InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
INSULATION IDENTIFICATION GUIDE
INSULATION INSPECTION & IMPROVEMENT

ACOUSTICAL SEALANT CHOICES
AIR BYPASS LEAKS
AIR LEAK MINIMIZATION
AIR LEAK SEALING PROCEDURE
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS FLOORING REMOVAL GUIDE
ASBESTOS IDENTIFICATION IN BUILDINGS
ASBESTOS LIST of PRODUCTS
ASBESTOS MATERIAL REGULATIONS
ASBESTOS PHOTO GUIDE to Materials
ASBESTOS RISK ASSESSMENT
ASBESTOS REMOVAL, Wetting Guidelines
ASBESTOS ROOFING / SIDING DUST
Asbestos Under the Microscope
ATTIC LEAKS, CONDENSATION & MOLD
ATTIC VENTILATION

BASEMENT CEILING VAPOR BARRIER
BASEMENT HEAT LOSS
BASEMENT LEAKS, INSPECT FOR
BASEMENT WATERPROOFING
BATH & KITCHEN DESIGN GUIDE
BATHROOM VENTILATION
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLOWN-IN INSULATION
BOOKSTORE - INTERIORS
BRICK LINED WALLS
BRICK VENEER WALL INSULATION
BRICK VENEER WALL Loose, Bulged
BRICK WALL DRAINAGE WEEP HOLES

BUCKLED FOUNDATIONS due to INSULATION?
BUILDING NOISE DIAGNOSIS & CURE

CABINETS & COUNTERTOPS
Carbon Nanotube Materials
CACTUS FUNGI / MOLD
CAR MOLD CONTAMINATION
CARPET DUST IDENTIFICATION
CARPET MOLD CONTAMINATION
CARPET TEST PROCEDURE
CARPETING & INDOOR AIR QUALITY
CARPETING, SELECTION & INSTALLATION
CATHEDRAL CEILING INSULATION
CATHEDRAL CEILING VENTILATION
CEILING FINISHES INTERIOR
CEILINGS, DROP or SUSPENDED PANEL
CEILINGS, PLASTER TYPES
CEILINGS, PLASTER, LOOSE HAZARDS
CEILING TILES - Asbestos-Containing
CONDENSATION or SWEATING PIPES, TANKS
CRAWL SPACES

DEFINITION of Heating & Cooling Terms
DEHUMIDIFICATION PROBLEMS
DECK & PORCH CONSTRUCTION
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

ENGINEERED WOOD Flooring

FIBERGLASS HAZARDS

FIBERGLASS INSULATION
FIBERGLASS PARTICLE CONTAMINATION TEST
Fiberboard Insulation Sheathing Mold
Fiberglass Enviro-Scare
FIBERGLASS INSULATION MOLD
Fireproofing containing Asbestos
FRAMING DETAILS for BETTER INSULATION
FRAMING DETAILS for DOUBLE WALL HOUSES
FRAMING METAL STUD PERFORMANCE
FREEZE-PROOF A BUILDING

HEAT LOSS RATE CALCULATIONS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSEWRAP INSTALLATION DETAILS
HOUSEWRAP AIR & VAPOR BARRIERS
HOUSE DOCTOR, how-to be
HOUSE PARTS, DEFINITIONS

HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INDOOR AIR QUALITY & HOUSE TIGHTNESS

