How to Add Air to a Water Pressure Tank
Water pressure tank air pre-charge:
This article describes how to add air to a building water pressure tank and it reviews the function and repair of water tank air volume controls or snifter valves in a building water supply system where a private well is the water source.
This article describes three alternative methods for fixing that problem. The illustration at page top is courtesy of Carson Dunlop Associates, Inc. in Toronto.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Usually a short-cycling well pump problem - the always pump comes on immediately or turns on and off rapidly while you're running water - can be traced to loss of the air charge in the water pressure tank. We call this a "waterlogged" pressure tank.
Besides being annoying (pulsating water pressure), short-cycling of the water pump can damage the pump controls or may even cause damage to the pump itself.
Adding air back to the water tank will usually solve this problem.
Below we summarize these three methods for adding air to a water tank, and we provide links to in-depth detailed procedures.
Also on this page:
...
Air Volume Control devices (AVCs) are designed to automatically keep the required air charge in the pressure tank.
AVCs are found normally only on older type bladderless steel water tanks (photo above) and not on bladder type captive air water tanks that use a vinyl or rubber bladder to keep water and air separated.
Therefore the procedures describe in this section are intended only for conventional non-bladder type water pressure tanks that use an AVC, such as the water tank shown in our photos.
The AVC or snifter valve is intended to automatically put a little bit of replacement air into the tank from time to time as water pressure cycles up and down, that is, each time that the water pump runs.
The AVC device on older water systems often stops working.
If your AVC has stopped working it can be repaired or replaced or even abandoned as we explain in detail
at AIR VOLUME CONTROLS, WATER TANK.
Another choice is to remove the air volume control and plug its fittings if it is leaking, and use one of the other water tank air charge methods described in these articles.
If you decide to abandon rather than repair an AVC that means you'll need to manually set the air pre-charge in the water tank, best using the procedure we describe
at DRAIN the TANK COMPLETELY of WATER - this only works for bladderless water pressure tanks.
Below we illustrate another type of water tank AVC.
Watch out: If your water tank air charge is being lost rapidly, say within days of setting the proper air charge, then your water tank may have an air leak that can be fixed. Or you may need to replace the tank.
In that case see WATER TANK REPAIRS
...
An air valve may be found on the water tank, on piping near the tank or water pump, or at the water tank outlet tee as shown in our photo at left.
Using a bicycle pump or a canister of compressed air one can add air to the water tank.
To add water to your water pressure tank accurately and effectively, it's best to follow these steps:
More Step by step details for adding air to a water pressure tank by using the air inlet valve are found
...
In our photo below the DRAIN valve (round bblack handle) is shown and labeled.
A simple method for recharging the air in a water pressure tank is to turn off the pump, attach a garden hose to the tank drain, open the hose, drain the tank completely, and then let the pump re-fill the tank.
Opening a nearby faucet or valve will speed the drain process by letting air into the system.
Details of the method we just described are
at WATER TANK AIR ADD BY DRAINING
If your well tank is a "captive air" or bladder type pressure tank such as the Well-X-Trol™ series
see WATER TANK BLADDER PRESSURE ADJUSTMENT.
Bladderless water pressure tanks and their types, installation, and repair or adjustment are described
and
at WATER TANK CAPTIVE AIR vs TRADITIONAL WellMate
Bladder type or captive-air water pressure tanks and their repairs are described
at WATER TANK BLADDERS & CAPTIVE AIR
and at WATER TANKS HOW THEY WORK.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
I have a 30/50 switch so i need 28 psi in the water tank. do i put the air in at 28psi on an empty tank of water or add the water then try to add air up to 28psi? (June 12, 2012) Anonymous
Reply:
Anon:
For a bladder type water pressure tank that uses an internal vinyl or rubber bladder to keep water and air separated, If you are setting air pressure in a water pressure tank in the range you describe, the assumption is that the tank has been emptied of water.
