InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • DAMAGE ASSESSMENT
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



InspectAPedia ® Home

HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of CHIMNEYS & FIREPLACES
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AGE of WATER HEATERS
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS
AIR FLOW MEASUREMENT CFM
AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTIFREEZE for BOILERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTER VALVE, HEATING SYS
BACKFLOW PREVENTER, HEATER WATER FEEDER
BACKUP HEAT for HEAT PUMPS
BANGING HEATING PIPES RADIATORS
BAROMETRIC DAMPERS
BASEBOARD HEAT
BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall
BOILERS, HEATING
BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BTU USAGE MONITORS
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CAR MOLD CONTAMINATION
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS
CREOSOTE FIRE HAZARDS
Curved Brick Chimneys - Sulphation

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS
DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEM & DUCT DEFECTS
DUST, HVAC CONTAMINATION STUDY
DUST SAMPLING PROCEDURE

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT
FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE SIZE SPECIFICATIONS
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS
HEAT LOSS in BUILDINGS
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS, DIAGNOSIS, REPAIR
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL TANKS
HEATING OIL TYPES & PROPERTIES
HEATING OIL USAGE RATE
HEATING SMALL LOADS
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES
HOT WATER HEATERS
HOT WATER IMPROVEMENT
HUMIDITY LEVEL TARGET

ICE DAM PREVENTION
INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
METHANE GAS SOURCES
MIXING / ANTI-SCALD VALVES
MIX VALVE SCALD PROTECTION, Best Practices
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS in AIR HANDLERS & DUCT WORK
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS
OIL TANK ABANDONING PROCEDURE
OIL TANKS, BURIED
OIL TANK GAUGES
OIL TANK INSPECTION REPORTS
OIL TANK LEAKS & SMELLS
OIL TANK PIPING & PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK REGULATIONS
OIL TANK REMOVAL COs
OIL TANK SAFETY
OIL TANK SLUDGE
OIL TANK STANDARDS
OIL TANK TESTING
OIL TANK TESTING COs
OIL TANK WATER REMOVAL

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS
PRESSURE REDUCING VALVES
PRESSURE REGULATOR, WATER
PUFFBACKS, OIL BURNER
PUMPS, PONY PUMPS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
REFRIGERANTS & PIPING
RELIEF VALVE LEAKS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick RepaiR
RESET SWITCH - ELECTRIC MOTOR
Reset Switch - Stack Relays

SAFETY HAZARDS & INSPECTIONS
SAFETY HAZARDS GUIDE
SAFETY, HEATING INSPECTION
SAFETY RECALLS, Chimneys, Vents, Heaters
SOLAR HEATING SYSTEM DESIGNS
SOOT on OIL FIRED HEATING EQUIPMENT
SPILL SWITCHES - Flue Gas Detection
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
STACK RELAY SWITCHES
STAIN DIAGNOSIS on BUILDING INTERIORS
STEAM HEATING SYSTEMS

TANKLESS COILS
Thermal Expansion Cracking of Brick
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
THERMAL IMAGING, THERMOGRAPHY
THERMAL IMAGING MOLD SCANS
THERMAL MASS in BUILDINGS
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
THERMOSTATS, WATER HEATER
THERMOSTATIC EXPANSION VALVES
Transite Pipe Chimneys & Flues

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WATER SOFTENERS & CONDITIONERS
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE VALVES

More Information

Flood waters rising at Wappingers Creek (C) Daniel FriedmanFlood Damage Repairs for Heating Systems
How to restore flooded heating boilers, furnaces, water heaters
     

  • Guide to repairing flooded heating & water heating equipment: what items should be inspected, replaced, or repaired on an oil fired boiler, furnace, or water heater that has been wet or flooded?
  • How do I get my oil or gas fired water heater, boiler, or furnace running again after building flooding?
    • AIR HANDLERS: air conditioning & warm air furnace flood or storm restoration steps
    • BOILERS: hot water or steam heating system flood or storm restoration steps
    • BASEBOARD heat or RADIATORS inspection & restoration after a flood
    • CHIMNEYS: check the chimneys, flues, and vents after building flooding or other disasters
    • COMBUSTION CHAMBER & chamber liner: dry or replace after flooding
    • CONTROLS on heating equipment: how to inspect, test, or (usually) replace after flooding
    • DUCT SYSTEM FLOOD or WATER DAMAGE - separate article
    • GAS BURNERS & Gas Fuel System & gas piping & appliance checks after building flooding or other disaster
    • INSULATION in air handler, boiler, furnace or water heater insulation inspection & cleaning/replacement after a flood or other disaster
    • OIL FIRED HEATERS: oil burner, fuel unit oil filter & oil piping, valves & oil tank restoration to service after building flooding or other disaster
    • PRESSRUE TEMPERTURE RELIEF VALVE assembly inspection & restoration after a flood or other disaster
    • WATER HEATERS: Checks & tests for restoring a flooded or storm damaged water heater to service
  • Different depths of flooding have different implications for inspection & repair of heating appliances after hurricanes, rising flood waters, burst pipe leaks, of sewer backups - Recommended safety checks, inspections, & repairs for flood-damaged water heaters, boilers, furnaces
  • DIAGNOSE & FIX HEATING PROBLEMS-BOILER - separate article
  • DIAGNOSE & FIX HEATING PROBLEMS-FURNACE - separate article
  • ELECTRIC WATER HEATERS & GAS FIRED WATER HEATERS - separate articles
  • FLOOD DAMAGE in DUCT WORK - separate article
  • Questions & Answers about cleaning & repairing flooded heating equipment: oil & gas or electric boilers, furnaces, water heaters
  • References