INSULATION INSPECTION & IMPROVEMENT
INSULATION CHOICES
Insulation Air & Heat Leaks
INSULATION FACT SHEET- DOE
INSULATION IDENTIFICATION GUIDE
  ASBESTOS-FREE INSULATION MATERIALS
  ASBESTOS IDENTIFICATION IN buildings
  Asbestos Pipe Insulation
  Balsam Wool Batt Insulation
  BLOWN-IN INSULATION
  BRICK LINED WALLS
  BRICK VENEER WALL INSULATION
  Cellulose loose fill insulation
  Ceramic Insulation
  Concrete insulation, light-weight
  Cotton Insulating Batts
  Fiberglass Insulation
  Foam Board Insulation
  Foam Insulation Types - Visual Id
  Homasote & Other Insulating Board
  Icynene Foam Spray Insulation
  Insects & Foam Insulation
  Mineral Wool - Rock Wool Insulation
  Paper Duct Insulation
  Perlite Insulation
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION
INSULATION INSPECTION & IMPROVEMENT
INSULATION LOCATION - WHERE TO PUT IT
INSULATION LOCATION for BRICK VENEER WALLS
INSULATION LOCATION for CAPES, CRAWLSPACES
INSULATION LOCATION for CATHEDRAL CEILINGS
INSULATION LOCATION for GREENHOUSE or SOLARIUM
INSULATION MOLD
INSULATION R-Values & Properties

KIT HOMES, Aladdin, Sears, Wards, Others
KITCHEN & BATH DESIGN GUIDE
KITCHEN VENTILATION

LEED GREEN BUILDING CERTIFICATION
LEED Building Designation & IAQ
LOG HOME ENERGY EFFICIENCY
LOG HOME GUIDE

MOLD in FOAM INSULATION, RESISTANCE

MOISTURE CONTROL in BUILDINGS
MSDS Material Safety Data Sheets
MVOCs & MOLDY MUSTY ODORS
MYCOPHOBIA, STAINS MISTAKEN for MOLD
MYCOTOXIN EFFECTS of MOLD EXPOSURE

Nanomaterials Hazards
NOISE / SOUND DIAGNOSIS & CURE
NOISE, AIR CONDITIONER COMPRESSOR
NOISE, DUCT VIBRATION DAMPENERS
NOISE CONTROL for HEATING SYSTEMS
NOISE CONTROL for FLOORS
NOISE CONTROL for PLUMBING
NOISE CONTROL for ROOFS
NOISES COMING FROM WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODOR DIAGNOSIS CHECKLIST

PAINT FALURE, DIAGNOSIS, CURE, PREVENTION
Paper Duct Insulation Containing Asbestos
PASCAL CALCULATIONS
PASSIVE SOLAR DESIGN METHOD
PASSIVE SOLAR HEAT PERFORMANCE
PASSIVE SOLAR HOME, LOW COST
PHOTOVOLTAIC POWER SYSTEMS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
REFLECTIVE INSULATION
RIGID FOAM USE INDOORS

ROT, FUNGUS, TERMITES
ROT, TIMBER FRAME

SAFETY HAZARDS & INSPECTIONS
  MSDS Material Safety Data Sheets
SEARS KIT HOUSES
SHEATHING, FOIL FACED - VENTS
SLAB INSULATION, PASSIVE SOLAR

SOUND CONTROL in buildings

STAIN & BIODETERIORATION AGENT CATALOG
STAINS on buildings - QUICK GUIDE
STAIN DIAGNOSIS on BUILDING EXTERIORS
STAIN DIAGNOSIS on BUILDING INTERIORS
STAIN DIAGNOSIS on ROOFS
STAIN DIAGNOSIS on STONE
STAINS & FINISHES, INTERIOR
STAINS on INDOOR SURFACES: PHOTO GUIDE

STAIRS, RAILINGS, LANDINGS, RAMPS
STONE CLEANING METHODS
STONE VENEER WALLS
STUCCO WAll FAILURES DUE TO WEATHER
STUCCO WALL METHODS & INSTALLATION
STUCCO OVER FOAM INSULATION
STUCCO PAINT FAILURES
SUMP PUMPS GUIDE
SWEATING (CONDENSATION) on PIPES, TANKS

THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING Indicates Heat Loss
THERMOSTATS, HEATING / COOLING

TRIM, INTERIOR INSTALLATION
TRUSS UPLIFT, ROOF
TRUSSES, Floor & Roof

VAPOR BARRIERS & CONDENSATION in BUILDINGS
VENTILATION in buildings
VINYL Siding or PLASTIC Window ODORS in buildings
VINYL CHLORIDE HEALTH INFO

