|
|
Complete Diagnostic Guide for Water Pump Short Cycling
- SHORT CYCLING DIAGNOSIS TABLE - Table of all known well pump short cycling causes & diagnostic & repair steps
- What causes the water pump to turn on and off too often or too rapidly?
- How to diagnose & correct short cycling "on-off" of the building water pump
- SHORT CYCLING WATER PUMP - separate article
- Questions & Answers about troubleshooting well pumps that turn on and off too often - short cycling water pumps
- References
|
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This well pump problem table describes the steps to diagnose and cure all known causes of well pump short cycling - what causes the well pump to run too often.
Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.
Well Pump Short Cycling Diagnostic Guide - What to Check, How to Fix
 Short cycling of a water pump (which is discussed in this article) means that the water pump turns on and off too rapidly or too frequently when water is being run in the building.
If this is the problem with your water pump, see our description of the most common SHORT CYCLING CAUSES.
Here we provide a complete SHORT CYCLING DIAGNOSIS TABLE of all known causes of well pump rapid cycling. For each cause the table provides a diagnostic procedure and recommends a repair procedure.
If you are not sure what "water pump short cycling" means or how it is recognized, see SHORT CYCLING WATER PUMP.
Some of the well pump troubleshooting suggestions in this list can be found at the Betta-Flo Jet Pump Installation Manual from the National Pump Co.
|
Well Pump Short Cycling Diagnosis: Things to Check if the Well Pump Runs Too Often |
| Pump Trouble Cause |
Diagnostic Procedure |
Repair Procedure |
| Short cycling water or well pump explanation |
Read in depth on causes and cures of well pump short cycling on and off - alternative to using this more concise diagnostic table (below). |
See the diagnostic article at SHORT CYCLING CAUSES |
| Intermittent water pressure explanation |
The water pump sometimes runs for no apparent reason at all, when no water appears to be running, but the pump is not cycling on and off rapidly - it just comes on and goes through a cycle at odd times. |
See the diagnostic article at INTERMITTENT CYCLING WATER PUMPS |
| Lost water pressure |
Water pressure is poor or has stopped completely |
See WATER PRESSURE LOSS DIAGNOSIS & REPAIR |
| Water pressure tank leak, loss of air charge |
Inspect the water pressure tank for obvious perforations or severe rusting.
Apply soapy water to the entire surface of the water tank, especially above the water line. You can spot the water line as the high point of condensation on the water tank exterior.
Remember to check also for leaks at the air valve(s) used to pump air into the pressure tank. |
Temporary repair of a rust-perforation of a non-bladder type water tank may be possible using a sheet metal screw and neoprene or rubber washer. But the tank needs replacement.
See
Well Tank relation to Water Pressure
Shaking the Water Tank? - is it full of water?
WATER TANK AIR VALVE REPAIRS. |
| Water pressure tank bladder damage or leak |
If the pressure tank is a "captive air" or internal bladder type tank, a leaky or damaged bladder can cause the water tank to become waterlogged and cause short cycling of the water pump.
Most bladder type water tanks contain water inside the bladder and air outside it. Be sure you checked the tank for apparent leaks as we described in the step above.
If your bladder type water tank is fiberglass it may be reversed in design, containing air in the bladder and water in the tank. Still a damaged bladder leads to a waterlogged tank. |
A leaky or damaged water tank bladder needs to be replaced or the entire assembly replaced.
See Bladder type Water Tank Failures and
Repair for Burst Tank Bladder |
| Defective or leaky Air Volume Control |
A leaky or failed air volume control (AVC) will lead to a waterlogged water tank as the control is no longer doing its job of maintaining the tank's air charge. (Not all water tanks have an AVC).