See WATER TANK AIR, HOW TO ADD for complete details.
For "Bladderless" water tanks that do NOT use an internal bladder to keep water and air separate, and if the air charge is too low, you can add air after water is in the tank as well. Just watch the gauge. If you add too much air typically the excess air will flow out at the nearest faucet when you next run water.
Many bladderless water tanks use a device intended to keep adding air to the tank as needed - and on older systems these have often stopped working. See AIR VOLUME CONTROLS, WATER TANK
For some (not all) bladderless water tanks that are fed from a deep well submersible pump, a combination of drain on the well piping and an air inlet "snifter" valve on water pipes near the water tank, see DRAIN BACK & SNIFTER VALVE OPERATION
I have a JRS7 Goulds jet pump 3/4 hp, recently i have been encountering a problem which I cant' seem to rectify.
My pump is set that immediately when any tap is opened it will come on and the pump will turn cut off as soon as the tap is closed.
I have changed the pressure switch and am still experiencing the problem.
- Shawn White 7/23/11
Reply:
Shawn, if a pump always comes on immediately when you open a faucet and shuts off when you close the faucet, and IF your water is supplied by a conventional water pump and pressure tank systenm, THEN your water pressure tank is water logged - it's lost its air charge.
See the procedure for adding air back to your water tank
at WATER TANK AIR, HOW TO ADD
Watch out: if you are running water slowly but the pump never can "get ahead" enough to reach the CUT-OFF pressure then there may also be an underlying problem of a well with a very poor flow rate OR something else that's limiting the ability of your pump to send water into your pipes and pressure tank.Examples are a damaged pump impeller or a leak somewhere in the water piping system.
IF your water pump is a tankless water pressure system or pressure booster pump then your system does not use a water pressure tank and cycling of the pump on whenever you run water is normal. Those pumps are described separately
My pressure is set at 60 to 40, When you turn the water on it drops from 60 to 40 immediately and will continue to turn on and off until the water valve is turned off.
The pump basiclly want shut off until you stop using water (June 24, 2014) Anonymous
Reply by (mod)
Anon when pressure drops immediately on opening a tap I expect that there is little or no air charge in the pressure tank.
Your water tank is "waterlogged".
Take a look at
Thanks Dan! While I was waiting for this answer, ;) I turned power off, found out there is no valve on the tank to drain it, so I flipped power back on.
Watered a rose bush & it was NOT cycling on & off! So I am thinking turning power off fixed it... we will see. Thanks so much for your answer, I love this site as I am single women in need of fixes sometime! Appreciate it - On 2011-08-11 by Anonymous
Thanks for all the information...saved me a call to the plumber today! Great site with a ton of information. - On 2011-06-21 by Adam Bunday
I like this site. It is clear, concise and descriptive. Thanks for the help with the well water pressure problems we recently experienced. If I can follow the instructions anyone can! On 2011-06-02 by linda hawwk
...
I can't thank you enough for your website and quick response! I wanted to write you back and let you know the outcome of my little well issue.
The surging water I described appears to have been caused by what you describe as “Well pump short cycling.” After reading (more carefully) your article:
Well Pump Short Cycling: How to diagnose “Water Pump Short Cycling” and restore Air in a Building Water Tank and your response, I was hopeful that the cause was a waterlogged tank. I read your step by step instructions and it worked beautifully.
Opening up nearby hose bibs and the schrader valve helped the water drain more quickly, but it still took several hours to drain the tank.
Before I tried this, the tank was draining so slowly and gurgling, I didn’t think it was still full of water. It has been nearly a week the well is working perfectly now.
Not only did you save me some money, but more importantly, fixing it myself was good for my self esteem. Thanks again! On 2011-12-12 by Max
...
Continue reading at AIR INLET VALVES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see WATER TANK AIR, HOW TO ADD FAQs - questions and answers posted originally on this page
r see these
WATER TANK AIR, HOW TO ADD at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.