WALL SIDING TRIM & FINISHES
WALL FINISHES INTERIOR
WATER BARRIERS, EXTERIOR BUILDING
WATER ENTRY in buildings
WIND WASHING INSULATION At EAVES
WINDOWS & DOORS
WINTERIZE A BUILDING
WOOD Burning Heaters Fireplaces Stoves

More Information

Mineral wool insulation in an attic Insulating Material Identification Guide
How to Identify All Types of Building Insulation Products
InspectAPedia®  -      

  • Photo guide to identification of different building insulation materials
  • Properties of different building insulation products
  • Description of non-asbestos materials sometimes mistaken for asbestos in buildings
  • Types & photographs of building insulation that does not normally contain asbestos
  • Questions & answers about how to identify different kinds of building insulation

How to identify types of insulation used in buildings & their mechanical systems: this series of articles provides details about all types of building insulation, identifying each type of insulation. We illustrate and include photographs of insulation materials that would not be expected to contain asbestos as well as asbestos-containing materials.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

ASBESTOS-FREE INSULATION MATERIALS vs ASBESTOS-CONTAINING INSULATION - Examples of insulating materials that do or do not commonly contain asbestos including some mistake for asbestos

This document assists building buyers, owners or inspectors who need to identify building insulation or who need to recognize asbestos-containing materials (or probable-asbestos) in buildings by simple visual inspection. Separately at INSULATION INSPECTION & IMPROVEMENT we provide details about inspecting and improving the level and effectiveness of insulation in buildings, as well as advice on troubleshooting insulation system defects & problems.

While an expert lab test using polarized light microscopy may be needed to identify the specific type of asbestos fiber, or to identify the presence of asbestos in air or dust samples, many asbestos-containing building products not only are obvious and easy to recognize, but since there were not other look-alike products that were not asbestos, a visual identification of this material can be virtually a certainty in many cases.

cellulose building insulation

Asbestos Free Building Materials

Our photo at left is of blown-in cellulose insulation. The links just below under the green heading provide articles describing building insulation materials that would not be expected to contain asbestos.

  ASBESTOS-FREE INSULATION MATERIALS
    Balsam Wool Batt Insulation
  BLOWN-IN INSULATION
  BRICK LINED WALLS
  BRICK VENEER WALL INSULATION
  Cellulose loose fill insulation
  Ceramic Insulation
  Concrete insulation, light-weight
  Cotton Insulating Batts
  Fiberglass Insulation
  Foam Board Insulation
  Foam Insulation Types - Visual Id
  Homasote & Other Insulating Board
  Icynene Foam Spray Insulation
  Insects & Foam Insulation
  Mineral Wool - Rock Wool Insulation
  Paper Duct Insulation
  Perlite Insulation
  PHENOLIC FOAM INSULATION
  POLYISOCYANURATE FOAM INSULATION
  POLYISOCYANURATE FOAM BELOW SLABS
  POLYSTYRENE FOAM INSULATION
  RADIANT BARRIERS
  REFLECTIVE INSULATION
  RIGID FOAM USE INDOORS
  STRESS SKIN INSULATED PANELS
  STUCCO OVER FOAM INSULATION
  SUPER HI-R INSULATION
  SUPERINSULATION RETROFIT
  Urea Formaldehyde Foam Insulation UFFI
  URETHANE FOAM Deterioration, Outgassing
  VERMICULITE INSULATION - some (not all) Vermiculite contains asbestos depending on where the vermiculite was mined

Mineral wool insulation in an attic

These non-asbestos insulations include cellulosic insulations such as loose-fill cellulose and balsam wool batts, cotton insulation, fiberglass insulation, mineral wool insulation, slag wool insulation, and rock wool insulation.

