection, diagnosis, and repair information provided free to the public - we have no business nor financial connection with any manufacturer or service provider discussed at our website. We do not sell products nor services.
Alphabetic Index to Water Pump & Water Tank Manuals by Brand
A - B - C - D - E - F - G - H - I - J - K - L - M - N - O - P - Q - R - S - T - U - V - W - X - Y - Z
Also see
- PRESSURE SWITCH INSTALLATION MANUALS [web article] for water pump & tank pressure controls
- WA DOH BLADDER PRESSURE TANK TROUBLESHOOTING GUIDE [PDF] Washington State Department of Health, retrieved 2021/12/02 original source: https://www.doh.wa.gov/portals/1/Documents/pubs/331-342.pdf
Excerpt:
- Check for waterlogged bladder pressure tank problems
- When the internal bladder fails and water fills the air
space around the bladder inside the tank, the tank is
waterlogged. You should replace waterlogged tanks.
- Gently tipping the tank may identify a waterlogged
tank by weight.
- The pump motor cycles on/off rapidly.
- Listen. When you tap on the outside of the tank, it
sounds different from those with a proper air-water
balance.
- When you depress the central pin of the air-charging
valve, water escapes through the charging valve.
- Stale, rusty water appears at the tap due to corrosion
inside the tank.
A
Access Water Energy - Australia
- Access Water Energy, PO Box 2061, Moorabbin, VIC 3189, Australia, Tel: 1300 797 758, Web: http://www.accesswater.com.au/ Email: sales@accesswater.com.au
Moorabbin Office: Kingston Trade Centre, 100 Cochranes Rd, Moorabbin, VIC 3189
Australian supplier of: Greywater systems, Solar power to grid packages, Edwards solar systems, Vulcan compact solar systems, water & solar system pumps & controls,
Also:
- Ace-In-A-Hole - see Simer on this page.
- AIR VOLUME CONTROL REPAIR
- AMT - see Gorman-Rupp Pumps - gas & electric operated water pumps
- AquaBoost - See Goulds Pumps - pump controller for municipal water systems
- AquaCharge - see King Pumps (obsolete)
- American Granby - water pump accessories & water system accessories such as air volume controls - AVCs
Alton Pumps, UK
- Alton Pumps Ltd Unit 4 Riverwey Industrial Park, Newman Lane, Four Marks, Alton GU34 2QL, UK Tel: 01420 561661 Website: https://www.altonpumps.comEmail: sales@altonpumps.com
Amtrol Pumps & Tanks
- Contact: AMTROL Inc. Corporate Office 1400 Division Road West Warwick, R.I. 02893 Phone: (401) 884-6300 Email: info@amtrol.com, Website: http://www.amtrol.com/, Amtrol RP-HP Pressureiser water pressure booster systems include a pressure boosting pump integrated with an Amtrol water pressure tank.
The system is designed to boost building water pressure 50-50 psi above the incoming municipal-supplied water. Amtrol has offices world wide including Canada, Central America, Europe, Puerto Rico, Mexico, South America, United States
- AMTROL PRICE BOOK 2022 [PDF] (2022) Current List Prices for Amtrol Products in the U.S.
- AMTROL WELL-X-TROL INSTALLATION & OPERATION MANUAL [PDF] Owners installation and operating instructions
- AMTROL WELLXTROL WELL TANK SPECIFICATIONS [PDF] WX-101 - WX-350 drawdown volumes and specification data
- AMTROL WELL-X-TROL DIAPHRAGHM WELL TANKS WX-100, 200, 300 Series [PDF] (2014)
- AMTROL WELL-X-TROL RESIDENTIAL WELL TANKS INSTALLATION & OPERATION MANUAL WX-101-WX-350 [PDF] (2019) Worthington Industries, 1400 Division Road, West Warwick, RI USA 02893
T: 800.426.8765 www.amtrol.com
Models WX-101 through WX-350
- AMTROL WELL-X-TROL TANK SIZING CHART [PDF] water pressure tank size selection guide
- AMTROLWELL-X-TROL WELL TANK SPECIFICATIONS [PDF] data submittal sheet from Amtrol
Diaphragm Well Tanks: WX-100, 200 and 300 Series, 150 PSIG Working Pressure
A.O. Smith Water Tanks: PermaTank Water Tanks, Trident Water Tanks
- Contact: A.O. Smith Water Systems (an A.O. Smith Company) provides a range of water pressure tanks under the PermaTank brand and the Trident brand. Water Systems, 4302 Raleigh St., Charlotte NC 28213, USA, Website: http://www.wstanks.com/ Technical Support Tel: 1-800-549-6233
- A.O. Smith DIAPHRAGM WELL TANK INSTALLATION MANUAL [PDF] (AOS Website) for vertical and in-line and horizontal series water tanks ranging in size from 2 to 119 gallons - local backup copy saveda as AOS-Well-Tank-IO-Manual.pdf
AOS Water-Systems - PermaTank Water Tank Manuals
- Contact Perma Tank,
500 Tennessee Waltz Parkway, Ashland City, TN 37015 USA, Tel: 1-800-365-4300 Email: info@permatank.com
- AO SMITH WATER SYSTEMS WATER TANK MANUAL [PDF] - Vertical Series:
14-20-25-32-36-52-65-86-96-119 gallon tanks, In-Line series 2-5-7 gallon tanks, & Horizontal series water tanks in 7-14 & 20 gallon size,
Watch out: This Well Tank is designed and intended for cold (ambient temperature) water storage at a maximum pressure of 100 PSIG or 125 PSIG depending on your tank model, any use other than with cold water, or at a sustained or instantaneous pressure in excess of 100 PSIG or 125 PSIG depending on your tank model is UNSAFE.
A pressure relief valve of adequate size must be incorporated in the system. The relief valve must be selected to pass the full capacity of the pump when the pressure in this tank is 100 PSIG or more. Consult pump manufacturer for pump capacity at relief pressure.
- AO SMITH DIAPHRAGM WELL TANK INSTALLATION MANUAL [PDF] (2018) 100305320 2000199921 (Rev. C) A. O. Smith, 500 Tennessee Waltz Parkway, Ashland City, TN 37015Phone: 1-800-527-1953www.hotwater.com retrieved 2020/10/20 original source: A.O. Smith at https://www.hotwater.com/Resources/Product-Literature/Instruction-Manuals/Tanks/
HORIZONTAL
SERIES:
7-14 & 20 GALLON
IN-LINE SERIES:
2-5 & 7 GALLON
VERTICAL SERIES:
14-20-32-36-52-65-86-96-119 GALLON
- AO SMITH PERMA TANK GLASS LINED & GALVANIZED PRESSURE TANK IO MANUAL [PDF] OM 184980 retrieved 2019/05/21 original source: http://www.wstanks.com/permatank/pdfs/184980-001.pdf
- AO SMITH PERMA TANK HEAVY DUTY GLASS LINED PUMP TANK IO MANUAL [PDF] (2014) retrieved 2019/05/21 original source: http://www.wstanks.com/permatank/pdfs/329091-000.pdf
AOS Water-Systems - Trident Water Tank Manuals
- Contact: Trident Water Tanks, a Water-Systems A.O. Smith company: Trident,
500 Tennessee Waltz Parkway, Ashland City, TN 37015 USA, Tel: 1-800-365-4300 Email: info@permatank.com
- AOS WATER SYSTEMS TRIDENT & TRIDENT ULTRA WATER TANK MANUAL [PDF] (2007) retrieved 2019/05/21 original source: http://www.wstanks.com/trident/pdfs/205778-001GenericStratfordManual.pdf
Aquatec Pumps
- Aquatec 8800 Series Booster Pumps, Aquatec International, 17422 Pullman St., Irvine CA 92614, Tel: 800-975-9995, Website: www.aquatec.com
Aurora Pumps
Aurora is a Pentair Brand
B
Berkeley Pumps
Berkley Jet Pumps are a Pentair Brand.
- Contact: Pentair Berkeley Tel: 1-888-237-5353 Website: https://www.pentair.com/en/brands/berkeley.html
Website Excerpt:
Since 1937, when Berkeley pumps were first used to irrigate the fertile fields of the San Joaquin Valley of Central California, up-through today's most challenging water transfer projects and residential water flow needs, the name Berkeley has stood for uncompromised quality and proven reliability.
As Berkeley has grown, so has its product line. Today Berkeley leads the industry with the most comprehensive product lines available in the industry.
- BERKLEY JET PUMP OWNERS MANUAL HORIZONTAL MULTI-STAGE JET PUMPS [PDF] (2009) Models 3/4HP - 7LT2, 1HP - 10LT2, 1 1/2HP - 15LT2
- See also PENTAIR PUMP & TANK MANUALS
Sim
When the water pump runs on at a pressure below the CUT OUT or high setting on the pressure control switch, then the problem is probably one of the ones shown above on this page:
WATER PUMP WONT STOP RUNNING
From your description of reduced flow it sounds as if your well has a reduced flow rate
OR the pump impeller is clogged or damaged,
OR (if later you find the system losing prime) then there is a leak in well piping somewhere or a bad foot valve
Pump is Berkley 5FN-L 0.5 hp 30-50psi and about 20 yrs old but I am not hearing any strange noises from it, I have a holding tank not a well, pump will will reach 32 psi but will not go higher, I changed the switch but still same issue
so I unplugged the pump, drain all water from system, plug in pump and seem to have a really strong initial surge of water then at 30psi the sound changes , I do have water so I am assuming it means I have prime?,
If I turn on a tap i am not getting sputtering water just a reduced flow as pump only goes to about 30psi
so I am thinking no air being sucked in, if I unplug the pump over night I still have about 30 psi of pressure next morning so I am assuming that means no leaks in piping and foot valve is good? May need cleaning? Thank you
Also
Blue Angel Pumps - sump, effluent, seweage, well & lawn pumps
Brady Products - Air volume controls, well screens, check valves, foot valves
Burks Pumps - end suction pumps & turbine pumps
BettaFlow Pumps
- Contact: National Pump Company, 7706 North 71st Ave., Glendale, AZ 85303, Tel: (800) 966-5240 Email: info@natlpump.com, website: http://www.nationalpumpcompany.com
- BETTA-FLO JET PUMP INSTALLATION MANUAL [PDF] retrieved anew 9/13/12, original source: http://www.nationalpumpcompany.com/pdf/Betta_Flo_IOM_Jet_Pump.pdf
British Pump Manufacturers Association
- BPMA, National Metalforming Centre , 47 Birmingham Road, West Bromwich B70 6PY UK Tel: 0121 601 6350, Email: enquiry@bpma.org.uk
BurCam Pumps
- Contact: BurCam, ; Bur-Cam Company, 2190 Boul, Dagenais West, Laval, Quebec, Canada H7L 5X9, Tel: 514-337-4415, Website: www.burcam.com, also sold through re-sellers such as Northern Tool, Sears, Walmart
- BURCAM SHALLOW WELL or BOOSTER PUMP MANUAL [PDF[ (2013)
Burcam Model 506532SS
dual application pressure booster pump can be used as a water pressure booster pump or as a shallow well single-line jet pump
C
Coming:
Charge N' Flow Portable pump kits
ChemFlo end suction centrifugal pumps - stainless steel
Conery float switches & pump basin accessories
Crane Pumps
D
Davey Pumps, Australia, New Zealand, USA, France
- Davey, Australia Tel: 1300 2 DAVEY or 1300 232 839 Website: davey.com.au
- Davey France Tel: +33 (0) 4 72 13 95 07 Website: daveyeurope.eu
- Davey New Zealand Tel: 800 654 333 or +64 9 570 9135 Website: daveynz.co.nz
- Davey International USA Tel: +61 3 9730 9121 Website: daveusa.com
Davey is Australia and New Zealand's international water products company. Davey Water Products designs, builds and sells products for transfer, conservation, treatment and filtration of water.
Dayton Pumps
- Dayton 4HFA8 booster Pumps sold through Grainger, Zoro, other retailer
Duro Pumps
Also
Drainosaur Water Removal Systems
E
EcoCirc Pumps
- ECOCIRC - B&G / XYLEM ECOCIRC XL PUMP INSTALLATION & OPERATION MANUAL [PDF] (2018) Xylem / Bell & Gossett - retrieved 2022/11/17 original source: https://www.nationalpumpsupply.com/content/pdf/bell-&-gossett-ecocirc-xl-installation-guide.pdf
Xylem Pumps: see contact information at Xylem on this page or contact Bell & Gossett
Excerpts: The ecocirc XL is a large wet rotor pump with energy efficient, electronically commutated permanent magnet motor.
The pump is designed for systems with variable flow rates to optimize pump operation thus reducing energy consumption.
The
pump can be set to any one of the multiple operating modes available, with each designed for a specific application to achieve high
performance and maximum energy savings
Pumps are offered in cast iron and stainless steel options to handle
HVAC and potable water applications respectively.
However, a single stainless steel body pump can handle heating, cooling and
plumbing applications if so desired.
The pumps are also suitable for
a 50/50 percent water/glycol circulating fluid. The built-in electrical
overload and dry run protection provide safety and protection from
damage.
EcoFlow Pumps & Tanks
F
Fairbanks Morse & Fairbanks Well Pumps, Manuals
- Contact: Pentair Fairbanks NIJHUIS 740 E. 9th St., Ashland OH 44805 USA, Tel: 1-888-416-9510
Fairbanks Morse is a Pentair brand
Flexcon Industries

Above, Flexcon's Flex-Lite well tank, described by the company as:
The Flex-Lite FL series' improved CAD2 diaphragm design is stronger and won't crease and wear out like bag designs. Flex-Lite well tanks features a chlorine resistant 100% butyl diaphragm with a precision molded copolymer polypropylene lower water chamber for superior air and water separation. - Flexcon cited below, 2021/08/06
- Contact: Flexcon Industries, 300 Pond St. Randolph MA 02368 USA Website: www.flexcon.com Tel: 1.781.986.2424 Email: request@flexconind.com
- Flexcon COMPOSITE WELL TANK INSTALLATION & OPERATING INSTRUCTIONS [PDF] (2018) retrieved 2021/08/06 original source: https://www.flexconind.com/flexcon%20composite%20well%20tanks%20iom%20lr%208-29-18.pdf
Excerpt:
This well tank has been designed to store and deliver
water under pressure between pump cycles in a domestic
water system.
It features a patented Controlled Action
Diaphragm (CAD2) system that completely contains the
system water in a safe NSF approved chamber. The CAD2
system prevents water from ever touching the internal walls
of the tank which greatly reduces external condensation.
- Flexcon, SMART TANK INSTALLATION INSTRUCTIONS [PDF], Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
Excerpt:
The Smart Tank pressure system provides constant pressure over a
broad range of flows, and the storage that every water system needs.
The unique
Smart Tee valve is connected to the Online tank with a union.
Every Smart Tank
system includes a relief valve and a manifold that provides ports for the system’s
pressure switch, pressure gauge, drain valve and relief valve.
This puts the controls
right where they belong - at the tank. The Smart Tee valve and Online tank have
been engineered to work together for optimum system performance.
- WELL RITE WATER TANK SPECIFICATIONS [PDF] - sizing chart for water tanks, Flexcon Industries
Flojak Pumps
Flojet Pumps

- Contact: ITT Industries, Flojet, offices in Canada, Germany, Italy, Japan, the United Kingdom and the U.S.
CANADA
Fluid Products Canada
55 Royal Road
Guelph, Ontario N1H 1T1
Tel: 519 821.1900
Fax: 519 821.2569
GERMANY
Jabsco GmbH
Oststrasse 28
22840 Norderstedt
Tel: +49-40-53 53 73 -0
Fax: +49-40-53 53 73 -11
ITALY
Jabsco Marine Italia
Via Tommaseo, 6
20059 Vimercate, Milano
Tel: +39 039 685 2323
Fax: +39 039 666 307
JAPAN
NHK Jabsco Company Ltd.