Inspect the AVC and its tubing for rust or water leaks. But an air leak may also be present - see our next step below. |
Repair or replace any suspect air volume control components. See WATER TANK AIR VOLUME CONTROLS
Optionally, remove and plug the AVC fittings and change to an alternative method of maintaining the air charge in the pressure tank:
|
| Air volume control tubing leak: |
Disconnect the air volume control at the water pump and plug that opening. If the water capacity improves there is probably a leak in the tubing or the control. |
Tighten all tubing fittings, be sure the tubing is correct diameter and proper fittings are used so that there are no air or water leaks. See WATER TANK AIR VOLUME CONTROLS |
| Bad pump pressure control switch |
Check the switch contacts for burning or wear |
Adjust or replace the pressure control switch. Temporary emergency repair by cleaning the switch contacts may be possible. See
WATER PUMP PRESSURE CONTROL SWITCH
PRESSURE GAUGES
PRESSURE GAUGE ACCURACY
PUMP PRESSURE CONTROL ADJUSTMENT
PUMP PRESSURE CONTROL REPAIR
PUMP PRESSURE CONTROL REPLACE |
| Bad pump pressure control switch tubing |
Check the tubing connecting the pressure switch to the pump housing for clogging |
Clean or replace the tubing and be sure the connections are not leaky - an air leak will prevent the switch from sensing pressure properly. See
PUMP PRESSURE CONTROL REPAIR
|
| Bad pump pressure control switch settings |
Especially if someone has been fooling around with the pump pressure control cut-in and cut-out pressure settings, the difference between the cut-in (low) and cut-out (high) pressures may be set too small.
Check the water pressure as the pump cuts in and again as it cuts off.
|
Typically we see about 20 psi difference between the pump cut-in and pump cut-out pressures. If you are finding less than this, adjust the pressure control switch accordingly. See
WATER PUMP PRESSURE CONTROL SWITCH
PRESSURE GAUGES
PRESSURE GAUGE ACCURACY
PUMP PRESSURE CONTROL ADJUSTMENT
Watch out: Don't set the cut-out pressure too high or the pump will just keep running. Also, pump gauges are not always accurate. You may need to use a static pressure gauge on a nearby hose fitting such as for the washing machine. See WATER PRESSURE GAUGE ACCURACY
|
| Bad water pressure tank location |
Locating the water pressure tank too far from or on a different level from the pressure control switch can cause pressure control switch bouncing and rapid water pump on-off cycling at the start or end of a water pump operating cycle. |
See Where to Locate the Replacement Water Pressure Tank |
| Blocked water piping, clogged water filter or other water treatment equipment |
A blocked or clogged water filter or pipe or other water treatment equipment close to the water pressure tank can cause very rapid on-off cycling of the water pump, particularly if the filter, valve, or equipment is located between the water pump and the water pressure tank. |
Check the order of installation of equipment. Be sure at least one clear water piping pathway is open between the water pump outlet side and the water pressure tank inlet side.
Replace a dirty, clogged, or suspect water filter cartridge. See WATER FILTERS and CLOGGED SUPPLY PIPING.
Watch out: turn off the pump right away to avoid damage.
|
| Closed or partly closed water supply valve |
Be sure that you haven't forgotten and left a valve closed between the water pump and water pressure tank. This can happen if someone closes a valve to perform other work on the plumbing system and forgets to open it again. |
Be sure at least one clear water piping pathway is open between the water pump outlet side and the water pressure tank inlet side.
Watch out: turn off the pump right away to avoid damage. |
| Plumbing piping or fixture leak on the discharge or supply side of the system |
A plumbing supply piping leak or running toilet can lead to frequent cycling of the water pump.
Shut off all of the fixtures in the plumbing system at their local shutoff valves. If no shut off valves are installed or if they are stuck, install or repair them at the next opportunity.
Listen for leaks. Check for running toilets by using a small amount of food coloring or septic dye dye in the toilet tank. If colored water appears in the bowl the toilet flush valve is leaking.
|
Repair any plumbing leaks or leaky fixtures.
See
Turning on Water when de-winterizing
Water Supply/Drain Pipe Leak Types
PIPING IN BUILDINGS, Clogs Leaks Types
See
WELL PIPING LEAK DIAGNOSIS |
| Piping or fitting leak on the suction side or well side of the system |
A leak in the well supply piping anywhere between the water pick-up point in the well bottom and the entry to the water pressure tank can cause loss of water pressure and water pump short cycling. (It can also cause air entry into the piping system).
For shallow wells install a pressure gauge on the suction side of the system. If your well is a deep well (2-line jet pump) install a pressure gauge on the pump if an attachment point is available.
Let the pump run until it reaches its cut-off pressure. Note the pressure on the gauge. Turn off power to the pump. Turn off water leaving the pressure tank and feeding the building - the valve on the "discharge" side of the system.
Alternatively, after closing the water valve on the output or discharge side of the system (stop feeding water to the building), use a bicycle pump to pump air into the system at the air inlet valve (if your system has one). Pump to 30 psi.
Watch for a pressure drop. If the system won't hold pressure then there is ale a leak on the "suction side" of the water system.
Leaks may be a bad check valve, foot valve, or piping connection anywhere between the pressure tank and well bottom. |
At AIR DISCHARGE at FAUCETS, FIXTURES and at SHORT CYCLING CAUSES we discuss the role of a bad check valve or a hole in the well piping in causing well pump short cycling - water and pressure are lost through the leak when the pump runs, and air may enter the piping when the pump stops - depending on where the leak is located.
First check and tighten all above-ground well piping connections to be sure nothing is leaking. Remember to check or replace any above-ground check valves that may be leaking.
Repeat the test.
If the system still won't hold pressure you will need to pull the well piping and check for a defective or leaky piping connection, leaky well piping check valve above ground, at the pump (if there is a valve there) or in the well at the foot valve.
See
WELL PIPING LEAK DIAGNOSIS
and
AIR DISCHARGE at FAUCETS, FIXTURES
WELL PIPING FOOT VALVES
WELL PIPING TAIL PIECE
CHECK VALVES, WATER SUPPLY
WATER PUMP PRIMING PROCEDURE
|
| Leaking foot valve in the well or leaking check valve at the pump |
If the well pump frequently loses prime, there may be a leaky or failed check valve (at the pump) or foot valve (in the well). |
If your jet pump (above ground) incorporates a check valve at or in the pump that valve may have failed. If there is no foot valve in the well (or if that valve doesn't work), the failure of the above-ground check valve at the pump can lead to short cycling or to loss of pump prime.
To examine the foot valve the well piping has to be pulled. For this reason if you do pull the well piping we recommend replacing the foot valve rather than having to repeat this procedure again soon. Remember to inspect the piping, connections, tailpiece, ejector, and all components in the well.
See
SHORT CYCLING CAUSE: WELL PIPE LEAKS
WELL PIPING FOOT VALVES
WELL PIPING TAIL PIECE
CHECK VALVES, WATER SUPPLY
WELL PIPING LEAK DIAGNOSIS |
| Short cycle stop valve stopped working |
If a well pump short cycleing cycle stop valve has been installed and the system is relying on this device to cure a well pump cycling on and off too often, check that the valve is installed correctly and is working properly. |
See SHORT CYCLE STOP VALVE |
| If the Well Pump Motor Runs for no apparent reason |
If the pump runs too often the cause may be a control problem, water tank problem, piping problem, or a well problem. |
See INTERMITTENT CYCLING WATER PUMPS if the pump runs at odd times for no apparent reason. |
| If the Well Pump Motor Keeps Running & Won't Stop |
If the pump won't turn off the cause may be a damaged pump control, a plumbing or fixture leak, or a well problem. |
Watch out: If the pump motor won't shut off you should turn off electrical power to the pump to avoid damaging it, then diagnose the problem.
See WATER PUMP WONT STOP RUNNING and WELL PIPING LEAK DIAGNOSIS |
| Other causes of well pump short cycling that we have not mentioned: ask your plumber. And CONTACT us to add that helpful information for others. |
CONTACT us by email with questions or suggestions about this list.
Short cycling of a water pump which is defined at SHORT CYCLING WATER PUMP means that the water pump or "well pump" turns on and off too rapidly or too frequently when water is being run in the building. If this is the problem with your water pump, SHORT CYCLING CAUSES describes the most common causes of this problem. We also provide a complete SHORT CYCLING DIAGNOSIS TABLE that lists all possible causes of well pump rapid cycling on and off. If you are not sure what "water pump short cycling" means or how it is recognized, read SHORT CYCLING WATER PUMP.
Intermittent water pump cycling which is discussed at Intermittent Water Pump Cycling When No Water is Running means that the water pump comes on for no apparent reason.
