Intermittent Water Pump Cycles Q&A-4Intermittent water pump cycling on and off, Q&A-4.
Here we field reader questions on why a well pump turns on or on and off when we think no water is being used in the building.
This article series explains how to diagnose & repair water pump intermittent cycling - the water pump comes on when no water is being run in the building. Intermittent water pump cycling means that the water pump comes on for no apparent reason.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These older questions & answers about unexplained water pump cycling on and off, posted originally
at WATER PUMP INTERMITTENT CYCLING - topic home.
Be sure to review the causes and cures discussed in that article
Before we get to recent reader Q&A on water pump cycling problems, lets
On 2019-03-28 by kay - Davey 350p8c water pump that keep short cycling
@kay,
Our pump runs (on and off, on and off constantantly) - we turn it off when not in use.
I have a Davey 350p8c water pump that keep short cycling I have tried to fix it by putting air into the bladder but it still short cycles any help would de appreciated
On 2019-03-29 by (mod) - our pump just never turns off
It sounds as if there is both a leak or water running somewhere in your home that turns the pump "ON" combined with a waterlogged pressure tank that causes the pump to turn of and off after just a few seconds. 6
Continuous pump running or separately pump rapid on-off short cycling - are NOT the same as "intermittent" pump on-off cycling at odd intervals or at periods when no water is being run.
If your pump seems to run for no reason but intermittently - that is it will turn off but then runs again - the diagnosticsat WATER PUMP INTERMITTENT CYCLING are what you should read.
Continuous pump operation: if the pump won't stop running the cause may be simply a high water usage rate that exceeds the pump or well's capacity to deliver water or there may be a leak or a bad control.
See WATER PUMP WONT STOP RUNNING to diagnose and fix that problem
On 2019-02-19 by Susan - Need help fixing intermittent pump cycling
We have intermittent pump cycling. We have 1/2 hp shallow well jet pump, a 36 gallon air pressure tank, and a foot valve in our cistern. We cannot locate any leaks inside the house... We have lost about 1500 gallons of water over 3-4 days.
We noticed the issue after a really cold -7 low, for a couple days. The pump is under our house.
We did not have any pipes freeze. We have replaced the air tank. But still hearing pump cycle intermittently.
We cannot figure out where our water is going and why the pump is cycling when nothing is on! Help!
On 2019-02-19 by (mod) - We have intermittent pump cycling.
Susan
If you turn off water between the pressure tank in the house and pressure continues to drop from you know on which side of the tank and pump the leak is present. From that point you would suspect a leaky foot valve Aura Lincoln piping between the foot valve and the pressure tank that you have not yet found.On 2019-02-19 by Anonymous
Thank you... Would that cause us to lose all of the water in our cistern? Where is the water going?
On 2019-02-19 1 by (mod) - what would cause us to lose all of the water in our cistern?
If the leak is outside, into the ground
How does water enter your cistern? From what source?
Could the cistern itself be leaking?On 2019-02-20 by Susan
PS. We are not losing prime even with pump shut off.
the cistern is fed from rain water or water that is trucked in. I went looking for leaks this evening. I thus far have found nothing. Next is to dig up the line to the frost free hydrant , outside water spigot. That is the only fixture that I cannot visably see the lines.
We have turned the pump off when not in use to keep from feeding the leak.
Seems it causes our hot water tank to lose water when the pump is not keeping the lines under pressure.
We can hear it start to make a lot of gurgling noises after the pump has been off for a couple of hours, kind of like a boiling water with space above inside a closed tank sound.
So my guess is the leak is allowing air into the system when not under pressure...now to find the leak!
It is possible the cistern itself could be leaking but when the pump was off all day,the water level did not change.It went down 6inches over night when the pump was on and cycling intermittently.
On 2019-02-20 by (mod) -
At this point i would follow the pipes in detail.
See all of the diagnostics
at WATER PRESSURE TABLE 1: PUMP WON'T RUN, WON'T STOP, or CYCLES - water pump diagnosis
On 2019-02-22 by Anonymous
thank you! We are working on process of elimination. I installed a shut off on the outside spigot. So far it seems to have improved the intermittent pump cycling. Time will tell. The plans are to leave the outside spigot shut off until better weather than dig it up.
On 2019-01-18 by TinaLynnNelson@aol.com - Suddenly my well pump won't shut off with a high pressure of 65.
HELP! Have submersible pump replaced 5 years ago.
Last year, changed well bladder tank from 40 gallons to 87 gallons as recommended by amount of faucets.
Since we've suffered from very rusty water & sulfur smell changed all plumbing lines, pressure gauges and added some extra valves for easier diagnosis with problems.
Added a pressure relief valve as recommended by new tank.
About 30 feet from well & tank is our house, against it is our salt softener (all internal parts changed out last year too) and added a double filtration system. New gauges and extra valves there as well.
Worked beautifully with clear un-smelly water. Suddenly my well pump won't shut off with a high pressure of 65. The tank appears to have water at the bottom as it doesn't sound hollow & its heavy. I checked for running water/leaks, then changed out the cut off switch. Strangely well pressure went down to 55 but still the pump did not shut off.
Adjusted new cut off switch to approx 50 (about 2 1/2 turns on diff. nut and 1/2 turn on larger). STILL PUMP RUNNING. The well pressure maintains 55 at tank.....45 at my house (normal drop between well & house after filters). Still pump running.
I checked control box. Capacitor was questionable as was a wire. Changed out complete control box. STILL PUMP RUNS CONTINUOUSLY.
I've been turning off the circuit breaker when I don't need water. I noticed that when the water is turned off it begins running back to the well.
So it sounds like it is running into all the lines because of the pump continuously running OR it may not be filling the tank, but as I said the tank sounds full at the bottom (not in the middle, I'd say lower 1/3) Spent all my money on control box & cut off.
WHAT could be the problem?
On 2019-01-18 by (mod) - submersible pump won't shut off
Tina
Watch out: very high pump pressure can burst a water pressure tank and injure people nearby or flood the building.
Besides that immediate concern, and if no water is running in your building and there's no well pipe leak, I suspect a clogged pressure control switch - replace it.
We have suggested diagnostic steps for a pump that won't stop
See WATER PUMP WONT STOP RUNNING
On 2019-01-05 by jacques Control switch keeps switching the pump on and off every few seconds
my dab controller keeps switching on and of every few seconds. It comes fro. a tank and supplies my toilet. all pipes are above ground so there is no leaks. do I replace the controller or is there a solution
On 2019-01-06 by (mod) -
Before replacing the pressure control switch take a look in the ARTICLE INDEX and review the diagnostic articles on WELL PUMP SHORT CYCLING as there are quite a few possible causes such as a leaky foot valve or well pipe.
...
Continue reading at WATER PUMP INTERMITTENT CYCLING or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER PUMP INTERMITTENT CYCLING FAQs-4 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.