Click to Show or Hide Related Topics

  • BUILDING DAMAGE ASSESSMENT & REPAIR - home
  • BUILDING ENTRY for DAMAGE ASSESSMENT
  • CAR, FLOOD DAMAGE DETECTION
  • CRAWL SPACES
  • DRINKING WATER - EMERGENCY PURIFICATION
  • DRINKING WATER - EMERGENCY SOURCES
  • DUCT SYSTEM FLOOD or WATER DAMAGE
  • EARTHQUAKE DAMAGE
  • ELECTRICAL SAFETY for FLOOD INSPECTORS
  • FIRE DAMAGED BUILDINGS
  • FLOOD DAMAGE REPAIR PRIORITIES
  • FLOOD DAMAGE CLEANUP & REPAIR GUIDE - home
  • FLOOD VENTS & FLOOD PORTS
  • FLOOD ZONES & FLOOD ZONE MAPS
  • FOUNDATION CRACKS & DAMAGE GUIDE
  • FOUNDATION DAMAGED by EARTHQUAKE
  • FOUNDATION DAMAGED, by FLOODING
  • FRAMING DAMAGE, INSPECTION, REPAIR
  • GAS DETECTION INSTRUMENTS
  • GAS, METHANE SOURCES
  • GENERATORS, BACKUP ELECTRIC
  • HEATING EQUIPMENT, FLOOD DAMAGE REPAIR
  • HOUSING, EMERGENCY & TEMPORARY
  • HUMIDITY CONTROL & TARGETS INDOORS
  • MOBILE HOMES, DOUBLEWIDES, TRAILERS
  • MOLD CONTROL, FLOOD RESPONSE
  • MOLD PREVENTION STEPS
  • OIL TANK WATER REMOVAL
  • OIL TANKS FLOATING UP
  • PUMPS, PONY PUMPS
  • ROOF DAMAGE, WIND
  • SAFETY for BUILDING INSPECTORS
  • SEPTIC SYSTEM FLOOD DAMAGE REPAIR
  • SEWAGE BACKUP, WHAT TO DO
  • SEPTIC SYSTEM PUMPS
  • SEWAGE BACKUP, WHAT TO DO
  • SEWAGE CONTAMINATION in BUILDINGS
  • SEWAGE PUMPS
  • SEWER BACKUP PREVENTION
  • SEWER GAS ODORS
  • SUMP PUMPS
  • TOILETS for DISASTER ZONE USE
  • TOILETS, EMERGENCY
  • WATER ENTRY in buildings
  • WATER HEATER FLOOD DAMAGE REPAIR
  • WELL FLOOD DAMAGE REPAIR
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

How to clean & restore flooded heating equipment or a flooded water heater to service: this article describes procedures for inspection and repair of flooded heating appliances: flooded heating boilers, furnaces, and water heaters. We list and describe procedures for every post-flood inspection and repair point for air conditioner air handlers, boilers, furnaces, and water heaters. Area flooding due to storms or building flooding due to a fire or burst water pipe can leave heating appliances inoperative as well as unsafe to use unless adequate inspection, cleaning, and repair or replacement of certain parts are made. This article series on oil hot water heat will answer most questions about oil-fired water heaters as well as many other building plumbing system inspection or defect topics. Our page top photos shows a client pointing to the level reached by flood waters in a building basement - the heating boiler, water heater, and other basement appliances had been inundated with muddy water from area flooding.

Green links show where you are. © Copyright 2013 InspectAPedia.com, All Rights Reserved. Author Daniel Friedman.

Flood Response: Inspection & Repair Advice for Flooded Heating Boilers, Furnaces, Water Heaters

Flooded heating boiler (C) Daniel FriedmanThis article describes air conditioning & heating system components that you need to inspect, clean, repair or replace after the equipment has been partially or completely flooded or otherwise damaged by a flood or other disaster.

For each component we explain what needs to be done to safely return the component and the system to safe reliable operation to provide building heat or hot water.

We include links to articles giving further details about cleaning, troubleshooting, or repair if needed.

How to Restore Heating Systems or Water Heaters to Operation after a Flood or Other Disaster

Question: How do I get my oil fired water heater, boiler, or furnace running again after building flooding?

I am having problems restarting the water heater ever since hurricane irene slammed into New Jersey and my basement flooded. We changed the motor and oil filter, but are having problems getting oil to feed through the lines I was wondering if there were suggestions. - Antoinette

Reply: recommended inspection & cleaning, replacement or repair points for oil fired water heaters, heating boilers, furnaces after a flood or other disaster

Water Heater Details (C) Carson Dunlop AssociatesWhen an oil fired water heater has been flooded, such as by hurricane Irene that flooded the Northeastern U.S. in August 2011, there are a number of concerns that need to be addressed.

Before addressing flooded water heaters, boilers, or furnaces, if your building has been flooded, see FLOOD DAMAGE ASSESSMENT, SAFETY & CLEANUP for advice about priorities of entry, diagnosis & repair of homes or other buildings after flooding from any cause.

CMHC provides this nice summary statement, for which we provide actual how-to details in this article:

If they have been soaked, consult an HVAC (Heating,Ventilation and Air Conditioning) contractor to replace the furnace blower motor, switches and controls, insulation and filters.

Inspect all flooded forced air heating ducts and return-duct pans and have them cleaned out or replaced. Seek advice from your local utility about a water heater that has been wet. Refrigerators and freezers may need to be replaced. [8]

Now to the flooded water heater: you report having taken two important post-flood steps by changing parts (motor and oil filter) but below we have listed suggestions that might help get the water heater (or a flooded heating boiler or furnace) running again and also assure its safety and forward life.

The extent of disassembly, inspection, and replacement of parts of any heating appliance (water heater, furnace, boiler) after building flooding depends on the height reached by floodwaters and perhaps also the duration of flooding.

Our flood damage photo at the top of this page shows our client pointing to flood water markings on the heating system expansion tank - water had nearly filled the basement of this home - the heating boiler had been completely under water. Our oil fired water heater sketch (left, - Courtesy Carson Dunlop Associates, used with permission) shows the internals of that appliance and illustrates what gets wet at different flood water levels.

Certainly any water heater, boiler,or furnace component that was under-water or soaked needs to be inspected, and as appropriate, cleaned or replaced. On the other hand, basement flooding that did not even reach the level of the oil burner assembly may have left that component intact, but still may have entered and damaged the heating appliance combustion chamber.

We list and describe procedures for every post-flood inspection and repair point for air conditioner air handlers, boilers, furnaces, and water heaters in the text below.

Air conditioning & warm air furnace flood or storm restoration steps: Check the air handler, blower assemblies, filters, & duct system of air conditioning or warm air heating systems after flooding or other disasters

Gas furnace schematic (C) Carson Dunlop Assoc.

The level of cleaning, repair or replacement of a flooded air handler used for air conditioning or warm air heating depends on the depth to which the unit was flooded and on just what components have become wet or flooded.

If the heating equipment was exposed to just a wet floor or even an inch of water it may be possible to quickly return the system to operation. But if the heating equipment was soaked (such as during extinguishment of a fire) or flooded (by rising floodwaters) then its safety controls, motors, switches, combustion chamber and other components that were wet or flooded will need cleaning, repair, or replacement, as we will describe below.

For detailed assistance with heating or cooling equipment that won't run after you've cleaned and replaced parts, see these articles:

  • DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
  • DIAGNOSE & FIX HEATING PROBLEMS-FURNACE - what to check if the furnace won't run or is not working properly
  • FURNACES, HEATING - flooded air handlers and blower assemblies need to be cleaned, sanitized, lubricated, controls replaced, motors checked, tested, possibly replaced

The sketch at left illustrates basic parts of a conventional gas fired warm air heating furnace; image courtesy of Carson Dunlop Associates.

Boilers: hot water or steam heating systems: check the boiler, controls, combustion chamber, fuel system after flooding or other disasters

Flood line on heating equipment (C) Daniel FriedmanFlood line on heating equipment (C) Daniel Friedman

The level of cleaning, repair or replacement of a flooded air handler used for air conditioning or warm air heating depends on the depth to which the unit was flooded and on just what components have become wet or flooded. We discuss gas burners or oil burners separately below.

Our photo (above right) shows that the oil fired heating boiler was flooded enough to place all of the oil burner key parts under at least some water - this system should not be operated before it is cleaned and restored by an expert.

