Building Inspection, Diagnosis & Repair Info

Sooty gas burner (C) Daniel FriedmanSoot Hazards in Buildings

This article describes health and safety concerns for people in buildings where there is visible soot that may be traced to gas appliances, fireplaces, oil burners, or other sources.

We also discuss best DIY methods for cleaning up soot deposits on building surfaces and materials.

Watch out: if your gas fueled heater or appliance is producing soot it may also be releasing fatal carbon monoxide gas. Turn off suspect equipment and be sure you have working smoke and CO Carbon Monoxide detectors in your building.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Are Soot or Soot Stains in Buildings Dangerous?

Photograph of  thermal tracking or soot tracking - cool surface, moisture condenses, soot is deposited - Daniel Friedman 02-12-16 Airborne soot particles

are a serious health hazard that, at 2021 U.S. standards for allowable exposure to airborne soot (12 mcg/L), is associated with 45,000 deaths a year in that country alone.

Because of their small size, in the 2.5 micron range, soot particles are breathed deeply into the lungs and are contributors to respiratory illness, strokes, and heart attacks. Airborne soot is a particular concern in urban areas and particularly affects black and brown communities whose housing tends to be closer to soot-producing industrial areas.

In 2021 the US EPA plans to review its standards for allowable airborne soot exposure.

Experts note that if the allowable soot level were dropped from its present 12 mcg/L down to 9 mcg/L the result would cut soot-related deaths in the U.S. by about 12,150 each year. - NY Times, 11 June 2012

Visible soot deposits:

Here, however, we address a less-widely-understood soot hazard: the presence of visible soot or soot deposits in building.

Dark sooty stains on ceilings, walls, or other surfaces may indicate unsafe heating equipment, a more-immediate hazard, or it might indicate other troublesome building conditions that are not safety hazards such as poor insulation, air leaks, or high moisture levels.

Unsafe heating equipment:

Above we warned about sooting gas fueled heaters - that can be quite dangerous because it indicates unsafe heater operation, risking both fatal carbon monoxide poisoning from malfunctioning gas heaters.

Similarly dangerous, a soot-producing oil burner offers the risk of a dangerous oil burner puffback explosion.

Building insulation, air leaks, moisture levels:

Soot or dark ghosting stains on building ceilings and walls may not, however originate with heating equipment but might instead tell us about faults in the building's insulation, air leakiness, and indoor moisture.

All three of those, in turn, speak to building comfort, heating and cooling costs, and to more subtle hazards like moisture-related hidden mold contamination.

Photo: severe dark ghosting stains or "thermal tracking" on building walls.

Sooty dark indoor stains may be due to more normal building activities: smoking, use of scented candles, dusty pets, even sooty outdoor air in some cities.

Watch out: also from HUD, cited below:

Smoke, soot and ash are serious health hazards.

Ash can act as a skin irritant. Soot particles can float in the air and are an irritant to the respiratory system.

Oily soot can contain toxins. As the heat of a fire increases, soot becomes pressurized and forced into small cracks, crevices and into surface finishes.

Smoke, soot and ash stain materials and can become trapped in window tracks, gutters, insulation, air conditioner equipment, vents, ducts and exterior drains.

Vertical black stripe stains on walls are most likely thermal tracking or ghosting (C) InspectApedia Really? Well, no. Not necessarily. While heavy indoor soot deposits from any source and oil burner soot particles in particular may be hazardous, that does NOT mean that typical light soot deposits such as those that map wall studs or ceiling joists are themselves capable of releasing enough particles into indoor air as to form a hazard.

See details at GHOSTING DARK STREAKS or LINES: CAUSES to diagnose lines or rectangular areas of stains on walls or ceilings

But Watch out: if you're seeing heavy soot deposits like those shown above, and if you've not already found and fixed the cause of that sooting on walls or ceilings, there could be very dangerous conditions in your building such as

See details at

Reader Question: are ghosting stains from a woodstove dangerous to building occupants?

Relating to “ghosting” from a woodstove seen on walls in house, is there reason to think this may present a health hazard to occupants?

The ghosting in our house cannot be smelled (unlike some houses of cigarette smokers), so was curious about wood smoke. I’ve repainted stove room and no issue with any stains bleeding through.

I’ve since put in an air purifier with HEPA filter in stove room and am considering a MERV 13 filter in box fan.

I may have to raise height of chimney as well. I realize that it’s site unseen, but curious what you think in general about the health piece.

This Q&A were posted originally

at WALL STAIN DIAGNOSTIC FAQs

Moderator reply: stains on the walls are probably not harmful but look further at building conditions

Debris particles including soot (C) Daniel Friedman at InspectApedia.comThank you for the helpful ghosting stains vs soot hazards question.

Photo: particle analysis n our forensic laboratory; those round black spheres of two sizes might be soot but as you'll see below, products of combustion often produce light, irregularly-shaped soot particulates. Top-lighting and more examination of these particles would be needed to complete identification.

There is ample research document in health hazards and air quality concerns with soot is airborne and thus breathed by people or other animals.

Soot particles are extremely fine, can pass deeply into the lung, and may be difficult to expel. Some of the citations I offer below document the health hazards of exposure to airborne soot and also describe the complexity of its chemistry and thus its variable effects.