3-21-10, Shin-Yokohama
Kohoku-Ku, Yokohama, 222
Tel: 045.475.8906
Fax: 045.475.8908
UNITED KINGDOM
Flojet
Bingley Road, Hoddesdon
Hertfordshire EN11 OBU
Tel: +44 (0) 1992 450145
U.S.A.
Flojet
20 Icon
Foothill Ranch, CA 92610
Tel: 949.859.4945
Flojet Pumps include water pressure booster pumps, AC & DC pumps used in dispensing equipment. Small pumps. Flojet is an ITT brand.
- Flojet Quad II Water Pressure System 3 GPM 115V 30 PSI # 2840-000
- Flojet Pumps Quad II Water System 3 GPM 12VDC 30 PSI # 2840-100A 12V DC water pressure system
Flotec Pumps

Flotec is a Pentair Brand
...
Above and below: examples of Flotec pump wiring color codes and connections, excerpted from the manuals above.

Franklin Electric Water Pumps
- Contact: Franklin Electric 9255 Coverdale Road, Fort Wayne, IN 46809
Tel: 260.824.2900 Fax: 260.824.2909 Web:
www.franklinwater.com
Contact the Franklin Electric Hot Line for assistance at 800-348-2420.
- Franklin Electric AIM MANUAL SUBMERSIBLE MOTORS APPLICATION, INSTALLATION, MAINTENANCE [PDF] (2015) includes tables of maximum wire distances for pumps by size, horsepower, run length, etc.
- FRANKLIN ELECTRIC INLINE SYSTEM CONSTANT PRESSURE SYSTEM OWNERS MANUAL [PDF] retrieved 2018/10/30, original source: http://littlegiant.com/media/130617/225883101.pdf
- Franklin Electric FRANKLIN CONVERTIBLE VERSAJET PUMP INSTRUCTIONS [PDF] - retrieved 2022/09/05 original source: https://franklinwater.com/media/117272/106580101_Convertible_VersaJet_Series_Manual_07-13_WEB.pdf
- FRANKLIN ELECTRIC CONVERTIBLE VERSAJET PUMP DEEP WELL INJECTOR KIT INSTRUCTION SHEET [PDF] (2018) - retrieved 2022/09/05 original source: https://franklinwater.com/media/233646/cjv-deep-well-instruction-sheet.pdf
Excerpt:
This carton contains all the parts needed to assemble a deep well injector suitable for installation in
a 4” or larger well or cistern when the intent is to lift water 25’ or more from below the location of the
Convertible VersaJet pump. It is important to match the correct nozzle and venturi combination with
the pump rating to obtain the desired performance (flow and pressure) from the depth to water (suction lift).
A standard 147E injector kit includes one each of a specific nozzle and venturi size. The
CVJ-DW1-5 injector kit includes an assortment of nozzles and venturi so the injector can be set up
for the desired performance at a specific site. Refer to the pump catalog performance charts and the
nozzle/venturi chart below to complete the deep well injector kit assembly that is right for the performance desired.
- Franklin Electric 4" DEEP WELL SUBMERSIBLE PMPS INSTALLATION & OPERATING INSTRUCTIONS [PDF]
- Franklin Electric, 4" ENVIRONMENTAL E-SERIES PUMPS OWNERS MANUAL [PDF] Franklin Electric, 400 E. Spring St.,
Bluffton, IN 46714 USA
Tel: 260-824-2900 Web:
https://franklinwater.com/ retrieved 2021/06/25, original source: https://franklinwater.com/media/110586/106259101_E_Series_06-12_WEB.pdf
- Franklin Electric, PUMPTEC CONTROL BOX & PUMP PROTECTION DEVICE IO MANUAL [PDF] Franklin Electric, 400 E. Spring St.,
Bluffton, IN 46714 USA
Tel: 260-824-2900 Web:
www.franklin-electric.com
- Franklin Electric, PUMPTEC-PLUS PUMP CONTROL & PROTECTION SYSTEM INSTALLATION GUIDE [PDF] Franklin Electric, op. cit.,
- Franklin Electric PUMPTEC QD CONTROL BOX INSTALLATION MANUAL [PDF] Franklin Electric, op. cit., retrieved 2021/06/25, original source: https://franklinwater.com/media/180820/qd_pumptec_manual-225559101_m1551-.pdf
Fristam Pumps
Also:
Flint and Walling division of Zoeller Pumps also see King Pumps
Flomax Self priming centrifugal pumps - industrial, agricultural applications.
G
Global Water Solutions Pressure Tank Manuals
- Contact: Global Water Solutions, Website: https://www.globalwatersolutions.com/
- GLOBAL WATER SOLUTIONS WATER TANK WELL TANK INSTALLATION GUIDE [PDF] for Models PressureWave™ / Max™ / UltraMax™ / M-Inox™ / E-Wave™ / Challenger™ /
C2-Lite CAD™ / FlowThru™ / All-Weather™ / HeatWave™ / SolarWave™ /
ThermoWave™ Series
Excerpts:
These instructions have been prepared to acquaint you with the
correct method of installing and operating your GWS pressure
tank. ... In the event of installation diffi culties or
the need for further advice, you should contact the dealer from
whom you purchased the system or the nearest GWS sales office.
PressureWave™, Max™, UltraMax™, M-Inox™, E-Wave™,
All-Weather™, Challenger™, C2-Lite CAD™, and
FlowThru™ Series tanks are designed for use in well water or
potable water booster systems.
HeatWave™ and SolarWave™ Series tanks are designed
for use in non-potable closed loop hydronic or solar water
heating systems.
ThermoWave™ Series tanks are designed for use in open loop
potable water heating applications.
PressureWave™, E-Wave™,
Challenger™ and SuperFlow™ Series may also be used in
open loop potable water heating applications.
See tank data label for maximum working pressure and
maximum temperature.
Goulds Pump Manuals & Guides

- Contact: Goulds, ITT Water Technologies, Inc., ITT Industries, 240 Fall Street, Seneca Falls NY 13148 USA, Tel: 31`5-568-2811, Website: https://www.gouldspumps.com
More Goulds pump documentation including parts lists can be found at the company’s website: https://www.xylem.com/en-us/brands/goulds-water-technology/products/all-products/js-plus-jszplus/documentation/
Note: (2022) Goulds is now a Xylem Brand.
- GOULDS JET PUMP CATALOG [PDF] (2022) identify Goulds Shallow Well, Convertible, Deep wet, & Self-Priming jet pumps, including models JRS, JRS+, BFO34, J+, JRD, HJ, SJ, VJ, and GE. - Xylem, Retrieved 2022/12/23, original source: https://www.xylem.com/siteassets/brand/goulds-water-technology/resources/brochure/jet-pump-series-brochure-brjetseries.pdf
- GOULDS COMMERCIAL PUMP CATALOG [PDF] (2017)
- GOULDS 3196 PUMP MANUAL [PDF]
- GOULDS 3299 PUMP MANUAL [PDF]
- GOULDS GT Irrigator PUMP INFORMATION [PDF]
- GOULDS GT IRRIGATOR PUMP INSTALLATION & OPERATION MANUAL (Version 7) [PDF]
- GOULDS GT IRRIGATOR PUMP PARTS LIST [PDF]
- GOULDS WATER & IRRIGATION PUMP CATALOG [PDF]
- GOULDS GT IRRIGATOR PUMP INSTALLATION & OPERATION MANUAL (Version 6) [PDF]
- GOULDS JET PUMP INSTALLATION OPERATION & TROUBLESHOOTING MANUAL [PDF] (2022) IM102 Residential Water Pump Installation, Operation and Troubleshooting Manual - Xylem, retrieved 2022/12/22, original source: https://www.xylem.com/siteassets/brand/goulds-water-technology/resources/manual/im102-web.pdf
- GOULDS JET PUMP INSETALLATION OPERATION & TROUBLESHOOTING MANUAL [PDF] (2009) IM102 Residential Water Pump Installation, Operation and Troubleshooting Manual
- GOULDS JET PUMP & SUBMERSIBLE PUMP SERVICE MANUAL [PDF] (2022) Xylem - retrieved 2022/12/22, original. Source; https://www.xylem.com/siteassets/brand/goulds-water-technology/resources/manual/gsservice-web.pdf
- GOULDS, B&G BELL & GOSSETT, RED JACKET & CENTIPRO TECHNICAL MANUAL & DATA [PDF] (2021), Xylem Inc. 2881 East Bayard Street Ext., Suite A Seneca Falls, NY 13148 Phone: (866) 325-4210 Fax: (888) 322-5877 www.xylem.com- retrieved 2022/12/23, original source
https://www.xylem.com/siteassets/brand/goulds-water-technology/resources/manual/water-products-technical-manual--ttechwp-r4-2-21--web.pdf
- GOULDS PUMPS INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS [PDF]
- Goulds Pumps JET PUMPS INSTALLATION OPERATION TROUBLESHOOTING MANUAL [PDF]
- GOULDS PUMPS TECHNICAL MANUAL & DATA [PDF] (2005), ITT Water Technologies, Inc., TIECHWP, extensive technical information about the design and operation of various types of water handling pumps, includes pump fundamentals, electrical information, wiring diagrams, flow rates, definitions of terms, formulas, conversion charts, typical pump installations for various pump types (jet, submersible, high capacity, centrifugal booster, jet booster pumps, pipe volume & velocity, pump motor data, emerson motor wiring, pressure control switch wiring & adjustments, pump wiring diagrams, and special devices for low yield wells.