Our photo (above left) provides two heating equipment flooding observations

  1. The heating boiler or furnace was set up on blocks, a clue that someone was aware of at least the possibility of exposure of the heater to wet floors - which in turn tells us that the building may have had a history of water entry and wet basement or floors
  2. The heater was recently flooded to about 4-inches above the unit's base - possibly floodwaters did not reach the oil or gas burner itself.

For detailed assistance see these articles:

  • DIAGNOSE & FIX HEATING PROBLEMS-BOILER - what to check if the hot water or steam boiler won't run or doesn't work properly
  • BOILER CONTROLS & SWITCHES (many controls on oil fired heating boilers are the same on oil fired water heaters)

What oil fired water heater or boiler parts are usually replaced after a building flood or similar fire or disaster?

Safety controls (see below) and insulation in heating equipment are usually replaced after flooding or other wetting disaster events like hurricanes or storms.

Baseboard heat or radiators inspection & restoration after a flood or other disaster

Oil fired water heater with a backpressure sooting problem (C) Daniel Friedman

 

Inspect the heating piping, baseboards, or radiators for leaks or mechanical damage, especially if there is any evidence of movement of or in the building.

If hot water heating system pipes were drained or if pipes broke and lost water, you will need to purge air from the system and to check circulator pump(s) and zone valves (if used);

If pumps or valves or control relays were submerged most heating service professionals will replace controls and will dry and test electric motors before returning them to service.

See AIRBOUND HEAT SYSTEM REPAIRS for assistance with purging air out of heating piping, baseboards, or radiators.

Chimneys: check the chimneys, flues, and vents after building flooding or other disasters

A cracked, plugged, or leaky chimney can cause fires or carbon monoxide poisoning.

Be sure you check metal and brick chimneys for cracks, damage, signs of movement, as well as for obstructions by dirt, debris. Also check for visible gaps, or leaks before lighting the furnace or a fire.

In addition, a thorough inspection of the combustion chamber for damage and debris must be conducted before the equipment is returned to service. Mud, sludge, debris anywhere inside of the heating appliance (combustion chamber, heat exchanger, chimneys, flues) has to be removed and the appliance cleaned. In addition, if area flooding sent flood waters inside of chimneys or flues (don't forget the chimney base and cleanout door) those areas need to be opened, inspected, cleaned.

  • For a complete guide to chimney inspection, diagnosis & repair see CHIMNEY INSPECTION DIAGNOSIS REPAI

Combustion chamber & chamber liner: dry or replace after flooding

Most oil fired heating equipment use a masonry (fire brick) or synethetic fabric combustion chamber liner. The liner heats to very hot during oil burner operation - a condition that helps assure complete combustion of fuel oil being sprayed into the combustion chamber.

Watch out: Firing up a flooded oil fired heating appliance before the combustion chamber liner has been dried or replaced risks damaging that component and possibly damaging the heater itself. Ask your service technician about the condition of the combustion chamber.

Controls on heating appliances: inspect, test, or (usually) replace after flooding

Photograph of  a modern oil-fired heating boilerHeating appliance (water heater, boiler, furnace) safety and limit switches and controls that have been flooded, in our OPINION, should be replaced. These include controls such as an aquastat, cad cell relay, stack relay, or fan limit control switch.

Circulator pump relays, while not safety devices themselves, may be inoperable after flooding without disassembly, dryout and cleaning - a procedure that may cost more than the cost to replace the control. Other electrical components such as electrical wiring may be re-usable after inspection.

Watch out: electrical panels and circuit breakers that have been flooded should be replaced as even if they "look" fine, we're not confident that internal working parts have not been damaged by water, corrosion, or even silt and debris. The risk is that a flooded circuit breaker has become mechanically damaged or corroded internally such that it may not trip properly in response to an overcurrent or short circuit that may occur when you are restoring power to the building or later in the future. The risk is thus a shock or fire.

  • Aquastat Functions - simple aquastats may be used as upper and lower limit controls on oil fired water heaters
  • BOILER CONTROLS & SWITCHES (many controls on oil fired heating boilers are the same on oil fired water heaters)
  • Cad Cell Relay Switch Flame Sensors - turns off the oil burner if it does not achieve proper flame ignition
  • Circulator Pumps & Relays - may be used if the water heater is connected to a continuous hot water loop plumbing system or in (more rare) cases where an oil fired water heater is being used as a building area heating device (usually not code-approved)
  • Limit Switches, Boilers combination aquastats or single-limit simple aquastats may be used as upper and lower limit controls on oil fired water heaters
  • RELIEF VALVES - TP VALVES - required on every pressurized tank, including oil fired water heaters
  • Reset Switch - Heater Primary Control
  • RESET SWITCH - ELECTRIC MOTOR
  • Stack Relay Switch - an older safety switch used to turn off the oil burner if successful burner flame ignition does not occur

Ductwork inspection & restoration after a flood or other disaster

The inspection points listed above pertain to oil fired heating devices that have been exposed to flooding or sewer backups. In addition, for building heating systems, the heat distribution system may also have been flooded, damaged, or require repairs and cleaning.