Our photograph (left) shows indoor use of polystyrene foam insulating board on the inside of a basement foundation wall - notice the absence of a suitable fire-resistant covering?

This installation probably violates local building codes. Foam insulating boards do not contain asbestos but can present a fire hazard because they give off dense smoke and possibly toxic fumes in a fire.

Other older building insulation materials such as corn cobs, newspaper, bricks, and simple reflective barriers using aluminum foil also would not be expected to contain asbestos.

Asbestos-Containing Products

Cement asbestos roof shinglesIn addition to many well-known asbestos-containing products are literally hundreds of other materials where asbestos fibers or powdered filler were used but that may be less well-known and less immediately recognized.

Many of these materials remain present in older residential and commercial buildings and as we describe at ASBESTOS REGULATION Update, some contemporary products are also permitted to contain asbestos. See the articles listed below:

ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS-FREE INSULATION MATERIALS
ASBESTOS IDENTIFICATION IN buildings
  ASBESTOS AIR DUCTS
  Asbestos Air Duct Vibration Dampers
  ASBESTOS in CARPETING, PADDING
  ASBESTOS CEILING TILES, Asbestos-Containing
  ASBESTOS DUCTS, HVAC
  ASBESTOS DUCT INSULATION, Asbestos Paper
  ASBESTOS DUCTS, Transite Pipe
  ASBESTOS FIREPROOFING SPRAY-On Coatings
  ASBESTOS FLOOR TILE IDENTIFICATION
  ASBESTOS FLOOR TILE LAB PROCEDURES
  ASBESTOS FLOOR TILE PHOTO ID GUIDE
  ASBESTOS FLOORING HAZARD REDUCTION
  ASBESTOS FLOORING REMOVAL GUIDE
  Asbestos Foamed-Over
  ASBESTOS INSULATION
  ASBESTOS PAPER DUCT INSULATION
  ASBESTOS PIPE INSULATION
  ASBESTOS ROOFING, CEMENT & FIBER CEMENT
  ASBESTOS SIDING CEMENT & FIBER CEMENT
  ASBESTOS in UNUSUAL PLACES
  ASPHALT-ASBESTOS PAINT / SEALANT
  TRANSITE PIPE AIR DUCTS
  TRANSITE PIPE CHIMNEYS / FLUES
  TRANSITE PIPE WATER SUPPLY
  VERMICULITE INSULATION
ASBESTOS FLOORING HAZARD REDUCTION
ASBESTOS FLOORING REMOVAL GUIDE
ASBESTOS LIST of PRODUCTS
ASBESTOS MATERIAL REGULATIONS
ASBESTOS MATERIAL REGULATIONS Update
ASBESTOS MATERIAL REGULATIONS, OSHA
ASBESTOS PHOTO GUIDE to Materials
ASBESTOS REMOVAL, Amateur, Incomplete
Asbestos Removal, Certification
ASBESTOS REMOVAL GUIDE, FLOORING
ASBESTOS REMOVAL, Wetting Guidelines
ASBESTOS RISK ASSESSMENT
Asbestos Under the Microscope

Questions & Answers regarding this article

Questions & answers about how to identify different kinds of building insulation.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

INSULATION IDENTIFICATION GUIDE

  • [1] 3/07: thanks to Gary Randolph, Ounce of Prevention Home Inspection, LLC Buffalo, NY, for attentive reading and editing suggestions. Mr. Randolph can be reached in Buffalo, NY, at (716) 636-3865 or email: gary@ouncehome.com
  • [2] 06/07: thanks for photographs of transite asbestos heating ducts, courtesy of Thomas Hauswirth, Managing Member of Beacon Fine Home Inspections, LLC and (in 2007) Vice President, Connecticut Association of Home Inspectors Ph. 860-526-3355 Fax 860-526-2942 beaconinspections@sbcglobal.net

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop, and from the InspectAPedia bookstore. The 2010 edition of the Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • American Plywood Association, APA, "Portland Manufacturing Company, No. 1, a series of monographs on the history of plywood manufacturing",Plywood Pioneers Association, 31 March, 1967, www.apawood.org
  • Animal Allergens: Dog, Cat, and Other Animal Dander - Cleanup & Prevention Information for Asthmatics and regarding Indoor Air Quality.
  • Asbestos: How to find and recognize asbestos in buildings - visual inspection methods, list of common asbestos-containing materials
  • Asbestos HVAC Ducts and Flues field identification photos and guide
  • Asbestos products and their history and use in various building materials such as asphalt and vinyl flooring includes discussion which draws on Asbestos, Its Industrial Applications, D.V. Rosato, engineering consultant, Newton, MA, Reinhold Publishing, 1959 Library of Congress Catalog Card No.: 59-12535 (out of print).
  • Asbestos Identification and Testing References
    • Asbestos Identification, Walter C.McCrone, McCrone Research Institute, Chicago, IL.1987 ISBN 0-904962-11-3. Dr. McCrone literally "wrote the book" on asbestos identification procedures which formed the basis for current work by asbestos identification laboratories.
    • Stanton, .F., et al., National Bureau of Standards Special Publication 506: 143-151
    • Pott, F., Staub-Reinhalf Luft 38, 486-490 (1978) cited by McCrone
  • ASHRAE resource on dew point and wall condensation - see the ASHRAE Fundamentals Handbook, available in many libraries. The following three ASHRAE Handbooks are also available at the InspectAPedia bookstore in the third page of our Insulate-Ventilate section:
    • 2005 ASHRAE Handbook : Fundamentals : Inch-Pound Edition (2005 ASHRAE HANDBOOK : Fundamentals : I-P Edition) (Hardcover), Thomas H. Kuehn (Contributor), R. J. Couvillion (Contributor), John W. Coleman (Contributor), Narasipur Suryanarayana (Contributor), Zahid Ayub (Contributor), Robert Parsons (Author), ISBN-10: 1931862702 or ISBN-13: 978-1931862707
    • 2004 ASHRAE Handbook : Heating, Ventilating, and Air-Conditioning: Systems and Equipment : Inch-Pound Edition (2004 ASHRAE Handbook : HVAC Systems and Equipment : I-P Edition) (Hardcover)
      by American Society of Heating, ISBN-10: 1931862478 or ISBN-13: 978-1931862479
      "2004 ASHRAE Handbook - HVAC Systems and Equipment The 2004 ASHRAE HandbookHVAC Systems and Equipment discusses various common systems and the equipment (components or assemblies) that comprise them, and describes features and differences. This information helps system designers and operators in selecting and using equipment. Major sections include Air-Conditioning and Heating Systems (chapters on system analysis and selection, air distribution, in-room terminal systems, centralized and decentralized systems, heat pumps, panel heating and cooling, cogeneration and engine-driven systems, heat recovery, steam and hydronic systems, district systems, small forced-air systems, infrared radiant heating, and water heating); Air-Handling Equipment (chapters on duct construction, air distribution, fans, coils, evaporative air-coolers, humidifiers, mechanical and desiccant dehumidification, air cleaners, industrial gas cleaning and air pollution control); Heating Equipment (chapters on automatic fuel-burning equipment, boilers, furnaces, in-space heaters, chimneys and flue vent systems, unit heaters, makeup air units, radiators, and solar equipment); General Components (chapters on compressors, condensers, cooling towers, liquid coolers, liquid-chilling systems, centrifugal pumps, motors and drives, pipes and fittings, valves, heat exchangers, and energy recovery equipment); and Unitary Equipment (chapters on air conditioners and heat pumps, room air conditioners and packaged terminal equipment, and a new chapter on mechanical dehumidifiers and heat pipes)."
    • 1996 Ashrae Handbook Heating, Ventilating, and Air-Conditioning Systems and Equipment: Inch-Pound Edition (Hardcover), ISBN-10: 1883413346 or ISBN-13: 978-1883413347 ,