- GOULDS PUMP REASSEMBLY INSTRUCTIONS [PDF] given below and my source of 20-30 foot pounds was from www3.aps.anl.gov/APS_Engineering_Support_Division/Mechanical_Operations_and_Maintenance/Subsystems/ASD-ME-Group_files/data/RFWater/Maintenance/Pumps/GouldsPumpsReassembly.pdf
- WATER PRESSURE BOOSTER PUMP [article]
- WATER PUMP VARIABLE FREQUENCY / VARIABLE SPEED DRIVE (VFDs) [article]
Grove Electric Pump Manuals & Guides
- Contact: C&G Electric & Plumbing, 1900 NE 78th St., Ste. 101, Vancouver WA 98665 USA
- GROVE ELECTRIC JET PUMP MANUAL [PDF] (1989) information sheet showing installation layout, engineer-reviewed in 2007
- Grove Electric, TYPICAL SHALLOW WELL ONE LINE JET PUMP INSTALLATION [PDF], Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
This page has illustrations and description of a typical shallow well one line jet pump installation.
- Grove Electric, TYPICAL DEEP WELL TWO LINE JET PUMP INSTALLATION [PDF], Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
This page has illustrations and description of a typical two line jet pump installation for deep wells.
Gorman-Rupp Pumps
Grundfos Scala Water Pump Manuals, Features, Warranty - Bombas, Guias por SCALA2

Details about the Scala pump series including manuals, troubleshooting procedures, repairs, field failure reports, and company contact information are now found
at GRUNDFOS SCALA 2 PUMP GUIDE & MANUALS
H
Also:
Heller Aller Company, Napoleon, OH, produced deep-well windmills and handpumps, 1886 - 1995, purchased by Hitzer in 1995. Heller Aller hand pump still in production.
Honda - engine driven water pumps - agricultural & emergency use
Hydrotronic Controls - automatic operation of pressure boosting pumps & similar applications.
Hydromatic Pumps
Hydromatic Pumps is a Pentair Brand
- Contact: Pentair Hydromatic, Tel:
US: 1-888-957-8677
CA: 1-519-896-2163
Wastewater: 1-855-274-8947
See also PENTAIR PUMP & TANK MANUALS
Hydrovar Pumps
Hypro Pumps
HyproPumps is also a Pentair Brand
I
Also:
Irrigator pumps - see Gould Pumps
J
Also:
Jabsco Pumps: hand diaphragm bilge pumps - owned by Xylem
K
L
Lancaster Water Pumps
Liberty Pumps
- Contact: Liberty Pumps 7000 Apple Tree Avenue Bergen, New York 14416 USA: Phone 800-543-2550 Fax (585) 494-1839
www.libertypumps.com wastewater, groundwater removal, condensate pumps
Leader Submersible Pumps
- Leader Submersible Pumps - drainage applications, ponds, water fountains, &c. HQ in Italy, offices in the U.S. A number of Leader pumps we found are out of production - Ed. (9/2022)
Little Giant Pumps
- Little Giant Pumps - transfer, pool, condensate, aquariums, &c.
- Contact: Franklin Electric 9255 Coverdale Road, Fort Wayne, IN 46809
Tel: 260.824.2900 Fax: 260.824.2909
www.franklinwater.com
- LITTLE GIANT INLINE SYSTEM CONSTANT PRESSURE SYSTEM OWNERS MANUAL [PDF] link as above, retrieved 2018/10/30, original source: http://littlegiant.com/media/130617/225883101.pdf
Lowara Pumps

Illustration: Lowara 3HME07S Variable Speed Pressure System pump - Australian distributor
- Contact: Lowara, LOWARA S.r.l. Unipersonale
Via Lombardi 14
36075 Montecchio Maggiore - Vicenza - Italy
Tel.(+39) 0444 707111 - Fax(+39) 0444 492166
e-mail: lowara.mkt@xyleminc.com
web: www.lowara.com - www.completewatersystems.com
- Xylem: see contact details at Xylem
- Lowara 3HME07S Variable Speed Pressure System pump - and other models sold in Australia - https://justwaterpumps.com.au/lowara-3hme07s-variable-speed-pressure-system/
- LOWARA GVF11-GVF12-GVF13 VARIABLE SPEED BOOSTER PUMPS IO MANUAL [PDF] Xylem, - retrieved 2022/11/17, original source: https://www.wdapompen.nl/Xylem_Lowara_GVF_drukverhogingset.pdf
Excerpt: Lowara GV series booster sets are designed to transfer and increase the pressure of water, in the following applications:
• Hospitals
• Schools
• Public buildings
• Industries
• Hotels
• Condominiums
• Sports facilities
• Mains water systems
GV series booster sets are pumping stations assembled with two up to a maximum of six vertical multistage
pumps from the e-SV series.
The pumps are connected to one another by suction and delivery pipes, and fixed onto a single base.
The pumps
are connected to the manifolds by means of stop valves and check valves.
An electric protection and control panel is installed using a bracket on the base of the set.
In the case of
particularly large electric panels, they are installed on the floor.