  • See FLOOD DAMAGE in DUCT WORK - flooded ducts need to be cleaned and sanitized and air filters replaced;

Gas Burners & Gas Fuel System & gas piping & appliance checks after building flooding or other disaster

If the gas has been turned off at the main valve serving your home, you need to have a professional restore gas service to your home, relight pilot lights, and do a final check of the system.

If the gas valve serving only one appliance is turned off, then you can probably turn gas service back on, check for leaks, and then relight that appliance.

First, make sure the room is well-ventilated (open windows & doors to outside) and that there are no open flames anywhere. Then turn on the gas valve. Check for leaky pipes. Let the gas run for a minute or two to clean any air and impurities out of the pipes. Then turn the gas off for a minute to allow the gas in the air to go away before you light the appliance.

Watch out: if you smell gas, do not turn on or off electric switches, use a telephone or cell phone, nor use any other equipment or control that can create even the smallest spark. Doing so risks a catastrophic gas explosion.

For detailed assistance see these articles

  • GAS BURNER Flame & Noise Defects
  • GAS FIRED WATER HEATERS
  • GAS PIPING, VALVES, CONTROLS
  • TANKLESS WATER HEATERS

Propane, L-P, and Butane Heating Equipment & Systems

Propane, LP gas, or butane fuels are kept in pressurized tanks, so there is no electric pump to turn on, and provided that the tank was not empty, no flood water would be expected to enter the tank.

Watch out: check the gas tanks for signs of movement or floating. If the tank has moved at all from its original position, inspect the gas piping for loose or damaged connections, and repair them before attempting to turn on the gas.

Then follow the instructions above for gas systems.

Oil System oil burner, fuel unit, oil filter & oil piping checks after building flooding or other disaster

Oil burner assembly inspection & restoration after a flood or other disaster

In the reader question above s/he said that the "motor" was replaced. If you are not sure whether just the electric motor on the oil burner was replaced or whether the whole oil burner assembly was replaced, see OIL BURNERS for an illustration of the different parts involved. If the oil burner was submerged, and if only the oil burner's driving electric motor was replaced, additional disassembly and cleaning are probably in order to be sure that the oil burner nozzle, blower assembly, and other parts are clean and working properly.

Make sure your main oil valve is turned off. Check your heating oil oil pump and oil burner assembly. If it got wet, have the oil burner and pump professionally checked and cleaned. If you want to clean it yourself, keep in mind that you will need replacement parts like oil burner nozzle, fuel unit screen, oil filter cartridge, and a clean heating oil supply ready to use when bleeding air and water from the system.

Look carefully for any signs of leaking oil; if you see any, call a professional. Look for signs that the pipes or oil tank moved during the flood. Oil tanks, even buried ones, will float when flooded. After you have turned the electricity back on, open the main valve and turn the pump on. Check for leaky pipes.

The amount of cleaning and parts replacement necessary for a heating system depends on the depth of flooding to which the equipment was exposed. A heating boiler or furnace whose oil or gas burner was not submerged may be got running with a careful cleaning and inspection of the combustion chamber and (if hot air heat) duct system, and chimney. But if the oil or gas burner was flooded it will need to be disassembled, cleaned, some controls and parts replaced, and tested.

Watch out: Rather than risk the fire or safety hazards that ensue if a heating system safety control is not reliable, heating professionals will generally replace any heating system control (like an aquastat, cad cell relay, stack relay) that has been soaked or submerged.

This article continues to list all of the major components of oil fired heating equipment and how they should be cleaned, inspected, repaired or replaced after a flood or other disaster.

For detailed assistance with oil burner inspection, cleaning, repairs see:

  • OIL BURNER FUEL UNIT - this is the oil pump on your oil burner
  • OIL BURNER INSPECTION & REPAIR - home page for oil burners
  • OIL BURNER NOZZLE & ELECTRODES
  • OIL FILTERS on HEATING EQUIPMENT & OIL LINE CLOGGING FIX & OIL LINE SAFETY VALVES
  • OIL TANK FLOATING UP & OIL TANK INSPECTION, ABOVE GROUND
  • OIL TANK PIPING & PIPING DEFECTS
  • OIL TANK WATER CONTAMINATION & OIL TANK WATER REMOVAL
  • RELIEF VALVE LEAKS & RELIEF VALVES - Water Heaters
  • Reset Switch - Heater Primary Control
    Reset Switch Broken - Quick RepaiR
    RESET SWITCH - ELECTRIC MOTOR
    Reset Switch - Stack Relays

Oil filter assembly inspection & restoration after a flood or other disaster

It makes sense to replace an oil filter cartridge after a building has been flooded; the cartridge canister is normally air tight and thus water tight. But repair steps, movement of equipment, or other events may have contaminated the canister itself or oil tank or piping, sending more debris into the canister and filter. For this reason it makes sense to not just replace the filter, but inspect and clean the canister that holds the filter.