      "The 1996 HVAC Systems and Equipment Handbook is the result of ASHRAE's continuing effort to update, expand and reorganize the Handbook Series. Over a third of the book has been revised and augmented with new chapters on hydronic heating and cooling systems design; fans; unit ventilator; unit heaters; and makeup air units. Extensive changes have been added to chapters on panel heating and cooling; cogeneration systems and engine and turbine drives; applied heat pump and heat recovery systems; humidifiers; desiccant dehumidification and pressure drying equipment, air-heating coils; chimney, gas vent, fireplace systems; cooling towers; centrifugal pumps; and air-to-air energy recovery. Separate I-P and SI editions."
    • Principles of Heating, Ventilating, And Air Conditioning: A textbook with Design Data Based on 2005 AShrae Handbook - Fundamentals (Hardcover), Harry J., Jr. Sauer (Author), Ronald H. Howell, ISBN-10: 1931862923 or ISBN-13: 978-1931862929
    • 1993 ASHRAE Handbook Fundamentals (Hardcover), ISBN-10: 0910110964 or ISBN-13: 978-09101109
  • Brick nogging used as soundproofing is mentioned in this article on Popular Forest
  • Brick Nogging, Historical Investigation and Contemporary Repair, Construction Specifier, April 2006. Historical use of brick in timber-framed buildings, drawing on the investigations of the Kent Tavern in Calais, VT. "Brick nogging is a European method of construction which was brought to the new world in the early-nineteenth century. It was a common construction method that employed masonry as infill between the vertical uprights of wood framing." -- quoting the web article review.
  • Photo of very rough in-wall brick nogging at an architects website
  • Building Research Council, BRC, nee Small Homes Council, SHC, School of Architecture, University of Illinois at Urbana-Champaign, brc.arch.uiuc.edu. "The Small Homes Council (our original name) was organized in 1944 during the war at the request of the President of the University of Illinois to consider the role of the university in meeting the demand for housing in the United States. Soldiers would be coming home after the war and would be needing good low-cost housing. ...  In 1993, the Council became part of the School of Architecture, and since then has been known as the School of Architecture-Building Research Council. ... The Council's researchers answered many critical questions that would affect the quality of the nation's housing stock.
    • How could homes be designed and built more efficiently?
    • What kinds of construction and production techniques worked well and which did not?
    • How did people use different kinds of spaces in their homes?
    • What roles did community planning, zoning, and interior design play in how neighborhoods worked
  • "An Example of Colonial Paneling", Norman Morrison Isham, The Metropolitan Museum of Art Bulletin, Vol. 6, No. 5 (May, 1911), pp. 112-116, available by JSTOR.
  • Dust from the World Trade Center collapse following the 9/11/01 attack: the lower floors of this building contained spray-on fire-proofing asbestos materials.
  • Energy Savers: Whole House Systems Approach to Energy Efficient Home Design [copy on file as /interiors/Whole_House_Energy_Efficiency_DOE.pdf ] - U.S. Department of Energy
  • "Energy Savers: Whole-House Supply Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Supply_Vent.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11880?print
  • "Energy Savers: Whole-House Exhaust Ventilation Systems [copy on file as /interiors/Energy_Savers_Whole-House_Exhaust.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11870
  • "Energy Savers: Ventilation [copy on file as /interiors/Energy_Savers_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Natural Ventilation [copy on file as /interiors/Energy_Savers_Natural_Ventilation.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Energy Recovery Ventilation Systems [copy on file as /interiors/Energy_Savers_Energy_Recovery_Venting.pdf ] - ", U.S. Department of Energy energysavers.gov/your_home/insulation_airsealing/index.cfm/mytopic=11900
  • "Energy Savers: Detecting Air Leaks [copy on file as /interiors/Energy_Savers_Detect_Air_Leaks.pdf ] - ", U.S. Department of Energy
  • "Energy Savers: Air Sealing [copy on file as /interiors/Energy_Savers_Air_Sealing_1.pdf ] - ", U.S. Department of Energy
  • Fiberglass: Indoor Air Quality Investigations: Health Concerns About Airborne Fiberglass: Fiberglass in Indoor Air from HVAC ducts, and Building Insulation
  • Humidity: What indoor humidity should we maintain in order to avoid a mold problem?
  • Ice Dam Leaks in building attics and roof cavities, how to inspect for evidence of leaks, identify causes, and correct bad attic ventilation, improper roof venting, and these causes of attic mold or roof structure damage
  • "Insulation: Adding Insulation to an Existing Home," U.S. Department of Energy - tips on how to do your own check for the presence of absence of insulation in a home
  • Insulation: Selecting Insulation for New Home Construction, U.S. Department of Energy - "Your state and local building codes probably include minimum insulation requirements, but to build an energy-efficient home, you may need or want to exceed them. For maximum energy efficiency, you should also consider the interaction between the insulation and other building components. This is called the whole-house systems design approach."
  • Insulation Types, table of common building insulation properties from U.S. DOE. Readers should see INSULATION R-Values & Properties our own table of insulation properties that includes links to articles describing each insulation material in more detail.
  • Mobile Home Inspections common defects unique to factory built housing, inspection methods
  • The National Institute of Standards and Technology, NIST (nee National Bureau of Standards NBS) is a US government agency - see www.nist.gov
    • "A Parametric Study of Wall Moisture Contents Using a Revised Variable Indoor Relative Humidity Version of the "Moist" Transient Heat and Moisture Transfer Model [copy on file as/interiors/MOIST_Model_NIST_b95074.pdf ] - ", George Tsongas, Doug Burch, Carolyn Roos, Malcom Cunningham; this paper describes software and the prediction of wall moisture contents. - PDF Document from NIS
  • Nogging: See this photo of exposed bricks on a building exterior on a building exterior in Canada. [Thanks to Carson Dunlop, Toronto - see References below].
  • Pergo AB, division of Perstorp AB, is a Swedish manufacturer or modern laminate flooring products. Information about the U.S. company can be found at http://www.pergo.com where we obtained historical data used in our discussion of the age of flooring materials in buildings.
  • Piquet Wall Construction: See this photo of piquet wall construction - involving timber-framed wall construction with long top girts, diagonal timber bracing, and small diameter logs placed vertically along with concrete chinking to fill in the wall plane.
  • Plank House Construction: weblog from plankhouse.wordpress.com/2009/01/25/plank-house-construction/ and where plank houses were built by native Americans, see
    Large 1:6 Scale Plank House Construction / P8094228, Photographer: Mike Meuser
    06/12/2007 documented at yurokplankhouse.com where scale model Museum quality Yurok Plank Houses are being sold to raise money for the Blue Creek - Ah Pah Traditional Yurok Village project.
  • Rubblestone Wall Filler: See this Lartigue House using exterior-exposed rubblestone filler between vertical timbers of a post and beam-framed Canadian building.
  • Manufactured & Modular Homes: Modular Building Systems Association, MBSA, modularhousing.com, is a trade association promoting and providing links to contact modular builders in North America. Also see the Manufactured Home Owners Association, MHOAA, at www.mhoaa.us. The Manufactured Home Owners Association of America is a National Organization dedicated to the protection of the rights of all people living in Manufactured Housing in the United States.
  • "Weather-Resistive Barriers [copy on file as /interiors/Weather_Resistant_Barriers_DOE.pdf ] - ", how to select and install housewrap and other types of weather resistive barriers, U.S. DOE
  • Weaver: Beaver Board and Upson Board: Beaver Board and Upson Board: History and Conservation of Early Wallboard, Shelby Weaver, APT Bulletin, Vol. 28, No. 2/3 (1997), pp. 71-78, Association for Preservation Technology International (APT), available online at JSTOR.
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com