Watch out: like many other environmental contaminants, soot particles don't affect everyone the same. Some people are more vulnerable, eg. children, the elderly, immune impaired (Bearer 1995) (Shriver 2009).

My OPINION about the health hazard from ghosting stains themselves is that it's not likely that such a hazard is detectable - meaning it's probably absent.

That is to say, once the building air no longer sports airborne soot particles, either having been adequately filtered or adequately provided by clean fresh outdoor air, we wouldn't expect there to be a hazardous level of airborne soot, and we wouldn't expect to be able to detect any meaningful level of airborne soot that was in fact attributable to those particles of soot that have become stuck-to or "plated" onto walls and ceilings where they form ghosting stains.

In sum, if you see the ghosting stain you know the soot particles have stuck to that surface. Those particular particles are not airborne.

Watch out: however if no one has identified and cured the *source* of indoor soot that has stained walls and ceilings the building could be in a very dangerous condition, particularly if sooting is coming not from a woodstove but from a malfunctioning gas-fired appliance.

The same conditions that produce gas-appliance soot are likely to be producing potentially fatal carbon monoxide gas.

Be sure your building has properly installed, located, and tested CO (Carbon monoxide) and fire/smoke detectors.

Watch out: if your woodstove remains in use, be sure also to

see WOOD STOVE OPERATION & SAFETY

Appearance of Types of Soot under the Microscope

Photo below: oil burner soot with fly ash, (at 1000x) photographed by the author while studying microscopy at McCrone Research Institute.

Oil burner soot with fly ash (C) Daniel Friedman at Inspecctapdia.com

Photo below: oil burner soot (at about 400x) collected from building indoor surfaces during an IAQ investigation.

Oil burner soot at a lower magnification (C) Daniel Friedman at InspectApedia.com

Should you be testing building air or surfaces for soot?

It's interesting that experts, discussing the hazards of breathing very small particles, refer to soot particles as being in the 2.5u range ( Bolstad-Johnson 2010). In our experience in the lab soot is so fragile that regardless of the particle size when it is collected, it is easily smashed into much smaller bits by the slightest pressure.

Photo below: soot plated out on building walls from a scented candle, formed thermal tracking stains. We collected surface samples for examination of these particles under the microscope in our lab. This photo is at about 400x.

Scented candle soot particle microscopic examination (C) Daniel Friedman at InspectApedia.comWe speculate that the actual range of inhaled soot might, in the body, be easily reduced to sub-micron size.

See details at AIRBORNE PARTICLE SIZES & IAQ

In our OPINION, testing your indoor surfaces or air for soot is probably not useful given the building history you've already reported. When you see dark sooting stains you already know these particles are present; and you already identified the source as a woodstove.

In general when we see thermal tracking stains, we look first for the source in order to address immediate safety concerns such as unsafe heating equipment or an unsafe chimney.

What about air tests to see if your ghosting stains are releasing soot into the air?

Having performed many tests of dust and debris particles on surfaces and in the air itself, I also caution that "air tests" for particles may be impressive but they're highly inaccurate. Details are

at AIRBORNE PARTICLE LEVEL VARIATIONS

If for research reasons you want to collect surface particles an easy and low-cost procedure that can work well is at

DUST SAMPLING PROCEDURE - collect gently, don't smash your particles.

alternatively see

VACUUM CASSETTE FILTER SAMPLE TESTS for DUST / MOLD

Soot Cleanup Advice

Question: how do we clean up soot from a plugged chimney?

Lots of soot became airborne when we had a plugged chimney recently due to excess soot in the stack and lack of cleaning. The soot is on the floor and basement. I read simple green or concentrated degreasers are good to use, and water, vinegar/baking soda dawn soap is not.

We would appreciate any suggestions. Anonymous by private email 2022/06/15

Moderator reply: soot cleanup methods depend on what got sooty

What we use to clean soot from surfaces depends on the surface material.

Any household cleaner works well on a hard surface.

Soot in carpets, drapes, furnishings, probably need a professional cleaner. I've found that tackling those yourself often makes the staining worse: wetting the sooty surface causes the soot particles to spread across and soak into such materials.
Sooty drywall walls and ceilings: we seal with a lacquer primer-sealer and re-paint. 

Watch out: be sure to read OIL BURNER SOOT & PUFFBACKS   to be sure you're not going to repeat the event. 

Soot Cleaning Advice

Soot from an oil burner puffback explosion is oily and is more-difficult to clean than lighter soot deposits from a fire, wildfire, or fireplace. Most likely you'll find some items like badly-sooted carpets are beyond economical cleaning if puffback damage was severe.

For fire and smoke damage, soot can be oily and easily stain textiles and porous materials. If possible, hire a professional fire damage restoration professional.

If that isn’t feasible, try these methods recommended by the U.S. HUD for fire or smoke-damaged homes - adapted with minor edits:

Source: U.S. HUD, REBUILD HEALTHY HOMES, Guide to Post-Disaster Restoration for a safe and healthy home [PDF] U.S. Department of Housing and Urban Development (HUD)

Research on Soot Hazards in Buildings

Debris in a stack pipe (C) Daniel Friedman


...





ADVERTISEMENT





...

Continue reading at WALL STAIN DIAGNOSIS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

SOOT HAZARDS in BUILDINGS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING INDOOR AIR QUALITY IAQ

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to GAS APPLIANCES, PIPING, CONTROLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT