Water Pump Pressure Control Switch Diagnosis & RepairPumptrol and similar water pressure control switch repair procedures.
Water pressure control switch repair: Pumptrol switch repair & repair kits.
This article describes how a water pump pressure control switch works and how to diagnose problems with the building water supply that seem to be traced to the pump control, switch, or to other underlying issues with a water pump, well, piping or other controls. We describe the diagnostic steps to take if a water pump won't turn on, won't turn off, or a switch that is burned, corroded or damaged.
We discuss: How to Repair a Water Pressure Control Switch that Sticks "ON" or "OFF" or is irregular, and how to Diagnose a Malfunctioning Water Pump Control Switch.
Pumptrol 20-40, 30-50, or 40-60 pressure switch operation. What are the controls, switches, valves found on water tanks and water pumps, what do they do, how are they repaired?
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article explains inspecting, cleaning, and possibly repairing a typical Water Pump Pressure Control Switch, normally found mounted on piping at the water pressure tank such as in this example [image] where you see a small gray-covered box with electrical wires coming in (power) and out (to pump) of it.
We describe troubleshooting several problems that can cause the control switch to fail to turn the pump ON when it should or that can cause the control to fail to turn the pump OFF when it should.
Following the procedure to test the operation of a pump control switch just below we provide links to individual diagnostic & repair articles that address particular pump operating problems such as a pump that won't turn on or won't turn off or that runs continuously.
If the water supply is high in sediment
often sediment will clog the pressure sensing opening at the bottom of the pressure control. We've tried cleaning out this orifice but it's never proven to be a lasting repair.
If your pump pressure switch stops responding to changes in water pressure it probably needs to be replaced.
If we’ve traced a pump control problem to the water tank or water pump pressure switch itself with some certainty, we will often just replace the switch.
But beware, we once replaced a pump control switch when the problem was a clogged filter which was causing the pump to cycle on and off erratically. We felt pretty stupid.
We’ll need to do some water pump switch diagnosis – here are a few ideas that may help getting a recalcitrant pump control switch working again.
Watch Out: Safety warning - Shock Hazards: To remove a pump control/pressure switch remember to turn off electrical power, and using a neon tester or VOM double check to make SURE that electrical power is off, and taped-off so that on one turns it on and causes you to get shocked.
Working around electricity and plumbing is particularly dangerous because of the increased chance of touching a live electrical wire while touching grounded plumbing piping. Turn off power.
See WATER PUMP ELECTRICAL SWITCHES.
A pump or water tank pressure control switch is designed and adjusted to turn the pump on at a "cut in" pressure, usually 20 psi or 30 psi, and to turn the water pump off at a "cut out" pressure, usually 40 psi or 50 psi.
When you buy this control it is usually set at the proper cut-in and cut-out pressures - check the box.
If your pump control is properly adjusted then it should be turning the pump on and off nicely at the pre-set pressures.
If the switch is behaving erratically or not coming on or not shutting off at all, there could be various explanations, some of which have nothing to do with the switch itself.
See WATER PRESSURE CONTROL SWITCH ADJUSTMENTS
These other problems are discussed
at WATER PRESSURE LOSS DIAGNOSIS & REPAIR
and WATER TANK REPAIRS.
Alternatively you may want to see one of these water pressure or pump diagnostic procedures:
1. The water PUMP WON'T TURN OFF when it should - the pump just keeps running.
If water pressure is at or above the pressure switch CUT-OUT pressure and the pump won't turn OFF there could be several causes and fixes that we will describe.
Watch out: this is a dangerous condition. If the pump brings water pressure well above normal building water pressure levels, say over 70 psi, there is risk of a burst pipe or burst water tank that can cause a flood or injure someone. Turn off the pump.
See WATER PUMP WONT STOP RUNNING - there we list all of the things that can cause a pump to run continuously.
2. The water PUMP WON'T TURN ON when it should.
If water pressure falls below the pressure switch CUT-IN pressure and the pump won't turn ON there could be several causes and fixes that we will describe.
See WATER PUMP WON'T START - where we list all of the things that prevent a pump from turning on.
Some water pump control problems can cause both pump-start and pump-stop problems, as you'll see in the following
3. The water pump runs but there is WEAK WATER PRESSURE
See PUMP RUNS, WEAK or NO WATER PRESSURE for a diagnostic table
4. The water pump runs but there is NO WATER PRESSURE
See NO WATER PRESSURE for a diagnostic table
5. The water pump runs but the PUMP CYCLES ON & OFF RAPIDLY or INTERMITTENTLY
See WATER PUMP SHORT CYCLING for diagnosing a pump that turns on and off too rapidly
See WATER PUMP INTERMITTENT CYCLING for diagnosing a pump that runs at odd times and for no apparent reason
The pump pressure control switch, by being connected
to the actual water piping in the building, senses the water pressure and when necessary, turns the water pump on.
The water pump pressure control switch either turns on the water pump directly, or (particularly when a submersible water pump is in use), this switch may operate a physically separate (usually wall-mounted) heavier-duty pump relay which turns on the water pump itself.
See WATER PUMP RELAY SWITCH for more details of that control.
Watch out: If your well pump won't stop running, you should probably turn power to the pump off to avoid burning up the pump motor.
If the water pump will not turn OFF,
see WATER PUMP WONT STOP RUNNING for detailed diagnostic and repair procedures.
If your well pump won't start, see the diagnostic and repair advice
See details at CHECK RESET SWITCH / BYPASS LEVER (not present on all controls)
See these two procedures
If the pump pressure control switch contacts are burned we can sometimes get it working again for a while by first, turning off electrical power as we described above,
and then using a file, carefully cleaning all touching-surfaces the switch contacts.
Details are at CHECK PRESSURE SWITCH RELAY CONTACTS
If after inspecting the pump pressure control switch or its mounting fittings you decide that you've repaired it or that you need to replace it, follow the instructions
at PUMP PRESSURE CONTROL REPLACE for reinstalling the control.
Watch out: do NOT try working on a pump control switch without first removing electrical power - you could be killed by electrical shock.
This topic has moved to PRESSURE SWITCH REPAIR KIT - separate article
This section has moved to WATER PUMP PRESSURE SWITCH MANUALS
Jack Moore said:
Wow, thanks for writing! This is really helpful to someone who just inherited a house with one of these pumps. No one I know had ever had one before, so I was a little intimidated. But now I know a little more about how to find, adjust, and repair the well pump. Glad I found this!
...
...
Continue reading at WATER PUMP PRESSURE SWITCH INSTALL / REPLACE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see WATER PUMP PRESSURE SWITCH REPAIR FAQs - pump control switch diagnostic & repair questions & answers posted originally at the end of this article.
Or see these
WATER PUMP PRESSURE SWITCH REPAIRS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.