Leak Inspection at Aboveground & Residential Heating Oil Storage Tanks
Indoor oil storage tank inspection and leak detection guide.
Advice and example photos for the visual inspection of above ground oil tanks for leaks and damage, improper piping, wrong location, bad fire clearances, including these details: damaged or leaky oil storage tanks, improper oil tank piping, valves, and indoor-type oil tanks located outdoors.
Here are photographs & explanation of some important indicators of oil storage tank condition that any home owner or home inspector can examine when an oil storage tank is visible and accessible inside or at a building.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Inspection of the Oil Storage Tank Exterior for Leak SignsIf an oil or other fuel storage tank is above ground and accessible for visual inspection it can and should be inspected for evidence of leaks or damage.
Here are some inspection pointers for heating oil tanks.Is the tank exterior sound, without leaking seams or excessive rust?
Is there a patch or other evidence of a history of leaking?
In the photo at above-left, note the wet bottom of the tank?
The inspector needs to decide if the oil on the tank exterior is from weeping at the fill or vent pipe fittings, from leaks at the oil line exiting the tank.
We were concerned about the evidence of seepage around the bottom left on this tank.
That oil stain does not seem to connect to the tank fill and vent fittings. The oil tank may have a perforation or an opening seam.
What about the next photo shown below?
A leak at fuel line or at the Fire-o-Matic shutoff valve, or perhaps due to an actual tank perforation?
The size and wetness of the oil spill on this basement floor is a bit large to blame on a drippy fire safety valve.
But notice that in the upper portion of the photo the oil tank itself looks new. This oil spill was from the previous oil tank installed in this location.
Also look for water entry around the oil tank and don't confuse a water leak for an oil leak.
Or more difficult, both leaks may be occurring at the same location. Look closely, and if necessary, touch, sniff, and sample the leak substance.
This last photo shows an actual tank leaking at its bottom from a perforation.
Memorize this photo and look under oil tanks when you're inspecting above ground indoor oil storage tanks.
If you see a tarry "stalactite" drip formation on the bottom portion of an oil storage tank, the tank is leaking, has perforated, and can leak catastrophically at any moment.
Watch out: do not pick, poke, or even touch an oil tank that looks like this. The risk is that you perforate the already thin tank bottom, leading to a much bigger and more costly oil leak mess.
Also see details of the Roth oil tank leak detector below on this page and at
For fire safety indoor oil storage tanks should not be located too close to oil burners or other heaters.
Typical indoor clearance requirements specify (or more accurately, used to specify) that the oil storage tank should be 10 feet from the oil burner.
Note: the 2012 IRC changed this minimum indoor clearance distance to 5 feet between the oil burner and the oil storage tank. Update courtesy of Carson Dunlop Associates, Toronto. You can see this design in our sketch at left, provided courtesy of Carson Dunlop Associates.
Even before the 2012 IRC change, some communities permited the oil tank to be located closer, just 5 feet away from the nearest oil burner.
If you cannot meet this distance requirement your local building officials or fire officials may approve the oil tank installation if you provide a fire barrier between the oil tank and the burner.
Tanks should also be located where they will not be damaged, such as by being struck by a vehicle entering a garage.
In some communities indoor oil storage tanks located in a garage must be protected against possible vehicle damage by steel posts or similar means.
In some communities indoor oil storage tanks must also be secured against possibly falling or tipping over, such as by using angled steel piping set into the floor and ceiling or floor and wall around the oil tank.
Also see OIL BURNER INSPECTION for a discussion of the impace of leaks at the oil burner assembly itself.
Our InspectApedia reader asked:
I am installing a pellet boiler and will need a second metal chimney as I am leaving my oil burner as a backup. I live in maine.
The only place I would like the metal asbestos chimney would run 40” away from my oil tank. Do you know what the code is on this?
I am having a heck of a time getting any answers regarding this? - R. B. Windham ME 2/27/2014
Insulated metal chimneys typically require a one-inch clearance from combustibles.
I think the reason you're not finding an answer to your question is that we're mixing up different constraints and safety concerns:
If you were worrying about a horizontal distance for a flue vent connector, from a heater to the chimney, that'd be a different story.
Suppose we wanted to run across an entire building from the heater to the chimney: the maximum horizontal length should not be more than 75% of the chimney height above the vent connector, or 100% if the chimney is insulated.
So you'd need a chimney at least 40 feet tall. But an option that may work acceptably is to include a draft inducer fan such as the type made by Field Controls.
NHFireBear
We have found multiple situations where an owner has installed an AST supported by nothing more than a pile of wooden pallets or other combustibles (wooden structure, discarded tires, etc)
NFPA 31 requires that above-ground tanks rest on solid concrete and that any supports be made of concrete, steel or solid masonry. Supports for outside tanks shall be fastened to their foundation.
Outside tanks up to 275 gallons may be installed within 5 ft of a property line and up to 660 may be installed within 10 ft, assuming local setback or fire code does not make it more restrictive than NFPA 31: 7.8 "Installation of Outside Aboveground Tanks."
Reply:
Thanks NHFireBear - we've added your note. We appreciate the editing assistance. - Ed.
Illustration: components of a Roth Double-Wall Oil Storage tank, cited below.
The oil tank piping installation and testing standards cited below are the most-widely adopted throughout states and cities in the U.S.
...
Continue reading at OIL TANK FILL & VENT PIPING INSPECTION CHECKLIST or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see ABOVE GROUND OIL TANK (AST) INSPECTION & TEST FAQs - questions & answers posted originally on this page
Or see these
ABOVE GROUND OIL STORAGE TANK (AST) INSPECTION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about indoor home heating oil storage tanks: installation, inspection, leaks, piping, troubleshooting
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.