Remove the oil filter cartridge and replace it; we don't recommend operating the heating equipment without a cartridge and filter in place because of the high probability of debris clogging that will occur in the oil pump or oil burner nozzle. Remove any water found in the oil filter canister as well as sludge or debris before you replace the oil filter with a new one.

  • See FILTERS, OIL on HEATING EQUIPMENT for detailed assistance.

Oil pump (fuel unit) internal filter screen assembly inspection & restoration after a flood or other disaster

Debris, sludge, water, rust particles are often found in the bottom of the oil filter canister. If these enter the oil burner's oil pump (properly, the fuel unit), its internal filter screen may also be clogged - I'd be sure that the fuel unit has had its filter screen replaced.

Debris in the oil burner fuel unit will clog its internal check valves and the oil burner nozzle too, damaging the pump and leading to improper, even unsafe oil burner operation or total loss of heat later on. Also a clogged filter screen can prevent the fuel unit from being able to pump oil from the tank - and could be mistaken for a blocked oil line.

  • See OIL PUMP FUEL UNIT for details.

Oil piping: How to check & repair heating oil piping on flooded water heaters, boilers or furnace after a flood or other disaster

If oil piping has become contaminated with sludge, it may be possible to blow the lines clear, but if not, oil line replacement will be needed unless the piping has been broken, kinked or mechanically damaged (as can occur if flooding cause an oil tank to float or move).

Oil lines between an oil tank and the water heater can become blocked with sludge, silt, mud, and even water or sewage if the lines are open to the flooding environment. If you have this problem, when the oil burner motor runs (the oil fuel unit is trying to pump oil) and you try to bleed air from the oil piping system you will find that no fuel is flowing from the oil tank to the burner motor.

  • Check that there is heating oil in the oil storage tank; check the oil tank gauge and check that the gauge is not stuck showing fuel on an empty tank. (OIL TANK GAUGES)
  • Check that the oil safety valves are properly opened - watch out these valves turn backwards from what you expect. (OIL LINE SAFETY VALVES)
  • Check for water in the oil tank and remove it if present (OIL TANK WATER REMOVAL)
  • Check that the oil filter is not clogged (OIL FILTERS on HEATING EQUIPMENT)
  • If the oil line is clogged see OIL LINE CLOGGING FIX for repair procedures.
  • On occasion the filter screen inside the oil burner fuel unit (oil pump) can become clogged (OIL PUMP FUEL UNIT)

But normally an oil line between the oil tank and oil burner, say at a water heater, is always full of fuel oil, and sealed against oil leaks out and air leaks in to the piping system. So dirt or water from outside the system would not easily enter the piping system.

How to bleed the oil piping properly to remove air from the system

Also be sure the service tech was following proper procedure for bleeding air out of the oil piping during service restoration. Details are at How to bleed air out of oil piping and oil burner fuel units.

  • For details on oil burner fuel unit installation, piping connections, controls, cleaning procedures, & how to bleed air out of an oil burner fuel unit and piping, see OIL BURNER FUEL UNIT.
  • Details about spotting oil or air leaks in oil piping are found at OIL LINE LEAKS.
  • Our complete guide to heating oil piping begins at OIL TANK PIPING & PIPING DEFECTS.

Oil tanks: heating oil storage tank check for floating up, movement, leaks, debris or water contamination after a flood or other disaster

So how might debris enter and clog oil piping after a building flood? If the oil tank itself were flooded you might have water and mud or silt and dirt on the tank bottom - if your oil line feeds from the tank bottom all of that crud would enter the oil line. So a further check of the condition of the oil tank is in order.

A buried oil tank should, like the oil piping, be sealed against outside water entry (though in times of area flooding a partially empty oil tank might float-up and break lines or cause leaks).

Watch out: if a buried oil tank or even an above ground oil storage tank was not sufficiently full of oil during area flooding the tank may have floated up out of the ground or off of its (above ground oil tank) supports. The result of such movement will be bent, damaged oil piping, possibly leaks and an oil spill, and water and debris may have entered the oil storage tank. See

  • OIL TANK FLOATING UP
  • OIL TANK INSPECTION, ABOVE GROUND

An above ground oil tank should be ok IF flood waters never rose high enough to enter the oil tank vent or fill piping.

If your oil tank itself checks out as not contaminated with water and dirt, and provided we are sure that the oil burner assembly was itself entirely replaced and that the oil pump (fuel unit) is working properly, and if you are unable to draw oil from the tank, the usual step employed by the service tech is to use a CO2 gas cartridge and special "gun" assembly that connects to the oil line and attempts to "blow out" an obstruction. If you are unable to make the line usable following that procedure, and provided we remain convinced that the line is the culprit, I'd have the service company run a new fuel line between the oil tank and the burner. Details are at OIL TANK WATER REMOVAL and at OIL LINE CLOGGING FIX

Oil valves: check the heating oil supply valves (fire safety valves or fire-o-matic valves) for proper position (opened)

A fusible link oil piping shutoff valve should be found at the oil burner (just before the oil filter) and perhaps also at the oil storage tank. A valve at the oil tank is often used for service convenience if the oil piping exits at the tank bottom. If oil piping or the oil tank were open to floodwaters debris often collects right at the control valve. See FIRE SAFETY CONTROLS for a discussion of oil piping fire safety valves.

Pressure temperature relief valve assembly inspection & restoration after a flood or other disaster

this important safety device should be flushed and tested as per the manufacturer's instructions. Dirt or debris in the relief valve interior could prevent its proper operation or, more often, it can cause the valve to leak if it has not been adequately cleaned.

See these detailed articles on relief valves

  • RELIEF VALVE LEAKS
  • RELIEF VALVES - TP Valves on Boilers
  • RELIEF VALVES - STEAM TP VALVES
  • RELIEF VALVES - Water Heaters
  • RELIEF VALVES - Water Tanks

Insulation in air handler, boiler, furnace or water heater insulation inspection & cleaning/replacement after a flood or other disaster

Most heating appliances (water heaters, furnaces, boilers) include an insulated outer jacket or "skin" that helps keep heat and noise inside the device and that improve its operation.

If the insulation on a flooded appliance is still wet when the appliance is turned back on you might get lucky and dry it out during the next operating cycle. Or equipment might be damaged, or the insulation might need replacement. Ask your service technician about the condition of the appliance insulating jacket.

Watch out: flood waters in a disaster often contain sewage and other pathogens that can enter and contaminate any kind of building or appliance insulation. You might, at least temporarily, take a chance on using an appliance like a water heater whose insulation was partly wet, but floodwater contaminated insulation in equipment like an air handler or inside of duct work that is made of or lined with fiberglass insulation is unsanitary. Blowing air from an air conditioner or heater into a building through pathogen-contaminated ductwork or air handlers is unsanitary and risks illness or disease. Such components should be replaced.

Flood Damaged Water Heaters: Checks & tests for restoring a flooded or storm damaged water heater to service

Schematic of a sacrificial anode on a hot water tank (C) Carson Dunlop

To get a water heater working after flood, hurricane, earthquake or other disaster damage the steps needed depend on the type of heater that you have installed. Most likely in all cases of tank type water heaters you'll want to drain and possibly sanitize the tank along with building water supply piping as well as flush and test (or replace) the pressure / temperature relief valve and discharge tube.

For gas or oil fired heaters, see the fuel and burner inspection and restoration procedures listed in this article. For other types of hot water equipment see or home page at x or see

  • ELECTRIC WATER HEATER ELEMENT TESTS
  • Electric Water Heater Checklist
  • INDIRECT FIRED WATER HEATERS
  • TANKLESS COILS
  • TANKLESS WATER HEATERS

For additional water heater inspection & cleaning procedures also see

  • BOILER CONTROLS & SWITCHES (many controls on oil fired heating boilers are the same on oil fired water heaters)
  • DRAIN a WATER HEATER TANK
  • MIXING / ANTI-SCALD VALVES - used to permit keeping the water heater at high temperature (more total hot water will be available) without risking scalding the building occupants
  • THERMOSTATS, WATER HEATER
  • TIMERS for ELECTRIC WATER HEATERS
  • WATER HEATER SCALE - De-Liming Procedure
  • RELIEF VALVES - Water Heaters - also See Testing the Water Heater Temperature Pressure Relief Valve

Here Carson Dunlop's sketch shows the location of the sacrificial anode on an electric water heater. If your hot water smells like rotten eggs, you should definitely check the condition of the sacrificial anode on the hot water heater, no matter what kind of water tank you've got installed. For details of how to inspect or replace the sacrificial anode or dip-tube on a water heater, please see Water Heater Anodes & Dip Tubes

...


Frequently Asked Questions (FAQs) about how to restore a flooded heater or water heater to service

...

Ask a Question or Search InspectApedia

Questions & answers or comments about cleaning & repairing flooded heating equipment: oil & gas or electric boilers, furnaces, water heaters - equipment that has been subject to flooding or water damage.

Ask a Question or Enter Search Terms in the InspectApedia search box just below.

Technical Reviewers & References

Related Topics, found near the top of this page suggest articles closely related to this one.

  • [1] "Repairing your Flooded Home", American Red Cross & FEMA: Federal Emergency Management Agency, FEMA PO Box 2012, Jessup MD 20794-2012. Printed copies of this book are available from the American Red Cross, from your local Red Cross chapter, or by writing to the address above. Web search 10/4/2010, original source: http://www.redcross.org/www-files/Documents
    /pdf/Preparedness/file_cont333_lang0_150.pdf
  • [2] The following are available free from: Federal Emergency Management Agency Attn: Publications P. O. Box 2012 Jessup, MD 20794-2012
    • Design Manual for Retrofitting Flood-prone Residential Structures, FEMA-114. This detailed manual explains all the floodproofing options in language a homeowner can understand.
    • Elevated Residential Structures, FEMA-54.
    • Floodproofing Non-residential Structures, FEMA-102.
    • Coastal Construction Manual, FEMA-55.
    • Manufactured Home Installation in Flood Hazard Areas, FEMA 85.
  • [3] The following are available for free from: U.S. Army Corps of Engineers Attn: CECW-PF 20 Massachusetts Avenue, NW Washington, D.C. 20314
    • Introduction to Flood Proofing, John R. Sheaffer, 1967
    • Flood-Proofing Regulations, U.S. Army Corps of Engineers, Pittsburgh District, 1990, 80 pages (Corps publication EP 1165 3 314).
    • Flood Proofing Systems & Techniques, L.N. Flanagan, editor, 1984
    • Flood Proofing Tests, Tests of Materials and Systems for Flood Proofing Structures, Corps of Engineers, National Flood Proofing Committee, August, 1988.
    • Raising and Moving the Slab- On-Grade House, Corps of Engineers National Flood Proofing Committee, 1990.
  • [4] The following publications are available from the American Red Cross. Contact your Red Cross chapter for more information:
    • Your Family Disaster Plan (ARC 4466)
    • Su plan para el hogar en caso de desastres (ARC 4466S)
    • Your Family Disaster Supplies Kit (ARC 4463)
    • Su Equipo de suministros para la familia en caso de desastres (ARC 4463S)
    • Safe Living in Your Manufactured Home (ARC 4465)
    • Are You Ready for a Flood or Flash Flood? (ARC 4458)
    • ¿Está preparado para una inundación or inundación súbita? (ARC 4458S)
    • Are You Ready for a Hurricane? (ARC 4454)
    • ¿Está preparado para un huracán? (ARC 4454S)
  • [5] Clean up References Many Cooperative Extension Service offices have home economists and food and farm experts. Check your telephone book under the county name. For example, if you live in Pittsburg County, check under “Pittsburg County Cooperative Extension Service”.
  • [6] Questions on cleaning or disinfecting of specific materials can be answered by manufacturers of cleaning products. Check the product labels for toll free telephone numbers.
  • [7] References on technical aspects of floodproofing can be located through the Floodplain Management Resource Center, a free service provided by the Association of State Floodplain Managers. Call 303/492-6818
  • [8] CMHC, Canadian Mortgage and Housing Corporation, "After the Flood — A Homeowner’s Checklist", retrieved 10/21/2012, original source http://www.cmhc-schl.gc.ca/en/co/maho/em/em_001.cfm [copy on file as After_The_Flood_CMHC.pdf]
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-747-7747 or by Email: johncranor@verizon.net
  • Carson, Dunlop &
Associates Ltd., TorontoCarson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. The firm provides professional home inspection services & home inspection education & publications. Alan Carson is a past president of ASHI, the American Society of Home Inspectors. Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides:
    • Commercial Building Inspection Courses - protocol ASTM Standard E 2018-08 for Property Condition Assessments
    • Home Inspection Education Courses including home study & live classes at eleven colleges & universities.
    • Home Inspection Education Home Study Courses - ASHI@Home Training 10-course program.
      Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITP in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference Book, a reference & inspection report product for building owners & inspectors.
      Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.
    • The Home Reference eBook, an electronic version for PCs, the iPad, iPhone, & Android smart phones.
      Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter inspectaehrb in the order payment page "Promo/Redemption" space.
    • The Illustrated Home illustrates construction details and building components, a reference for owners & inspectors.
      Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILL in the order payment page "Promo/Redemption" space.
    • The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones.

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson DunlopThe Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume. Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRB in the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The Home Reference eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones. Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRB in the order payment page "Promo/Redemption" space.
  • ...

HOME ABOUT CONTACT COPYING DESCRIPTION POLICIES PRINTING PRIVACY © 2013 Copyright InspectAPedia.com