- LOWARA UK VARIABLE SPEED BOOSTER PUMP SETS [PDF] Xylemc - retrieved 2022/11/17, original source: https://www.completepumpsupplies.co.uk/pub/media/bss/productattachment/lowaraboostersetbrochure.pdf
- LOWARA E-RANGE PUMPS, MOTORS, DRIVES CATALOG [PDF] Xylem - retrieved 2022/11/17, original source: https://www.wingleehardware.com/PDF/Lowara/CatalogueLowaraERange.pdf
- LOWARA SMART PUMP RANGE IO MANUAL [PDF] (2017) Xylem - retrieved 2022/11/17, original source: https://guradis.lt/wp-content/uploads/2018/05/844_001080136EN_B_05_2017.pdf
- LOWARA SMART PUMP RANGE INSTALLATION & OPERATION MANUAL [PDF] Lowara - Xylem - retrieved 2022/11/17, original source: https://brownbros.com.au/files/Operating_Manuals/MANUAL_Lowara_E-SM_0218_BBE_0820.pdf
- LOWARA SMART PUMP RANGE Additional INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS [PDF] (2018) Xylem, Web: www.xylem.com - retrieved 2022/11/17, original source: https://www.xylem.com/siteassets/brand/lowara/resources/manual/001080138en_d_04_2020_smart_pump_range.pdf
M
Matercalf Pumps

Matercraft one line jet pump shown above [citation needed]
McDonald Pumps
- Contact: A.Y. McDonald Mfg. Co
4800 Chavenelle Road
Dubuque, IA 52002
USA, Tel: 563.583.7311
800.292.2737 , 800.292.2737 FAX 800.832.9296 Email: sales@aymcdonald.com Web: aymcdonald.com
- McDonald Pumps, WATER & WELL PUMP BASICS [PDF] (2019), retrieved 2022/09/05, original source: https://www.rcworst.com/Shared/content/mfr/a_y_mcdonald_mfg_co/docs/a_y_mcdonald_pump_basics.pdf
pump catalog and pump explanation, theory, installation specifications, wiring, etc. - very helpful manual
How a centrifugal pump works
Which pump do I need (jet, submersible &c)
Typical jet pump installation
Submersible Pump installation
Pump performance curves - dynamic head vs. gpm delivered
Pump sizing guide
Water piping friction loss charts
Water pressure tank sizing guide
- McDonald 1000 Series VERTICAL MULTI-STATE PUMP INSTALLATION INSTRUCTIONS [PDF] - retrieved 2023/07/04, original source: aymcdonald.com/files/shares/3210-153_8-11_.pdf
Myers Pumps
Myers Pumps is now a Pentair Brand
- Contact: Pentair Myers Pumps, Tel:
US: 1-888-987-8677
CA: 1-800-387-4386
Wastewater: 1-855-274-8948
Aplex/Industrial: 1-888-416-9513
- Contact: (older) F.E. Myers, 1101 Myers Parkway, Ashland OH 44805-1969 USA Tel: 419-929-1144 Web: www.femyers.com
- Myers JET PUMP MANUAL QD-SERIES JET PUMPS [PDF]
See also PENTAIR PUMP & TANK MANUALS
Also:
MP Pumps: end suction centrifugal pumps - founded 1884, now a subsidiary of Techumseh Products Co. (since 1975)
MTH Pumps - commercial, industrial pumps
N
National Pump Company
- Contact: National Pump Company, LLC., National Pump Company Headquarters, 7706 N. 71st Avenue, Glendale, AZ 85303-1703 USA, Tel: (623) 979-3560 Website: https://www.nationalpumpcompany.com/
National Pum Company is a Gorman-Rupp company,.,
- BETTA-FLO JET PUMP INSTALLATION MANUAL [PDF] National Pump Company, 7706 North 71st Ave., Glendale, AZ 85303, Tel: (800) 966-5240 Email: info@natlpump.com, website: http://www.nationalpumpcompany.com, retrieved anew 9/13/12, original source: http://www.nationalpumpcompany.com/pdf/Betta_Flo_IOM_Jet_Pump.php
- National JET PUMP INSTALLATION MANUAL - Shallow Well Jet Pumps [PDF] (2016) - includes an excellent shallow well pump troubleshooting guide
- NATIONAL PUMP JET PUMP INSTALLATION MANUAL [PDF] and troubleshooting guide
O
Also:
Oasis Pumps: shallow well hand pumps, pitcher pumps
Oberdorfer Pumps, subsidiary of Thomas Industries, gear & belt driven pumps, industrial, automotaive
P
Pearl Submersible Well Pumps
- Contact: Pearl Submersible Well Pumps, 3000 W. 16 Ave., Miami Fl 333012 USA Tel: 954-474-9090,
- PEARL SUBMERSIBLE PUMP CATALOG [PDF] in English & Spanish
Also:
Pacer Pumps: gasoline engine driven pumps
Pony Pumps - see Little Giant Pumps
Pedrollo Water Pumps

- Contact: Pedrollo Electric Water Pumps, P.O.Box 52535, Moore Road, KZN. South Africa. 4083 Tel:+27 (0)82 651 984 Website: https://www.pedrollopumps.com/ email support@pedrollopumps.com
- PEDROLLO PUMP MANUAL [PDF] for Pedrollo water pumps
- PEDROLLO FLUX ELECTRONIC FLOW CONTROL SWITCH [PDF] used by Pedrollo water pumps & others
Pentair Water Tanks & Pumps & Pentair Manuals
- Pentair water system equipment including pumps & tanks and company contact information for Pentair and related brands is now found
at PENTAIR PUMP & TANK MANUALS
- See also STA RITE PUMPS at S
- See also WELLMATE WATER TANKS at W
Pentek Pumps
Pentek is a Pentair brand.
PermaTank water tanks
- See A.O. Smith - Water Systems Tanks at A
Pumping Solutions UK
- Pumping Solutions (UK) Ltd10 The ParkwaySpaldingLincolnshirePE11 3EE UK, Tel: 01775 711960 Website: http://www.pumpingsolutions.co.uk/
Q
R
Red Lion Pumps

Photo: convertible jet pump: Red Lion RJC-100
- Contact:
Red Lion pump company in the U.S. or Canada at:
RedLion Pumps, USA,
301 N MacArthur Blvd.
Oklahoma City, OK 73127-6616 USA
Red Lion Pumps Canada,
Sales and Marketing:
Suite 101 - 310 De Baets St. Winnipeg, MB R2J 0H4 Canada
Red Lion Pumps Canada, Customer Relations:
61 Parr Blvd, Unit 1
Bolton, ON L7E 4E3 Tel: t 888.956.0000
Red Lion Pump Co. Email:
USAcustomerservice@lgpc.com or
Canadacustomerservice@lgpc.com
Red Lion, itself a company dating from 1935, has recently picked up the Little Giant pump brand that we've used for decades.
- RED LION 1-2-3 EASY GUIDE to PUMP & TANK SELECTION [PDF] - retrieved 2022/09/05 original source: https://redlionproducts.com/media/33881/996245_rl-pump-and-tank-selection-guide_web.pdf
- Red Lion PUMP SPECIALIST TRAINING MANUAL [PDF] retrieved 2019/01/30 original source: http://redlionproducts.com/media/68986/995634_rl_training_manual-1-.pdf
RPS Solar Pumps
- Contact: RPS Solar Pumps, 40250 County Rd 27, Woodland CA 95776 USA, Tel: 888-637-4493 Web: https://www.rpssolarpumps.com/
We found it impossible to actually find information, pump specifications, etc. at this website but the company does offer an online solar pump sizing & pricing guide. - Ed. 2022/09/05
Also:
RainPerfect pump & solar panel for rain barrel water distribution. RainBarrell is an ITT company
Ranger 4" high-flow submersible well pumps are produced by Myer Pumps -see Myers.
Rule Pumps - submersible or 120V manual or automatic bilge pumps
Rustler 4" submersible well pumps are also produced by Myer PUmps - See Myers on this page.
S
Sears / Sears & Roebuck / Craftsman Jet Pumps
These Sears well pumps are in order by model number; note that some but not all can be converted between 2-line deep well service adn 1-line shallow-well service.
Shakti Pumps, India
- M/s Shakti Pumps India Ltd., 35 /1717-A, South Janatha Road, Palarivattom, Kochi, Kerala 682025, India
- Shakti: Plot No. 401 & 402, Sector 3, Industrial Area, Pithampur, Madhya Pradesh 454774, India
- Shakti Pumps Bangaluru
Water Pump Supplier
No. 107/2, 1st Floor, Shahazad Building Kumabaragundi Road, 4th Cross N.R. Road, Bengaluru, Karnataka 560002, India
- Shakti Pumps Shop No. C- 303, 304 & 305, Second Floor, Megacentre, Hadapsar, Pune, Maharashtra 411028, India
- Shakti Pumps Pune Shop No. C- 303, 304 & 305, Second Floor, Megacentre, Hadapsar, Pune, Maharashtra 411028, India
- Shakti Afridev deep well hand pump - 23/8/2 Badli Station Road, Sameypur Badli, Delhi, 110042, India
- Shakti Pumps India, S No 123,Aashirwad Complex,Opp Vivekananda Statue,Asian Highway 43, Ragavendra Nagar Colony, Medchal, Secunderabad, Telangana 501401, India
Shimge Pumps, China
- SHIMGE WATER PUMP MANUAL [PDF] Models: SQm、QB、WZB、AWZB、PW
- Shimge Pump Industry Group, Ltd., ref. 2020/02/02 original source: https://www.cn-shimge.com/upload/179/20190215095807801299.pdf
ShurFlo Pumps
Shurflo is a Pentair Brand
Shurwood Pumps
Shurwood is also a Pentair brand
Simer Pumps
Simer is also a Pentair brand
- Simer Water Pressure Booster Pumps, Simer Pump
293 Wright Street
Delavan, WI 53115, Tel: (800)468-7867, Website: http://www.simerpumps.com/
- Also see PENTAIR PUMP & TANK MANUALS
Speroni Electric Jet Pumps
- Contact: Speroni Water Pumps, S.p.a., I-42024 Castelnovo Di Sotto (RE) Via San Biagio, 59/A - 42024 Castelnovo di Sotto (Reggio Emilia) ITALY Web: https://www.speroni.it/ E-mail: speroni@speroni.it Phone: 0522 487011 (+39) 0522 487011
- CAM - APM JET PUMP INSTRUCTION MANUAL [PDF] (2016) Speroni, Italy, for this electric self-priming jet pump.
Square D Pump Controls
- Contact: Schneider Electric Square D® Brand Pumptrol® Pressure Control Switches, residential, commercial, industrial, Square D Company, Schneider Electric - North American Operating Division, 1415 S. Foselle Road, Palantine IL 60067, Tel: 847-397-2600
- SQUARE D COMMERCIAL PRESSURE SWITCHES [PDF] (2007)
- SQUARE D PUMP CONTROL CATALOG [PDF]
- SQUARE D Pump Controls PRESSURE CONTROL SWITCH MANUAL [PDF]
- SQUARE D 9013 SERIES PRESSURE SWITCH [PDF] (2008)
- SQUARE D 9013 SERIES F G PRESSURE SWITCH [PDF] (2007)
- SQUARE D PUMP SWITCH MAINTENANCE [PDF] Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches, Square D, Schneider Electric USA 8001 Knightdale Boulevard Knightdale, NC 27545 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com (2007)
- SQUARE D PRESSURE SWITCH TROUBLESHOOTING GUIDE [PDF]
Also see
Star Water Systems Pumps
- Star Water Systems, STAR VERTICAL JET PUMPS INSTALLATION & OPERATION & PARTS MANUAL (2013), Star Water Systems, 95 North Oak St., Kendalville IN 46755 USA, Website: https://www.starwatersystems.com retrieved 2019/01/30 original source: https://www.starwatersystems.com/content/literature/service/135258-FW0636-Vertical-Jet-Pump-Instr.pdf
Sta-Rite Industries Jet Pumps
Sta-Rite Industries Jet Pumps, are a Pentair brand.

Illustration: The Sta-Rite SLE-L Series Pro-Jet Convertible Jet Pump capable of providing water from either a shallow or a deep well depending on how the pump is set-up and which front-end is used.
[Click to enlarge any image]
- Contact: Pentair Sta-Rite, 293 Wright St., Delavan WI 53115 USA, Website: www.pentair.com Tel: 888-782-7483
Website excerpt:
The ProJet SN Series 1/2 through 1 1/2 HP shallow well jet pump provides excellent performance with strong pressure for wells to 25 ft. deep.
- Pentair STA-RITE CONVERTIBLE DEEP WELL JET PUMP OWNER'S MANUAL [PDF] “SL” Series / Série “SL” / Serie “SL”
“HL” Series / Série “HL” / Serie “HL”
- Sta-Rite D-Series CENTRIFUGAL PUMPS INSTALLATION, OPERATION, PARTS [PDF] Self-Priming Sta-Rite Pump Manual from Pentair (2013)
- STA-RITE PD2 SERIES CENTRIFUGAL PUMP IO MANUAL [PDF] Models PD2HD-L, PD2HE-L, PD3HF-L, PDHG-L, PDHHG-L, PDSSHFT pumps (1998)
- Sta-Rite PRO SHALLOW WELL JET PUMPS MANUAL [PDF] (2022) Pentair Berkeley Myers Sta-Rite Pro Shallow Well Jet Pumps
- Sta-Rite PENTAIR BERKELEY, MYERS, STA-RITE PRO CONVERTIBLE JET PUMPS MANUAL [PDF] Models: STA-RITE SL, HL, FL, HMS, PL, MS,
MYERS HR, HJ, MVPH
BERKELEY SL, HL, LT2, MS
- Pentair STA-RITE® SHALLOW WELL JET PUMP OWNER'S MANUAL [PDF] (2012) Installation/Operation/Parts / Installation/Fonctionnement/
Pièces / Instalación/Operación/Piezas retrieved 2020/05/28 original source: https://www.pentair.com/content/dam/extranet/flow/sta-rite/1119.pdf
- Sta-Rite SIGNATURE 2000 BOOSTER PUMP MANUAL [PDF] Signature 2000 1/2 - 3 hp (2007)
- Sta-RITE S.T.E.P. PLUS D Series SUBMERSIBLE PUMP MANUAL [PDF] (2004) Models: 10DOM05121, 10DOM05221,
20DOM05121, 20DOM05221, 20DOM05221+1,
20DOM05121+1, 30DOM05121, 30DOM05221
- Sta-Rite SUPERMAX VS Variable Speed Pump INSTALLATION & USERS GUIDE [PDF] (2014)
- STA-RITE SSJ-SERIES VERTICAL JET PUMP INSTRUCTION MANUAL [PDF] S724-series jet pumps (2013, revised 2015)
- Sta-Rite SUBMERSIBLE PUMP INSTALLATION & SERVICE MANUAL [PDF] (1988) for pumps manufactured after 1 January 1972, Sta-Rite Industries, Wicor Co., Delavan Wisconsin
- SuperMax is a commercial-grade swimming pool pump produced by Sta-Rite Pumps.
- Also see PENTAIR PUMP & TANK MANUALS
Carlos
It sounds like you're discussing the circumstance that we're attempting to diagnose and repair with the advice above on this page.
The SNE-L- shown right here - is a Sta-Rite Shallow-well Jet Pump produced by St-Rite Industries and, depending on water lift height, is capable of delivering a maximum of 13.7 gpm. The factory pressure switch settings are 30/50, that is CUT-IN at 30 psi and CUT-OUT at 50 psi.
Illustration: Sta-Rite shallow-well jet pump.
The SLE-L also above with our list of manuals is a different pump: the SLE is a convertible pump that can be set-up to pump from either a shallow well or a deep well. the deep-well version will use a two-line jet pump design.
The shallow well SNE-pump is used with shallow water sources up to 25 ft. of lift, such as driven point wells, shallow drilled or dug wells, or surface water sources. This pump can be used also as an in-house pressure-booster pump.
Please first check for something obvious like a leak or a debris-clogged pump impeller,
then take a look through the common causes of a pump that is unable to reach the cut-off pressure found
at WATER PUMP WONT STOP RUNNING
Let me know what you think and we will take it from there.
Pentair's Sta-Rite jet pump capacity in gallons per minute or liters per minute varies per feet of head (the total vertical lift the pump must handle) as shown in the chart below, courtesy of Pentair cited above. The SXX lines on the chart are for various Pentair Sta-Rite Pump models.

Really? This chart is confusing in that a typical shallow well 1 line jet pump can not lift water more than about 25 ft. See the Pentair Sta-Rite manual above for details.
Pump is an SNE L 1hp. Well is 130 ft. Never had this problem. Pump won't shut off at cut off setting.
Pressure from running pump does not exceed 43 psi. New pump, new pressure switch set at 30/50.
Tank at 28 psi. Replaced pvc from well head all the way to pump. Did not replace check valve near well head because I tested pressurized system for 4 days and the pressure held. At wits end. Help.
Strataflo Products, Inc.
- Contact: Strataflo Products Inc., 2010 Lakeview Drive
Fort Wayne, IN 46808 USA Tel: 260-482-4366
Fax: 260-482-3340
Email: sales@strataflo.com Web: https://strataflo.com
Strataflo produces foot valves & check valves used in wells, from 3/4" to 3".
Symcom Pump Saver Controls
- Contact: PumpSaver & SymCom, 2880 North Plaza Dr., Rapid City SD 57702 USA Tel: 800-843-5580 Website: www.symcom.com - Note: this website auto-forwards to https://www.littelfuse.com/ who have offices world wide and where you will drown trying to find help for your pump controller.
See also
LittleFuse, Corporate Headquarters,
8755 West Higgins Road, Suite 500,
Chicago, Illinois 60631
United States
+1 773-628-1000
- Contact Xylem - see Xylem on this page. Symcom is a Xylem brand
PumpSaver SymCom Accessories and manuals - we include all available revisions and manuals so that you can find the exact match for your specific PumpSaver control:
- OPERATING INSTRUCTIONS FOR SYMCOM’S
INFORMER
DIAGNOSTIC TOOL [PDF] PumpSaver Instructions
- PUMPSAVER PLUS INSTALLATION INSTRUCTIONS SYNCOM MODEL 231-P-INSIDER [PDF]
- PUMPSAVER PLUS INSTALLATION INSTRUCTIONS MODEL 233-P (2009 REVISION B1) [PDF]
- PUMPSAVER PLUS INSTALLATION INSTRUCTIONS MODEL 233-P (2009 REVISION A1) [PDF]
- PUMPSAVER PLUS INSTALLATION INSTRUCTIONS MODEL 233-P 233-1.5-P (2008 REVISION B) [PDF]
- PUMPSAVER PLUS INSTALLATION INSTRUCTIONS SYNCOM MODEL 233-P [PDF] (older models prior to 2009)
Excerpt:
SymCom PumpSaver®
Plus Model 233-P protects 230V, 2 or 3-wire, 1/3 – 3hp, single-phase pumps
from dry-well, dead-head, rapid-cycle, jammed-impeller, overvoltage and undervoltage conditions.
- PUMPSAVER ®
PLUS INSIDERS PUMPSAVER® PLUS 111, 233 AND 235 777KWHP – 3 PHASE TECHNICAL DATA [PDF] from Xylem, Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Phone: (866) 325-4210
Fax: (888) 322-5877
www.xyleminc.com/brands/centripro
- PUMPSAVER PLUS MODEL 235P INSTALLATION INSTRUCTIONS (2009) [PDF
- SYNCOM PUMPSAVER PLUS ENCLOSURE MOUNTING INSTRUCTIONS [PDF]
Also:
SuperMax is a commercial-grade swimming pool pump produced by Sta-Rite Pumps. - see Sta-Rite on this page
SuperBrute is a Grundfos circulating pump - see Grundfos on this page
T
Temco Water Pumps
Treadle Pumps
- TREADLE PUMPS, how treadle pumps work [PDF] Treadle pumps for irrigation in Africa
Excerpt:
A treadle pump comprises a cylinder fitted with a
piston and some means of pushing the piston up and
down (Figure 1). A pipe connects the pump to the
water source and at the end of this pipe is a nonreturn
valve that allows water to enter the pipe and
stops it from flowing back into the source.
The piston
and the cylinder must have a very close fit, so that
when the piston is raised, it creates a vacuum in the
cylinder and water is sucked into the pump.
When
the piston is pushed down, the water is pushed
through a small valve in the piston to fill up the space
above it.
When the piston is raised again, it lifts this
water until it pours out over the rim of the cylinder
and into an irrigation channel or tank.
At the same
time, more water is drawn into the space below the
piston. The downward stroke of the piston once again
pushes water through the small valve into the space
above the piston and the process is repeated.
Trident Water Tanks
- See A.O. Smith - Water Systems Tanks at A
TP Pumps UK
- TP Pumps, Pathfields Business Park, South Molton, North Devon EX36 3LH UK Tel: 01769 579487
TQ Pumps
- TQ Booster Pumps, Walrus Corporation, e.g. TQ400, TQ800, or TQ1500 electronic control water pressure boosting pump
Tsurumi Pump Co.
- Contact: Tsurumi Pump, Tsurumi Worldwide
Osaka Headquarters
16-40, 4-chome, Tsurumi,
Tsurumi-ku, Osaka 538-8585,
Japan
Phone: 81-6-6911-2351
Fax: 81-6-6911-1800
Offices in the U.S., Canada, Latin America & Worldwide. Tel: 888-TSURUMI (878-7864) Web: https://www.tsurumipump.com/
Tsurumi America
1625 Fullerton Court
Glendale Heights, IL 60139
tel: 630-793-0127
fax: 630-793-0146
toll free: 888-TSURUMI (878-7864)
info@tsurumipump.com
Tsurumi Canada
149 J.A. Bombardier
Suites 9-10
Boucherville, Québec
Canada, J4B 8P1
Tel : 450-449-6484
Fax : 888-449-5283
Toll free : 866-449-6484
info@tsurumicanada.com
Tsurumi Latin America
1625 Fullerton Court
Glendale Heights, IL 60139
Tel: (630) 793-0127
Fax: (630) 793-0146
Toll Free: 888-TSURUMI (878-7864)
info@tsurumipump.com
Products include water feature pumps, wastewater pumps, maintenance pumps
TT Pumps Ltd. UK
- T-T Pumps Ltd
Head Office
Onneley Works
Newcastle Road
Woore
CW3 9RU
England UK Tel: 01630 647 200 Website: https://www.ttpumps.com
Coming:
Topp
U
- Unitra SHALLOW WELL JET PUMP IO MANUAL [PDF] Unitra, Inc., Website: https://www.unitrainc.com/
Excerpt: Tanks without air seal for pre-charging will require an AIR VOLUME CONTROL
mounted on tank and connected to ¼” pipe tap marked A.V.C. on the pump casing
V
Valco Pumps
W
Water Ace Pump Company Manuals
- Contact: Water Ace Pump Company, 1101 Myers Parkway, Ashland OH 44805 USA, Tel: 1-800-942-3343 Web: http://www.waterace.com/
Consumer hotline: 800-942-3343 - instructions for the installation and maintenance of
Water Ace shallow well pump Model R510 1/2 HP
Water Ace deep well pump Model R100 convertible 1HP and
Water Ace deep well jet pump Model R250 convertible 1/2 hp.
Quoting from the company's website:
The Water Ace Pump Company... offer a complete line of sump, sewage, lawn sprinkler, swimming pool, submersible well and jet pumps as well as pressure tanks and accessories.
- WATER ACE JET PUMPS Model R510, R100, R520 INSTALLATION MANUAL [PDF] (1999) 1/2 hp and 1 hp pump and convertible water pumps, shallow well (one line jet pump) and deep well (two line jet pump)
- WATER ACE JET PUMPS Model RTS5, RTS7, RTS10 RC10 RC5 INSTALLATION MANUAL [PDF] (1999) Water Ace Pump Co., web search 08/28/2010, original source: http://www.waterace.com/pdf/RTS5%20RTS7%20RTS10%20RC5%20and%20RC10%20Jet%20Pumps%20Manual.pdf
- WATER ACE SUBMERSIBLE WELL PUMP INSTALLATION MANUAL - Water Ace Pump Co., web search 08/28/2010, original source: http://www.waterace.com/pdf/23833A019%20Well%20Pumps%20Eng.pdf
2-wire pump models R200 series & 3-wire pump models R300 series.
Spanish and French language submersible well pump installation manuals are available from the company.
Water Group Pumps & Manuals
- Contact: WaterGroup Inc.
Fridley, MN Rancho Cucamonga, 1-800-354-7867
Web: www.watergroup.com
WaterGroup Companies Inc. Regina, SK / CA Cambridge, ON 1-877-299-5999
- WaterGroup DUAL JET CONVERTIBLE JET PUMPS OPERATING & INSTALLATION INSTRUCTIONS [PDF] Models DCJ500 (#6330) & DCJ750 (#6331)
Excerpt: This pump is designed for shallow well installation for water level up to 25 feet, with injector installed on pump body; or for
deep well installation for water level up to 80 feet, with 1-1/4” pipes and injector down in the well.