Loss of water pressure means that the pressure with which water enters a plumbing fixture has become too slow, or is sometimes too slow or weak in water flow rate, or water flow may stop entirely. See WATER PRESSURE LOSS DIAGNOSIS & REPAIR
Readers of this document should also see these diagnostic guides for water pumps, wells, motors:
Readers of this document should see WATER PUMP TYPES & LIFE EXPECTANCY, and also see WATER TANK LIFE EXPECTANCY and WELL LIFE EXPECTANCY, but before assuming that a water problem is due to the
pump or well itself, see Water pump and pressure tank repair diagnosis & cost a specific case which offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost.
Frequently Asked Questions (FAQs)
...
Ask a Question or Search InspectApedia
Questions & answers or comments about troubleshooting well pumps that turn on and off too often - short cycling water pumps.
Ask a Question or Enter Search Terms in the InspectApedia search box just below.
Technical Reviewers & References
Related Topics, found near the top of this page suggest articles closely related to this one.
- Access Water Energy, PO Box 2061, Moorabbin, VIC 3189, Australia, Tel: 1300 797 758, email: sales@accesswater.com.au Moorabbin Office: Kingston Trade Centre, 100 Cochranes Rd, Moorabbin, VIC 3189
Australian supplier of: Greywater systems, Solar power to grid packages, Edwards solar systems, Vulcan compact solar systems, water & solar system pumps & controls, and a wide rage of above ground & under ground water storage tanks: concrete, steel, plastic, modular, and bladder storage tanks.
- Smart Tank, Installation Instructions [ copy on file as /water/Smart_Tank_Flexcon.pdf ] - , Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
- Typical Shallow Well One Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect_Jet_Pumps_1.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
- Typical Deep Well Two Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
- Water Fact Sheet #3, Using Low-Yielding Wells [ copy on file as /water/Low_Yield_Wells_Penn_State.pdf ] - , Penn State College of Agricultural Sciences, Cooperative Extension, School of Forest Resources, web search 07/24/2010, original source: http://pubs.cas.psu.edu/FreePubs/pdfs/XH0002.pdf
- Pumptrol® Pressure Switch Adjustment, Square D, Schneider Electric Corporation, 8001 Knightdale Blvd., Knightdale< NC 27545 1-888-778-2733 - Square D Technical Library, web search 07/24/2010 original source: http://ecatalog.squared.com/techlib/docdetail.cfm?oid=09008926800a93be
- 9013 Pumptrol® Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G, Catalog, SquareD, Schneider Electric Industries SAS, Schneider Electric Industries SAS, web search 02/23/2011, original source:
http://ecatalog.squared.com/pubs/Machine Control/
Pressure-Float-Vacuum Switches/Pressure Switches-Water and Air/9013CT9701.pdf
Square D is a brand of Schneider Electric.
- Class 9013 Square D Commercial Pressure Switches: Water Pump Pressure Control Switch Class 9013, Type F, G, Manual, Square D Company, 8001 Highway 64 East, Knightdale, NC 27545-9023, USA, (919) 266-3671, www.squared.com,
web search 02/24/2011, original source: stevenengineering.com/tech_support/PDFs/45COM.pdf.
- ...
- Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
- John Cranor is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-747-7747 or by Email: johncranor@verizon.net
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. The firm provides professional home inspection services & home inspection education & publications. Alan Carson is a past president of ASHI, the American Society of Home Inspectors. Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides:
- Commercial Building Inspection Courses - protocol ASTM Standard E 2018-08 for Property Condition Assessments
- Home Inspection Education Courses including home study & live classes at eleven colleges & universities.
- Home Inspection Education Home Study Courses - ASHI@Home Training 10-course program.
Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
- The Home Reference Book, a reference & inspection report product for building owners & inspectors.
Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
- The Home Reference eBook, an electronic version for PCs, the iPad, iPhone, & Android smart phones.
Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter inspectaehrb in the order payment page "Promo/Redemption" space.
- The Illustrated Home illustrates construction details and building components, a reference for owners & inspectors.
Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page "Promo/Redemption" space.
- The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones.
- Thanks to reader Wayne Ouellette
for discussing water tank replacement needs May 2010
- ...
Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair
The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
|
|