Water Systems Well Tank Manuals
- Contact: WaterWorker C.., 1400 Division Road, West Warwick, RI 02893 • Tel.: 401.884.6300 • Fax: 401.885.2567 • www.waterworkerdiy.com
Additional IO Manuals for WaterWorker equipment & tanks including boiler expansion tanks, water heater expansion tanks, digital pressure control are provided by the company at http://waterworkerdiy.com/installation_manuals.html
- WATERWORKER INSTALLATION MANUAL FOR VERTICAL WELL SYSTEM TANKS [PDF] Models HT14B, HT20B, HT30B, HT32B, HT44B, HT62B, HT86B and HT119B[PDF]
Manual De Instalación Para Los Tanques Verticales Del Sistema De Pozo
Excerpt: The Water Worker 32 Gal. Pressurized Well Tank is constructed of deep-drawn steel and features stainless-steel waterway lining for durability. The tank's steel shell supports the water weight to ensure water never sits in loose-fitting vinyl or rubber bags that can fold, crease and wear. A polypropylene liner separates the water from the steel shell to help prevent taste or odor from being absorbed into the water.
- WATERWORKER HORIZONAL WELL TANK INSTALLATION MANUAL [PDF] Models HT6HB, HT14HB and HT20HB
- WATERWORKER IN-LINE WELL TANK INSTALLATION MANUAL [PDF] Models HT2B, HT4B and HT8B
- WATERWORKER WATER PRESSURE BOOSTER SYSTEM INSTALLATION MANUAL [PDF]
WaterSystems Well System Tank Manuals
WellMate pumps & WellMate Water Tanks / Well Tanks
Wellmate is a Pentair brand
Well Rite
Well X Trol tanks
Wessels Co. Water Tank & Tank Bladders - Westank
- Contact: Wessels Co., 101 Tank St., Greenwood IN 46163 USA TEl: 317 888 9800 Website: www.westank.com
- WESSELS FXA TANK BLADDER REPLACEMENT INSTRUCTIONS [PDF] Model FXA 1000 - 15,000 - how to replace a bad, leaky or perforated water pressure tank internal bladder
White International
- WHITE AUTOMATIC RESTART PUMP CONTROLLERS [PDF] WHI-SK10PPHS2 WHI-SK20PPHS2, WHI-SK10AXHS2
- Australia Contact: WHITE INTERNATIONAL PTY LTD 52-60 Ashford Ave Milperra NSW 2214 PO Box 304 Milperra LPO NSW 2214 Phone 02 9783 6000 Fax 02 9783 6001 Customer Service Hotline 1300 783 601 Email Sales: sales@whiteint.com.au General info: info@whiteint.com.au www.whiteint.com.au
- New Zealand Contact: WHITE INTERNATIONAL NZ LTD 15G Kerwyn Avenue, East Tamaki, Auckland 2013, New Zealand Phone 09 579 9777 Fax 09 579 7775 Customer Service Hotline 0800 509 506 Customer Service Faxline 0800 804 344 Email Sales: sales@whiteint.co.nz General info: info@whiteint.co.nz www.whiteint.co.nz
Also:
Water Wizard is a sump pump from Little Giant Pumps.
X
- Xylem Pumps Contact: Xylem Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
USA, Phone: (800) 453-6777
Fax: (888) 322-5877 Web: www.xylem.com
- Xylem HYDROVAR PUMP CONTROL INSTALLATION, OPERATION, MAINTEANCE MANUAL [PDF] (2016) Hydrovar variable speed drive pump control
- Xylem LOWARA SMART PUMP RANGE Additional INSTALLATION OPERATION & MAINTENANCE INSTRUCTIONS [PDF] Xylem, Web: www.xylem.com - retrieved 2022/11/17, original source: https://www.xylem.com/siteassets/brand/lowara/resources/manual/001080138en_d_04_2020_smart_pump_range.pdf
- Also: Xylem - is the owner of other pump brands on this page:
See
Ecocirc, FloJet, Goulds, Hydrovar, Jabsco, Lowara, & Rule Pumps
Y
Z
Zoeller Pump Manuals & Contact Information
- Zoeller Pumps - dewatering pumps - Zoelle produces sump, effluent, sewage & grinder pumps; dewatering pumps, assembled sewage packages; water powered automatic sump pumps
Zoeller Pump customer service Tel: 1-800-742-5044
- Zoeller SHALLOW WELL JET PUMP INSTRUCTIONS [PDF] Models: KS05S, EK05S, CPH05S, ES07S, ES10S, EK10S, JHU15S, EL05S, EL07S, EL10S pumps.
Zimlet Manuals & Contact Information
- Contact: Zimlet USA, 400 Frenchtown Road - East Greenwich, RI 02818 – phone 401 884 4943
- ZIMLET USA WELL TANK INSTALLATION MANUAL [PDF] (2020) Models: Hydro-Plus, Hydro-Plus Bottom
Connection, Ultra-Pro, Inox-Pro, & Ultra Inox-Pro
...
ADVERTISEMENT
Reader Comments, Questions & Answers About The Article Above
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
Godfrey
Watch out: if your pressure relief valve on a water pump system was leaking and you ignore it the danger is that an over-pressure condition blows up the pressure tank killing or injuring anybody nearby. That actually happened, killing a plumber in New Paltz, NY so I'm no making this up.
About joining a red and black wire, sorry but I don't know what wires or what control are involved nor what you're doing, but that too may be dangerous.
Hello I have a problem with my pressure relief valve so I decided to bypass it by joining the red and the black wire
Reader comments:
(Nov 22, 2014) Anonymous said:
A knowledge full article which clearly explain answers of many questions in mind.
Question: how do I find the well?
(Apr 13, 2015) carlos trujillo said:
Can someone can tell me how i can find the well ,i did buy this house in 2005 never ask to the previus owner , and i hava no idea how to find the well pump ..thank you
Reply:
Carlos,
See
WELL LOCATION, HOW TO FIND
For advice on how to find the well
Question: why does my lake water pump no longer deliver water?
(May 13, 2015) Brenda said:
What would be the problem when the pump is not pulling water from the lake and there isn't any pressure?
Reply:
Electrical power to the pump is off
Failed pump motor
failed pump control
pump disconnected
pump intake screen clogged
piping leaky or disconnected enroute
See WATER PRESSURE PROBLEM DIAGNOSIS TABLE for a complete and easy-to-read catalog of possible explanations for loss of water pressure or well pump problems.
...
Continue reading at WATER PUMP REPAIR GUIDE - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
Recommended Articles
Suggested citation for this web page
WATER PUMP & TANK I&O & REPAIR MANUALS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Share this article:
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
Citations & Reviewers
In addition to any citations in the article above, a full list is available on request.
- Thanks to reader EK Woodard, Boise State University, Boise ID, for assistance in diagnosing poor water pressure following an electrical power loss.
- Pumptrol® Pressure Switch Adjustment, Square D, Schneider Electric Corporation, 8001 Knightdale Blvd., Knightdale< NC 27545 1-888-778-2733 - Square D Technical Library, web search 07/24/2010 original source: http://ecatalog.squared.com/techlib/docdetail.cfm?oid=09008926800a93be
- 9013 Pumptrol® Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G, Catalog, SquareD, Schneider Electric Industries SAS, Schneider Electric Industries SAS, web search 02/23/2011, original source:
http://ecatalog.squared.com/pubs/Machine Control/
Pressure-Float-Vacuum Switches/Pressure Switches-Water and Air/9013CT9701.pdf
Square D is a brand of Schneider Electric.
- Class 9013 Square D Commercial Pressure Switches: Water Pump Pressure Control Switch Class 9013, Type F, G, Manual, Square D Company, 8001 Highway 64 East, Knightdale, NC 27545-9023, USA, (919) 266-3671, www.squared.com,
web search 02/24/2011, original source: stevenengineering.com/tech_support/PDFs/45COM.pdf. Quoting:
The Type FSG, FYG, FRG - PUMPTROL® Water Pump Pressure Switches are used to control Water Pump Pressure Switches are used to control
electrically driven water pumps and have the following features:
- The Type FSG is the standard water pump switch, suitable for all types of pumps: jets, submersible,
reciprocating, etc.
- The Type FYG is designed to meet higher horsepower and pressure requirements.
- The Type FRG is reverse acting: the contacts open on falling pressure.
All are diaphragm actuated.
The Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch is used to control electrically
driven water pumps and air compressors. It has higher electrical ratings for direct control of motors in
pump and compressor applications. The Type G switch is diaphragm actuated and has contacts that
open on rising pressure.
- In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
CONTINUE READING or RECOMMENDED ARTICLES.
ADVERTISEMENT