Fiber Cement Siding DefectsFiber cement siding defects, failures, problem troubleshooting:
This article describes the types of problems that occur in fiber cement siding installations in North America, including siding shrinkage gaps at butt joints, cracks, breaks, and loose or buckling siding boards or shakes.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Article Series ContentsGaps at butt joints in fiber cement siding as well as questions about where caulk should and should not be applied are discussed separately
As you can see in our fiber cement lap siding butt joint gap photo at left, the gap is unattractive; in this installation we see the housewrap in the siding gap opening - telling us that there was no back-flashing and that wind-blown rain will certainly pass behind the siding at rates above usual - possibly leading to leaks into the building walls.
Other fiber cement installation & maintenance problems are described in the remainder of this article. .
But whose fiber cement siding is this?
Installed in 2003 the siding has been "repaired" (caulked butt joints) at least once, with gaps continuing to open, leading to a very unhappy homeowner.
Our second siding gap photo (below left) tells more about the history of this fiber cement siding installation.
The combination of an open lap siding butt joint and torn caulk in the same opening tells us that someone tried caulking the butt joint gaps, probably shortly after the fiber cement siding was installed.
Continued fibre cement siding shrinkage tore the caulk and increased the butt joint gap significantly.
Some manufacturer's instructions make clear that caulking of the butt joint in pre-finished textured lap siding is not recommended - most likely because the result is a still more ugly cosmetic defect.
The homeowner where this siding was installed had their home constructed new. The owners thought they were contracting for HardiPlank® siding. On investigation James Hardie's rep informed the homeowner, their attorney, and their special invetigator (not us) that the product was not from James Hardie. There was a suggestion that the product was from CertainTeed.
With assistance from the repair contractor, Galow Homes, [19] we visited the site both at initial siding assessment (2012) and during siding removal and exploration (2013), to collect fiber cement siding samples for further investigation. No one seemed to know whose fiber cement siding was installed. We confirmed that the siding was not made by James Hardie nor by Certainteed.
A chief cause of excessive fiber cement lap siding shrinkage in new installations is the installation of siding while it is too wet. Manufacturer's instructions generally say that the contractor should not install wet siding.
Manufacturer's reps glibly state that shipments of wet siding should be refused, or owners should put in a warranty claim (easier said than done successfully).
Our photo shows water inside the plastic wrap on a bundle of new fiber cement siding. But just how wet is "too wet" and how the siding contractor is supposed to decide that the material is too wet to install is left a mystery.
In any event, the installation troubles documented here are largely attributable to failure to follow fiber cement board lap siding installation specifications from either of the major U.S. manufacturers.
At left we illustrate another failure to follow the manufacturer's installation instructions. The siding is not caulked at its abutment to vertical trim.
JamesHardie's installation guide recommends caulking at the abutment of HardiePlank siding boards to vertical trim boards.
CertainTeed's installation guide has the same recommendation and is an extensive document with plenty of advice for the installing contractor and homeowner.
Generally the manufacturers do not recommend caulking at factory-painted fiber cement siding butt joints, presumably because it creates a cosmetic defect; some instructions permit caulking at primed (and smooth) siding, presumably because the caulk "cosmetic defect" will be hidden by the finish paint job.
At left we illustrate another failure to follow the manufacturer's installation instructions. JamesHardie's installation guide recommends installation of weather flashing behind the horizontal lap siding board butt joints and requires it in some products - it was omitted completely in this installation.
Similar advice is found in the CertainTeed lap siding installation guide.
And of course the fact that I can lift the board away from the wall suggests inadequate nailing as well.
And of course the fact that I can lift the board away from the wall suggests inadequate nailing as well..
Unfortunately more nailing defects were apparent at the gable ends of the home where the lap siding abutted (or was supposed to abut) the gable end trim.
Left un-nailed the corners of most of these siding boards were curling away from the building. .
Consistent with our earlier warning that one bad installation feature suggests more SNAFUs are in store, even in a casual inspection we noticed other disappointing details on this home that was less than ten years old:
This discussion moved to SIDING, FIBER CEMENT NAILING DEFECTS
In our OPINION fiber cement siding is not likely to actually "warp", as it's a cementious product; but indeed if the product is not properly installed, including end gaps at vertical trim abutments and proper nailing using the specified fasteners, at the specified intervals, and nailed into sound sheathing of adequate thickness or into wall studs, then expansion due to moisture uptake and/or thermal changes may result in buckling of the material, particularly on sun-exposed walls.
My finger is pointing to an area of buckled fiber cement siding above a garage door; we think that the buckling occurred because of failure to provide the required clearance gap at the abutment of siding ends to vertical trim, but feeble nailing may also have been a factor.
The omission of head flashing over windows & doors invites leaks behind the siding, rotted window & door trim, and a need for early exterior window & trim repairs or replacement.
The home in our photo was about ten years old. We found rotted trim on all sides of the structure.
When the siding was removed from the building in our photos we saw that the installers had installed the building house wrap improperly.
The top edge of lower sections of housewrap were lapped over rather than under upper housewrap sections.
This means that any water leaking behind the siding will find its way behind the housewrap, increasing chances of water entering the building wall cavity itself.
Water inside a building wall cavity means wet insulation, higher heating and cooling bills, mold contamination risks, and risk of wood structure attack by carpenter ants, termites, and wood-rotting fungi.
Details about the requirements for house wrap, product choices, and installation details are found
at HOUSEWRAP / SHEATHING WRAP and related articles provided there.
Builders are using J-channel windows, and other fittings and accessories originally designed for use with vinyl siding, but now with fiber-cement siding. In other words, they are using details that intentionally let water getting behind the siding, but not in a planned rain screen assembly.
Jame Hardie actually has a tech bulletin for this (attached, see p. 123), but I've literally never seen a builder use it (and when we contact Hardie about it they always side with the builders and claim that their recommendations are best practice but not required).
Builders claim that the WRB and tape window flashing suffice, but it makes no sense to me to dump water behind the siding.
The practice apparently does not violate any code provisions, window manufacturers have nothing to say about it, some fiber-cement manufacturers (other than Hardie) ignore it, others seem to address it in installation instructions but not to the extent that Hardie does.
Do you have any opinions or ideas about this, and/or do you know a building envelope consultant who might be interested?
I am thinking of proposing an article on this to JLC, but know it would need expertise of a building envelope specialist to carry any weight. - Anonymous pending agreement, the writer is a professional home inspector working in the South Eastern U.S. by email 2016/06/12
The detail you mention and the manufacturers' bulletin combined with actual practices combined with manufacturer's defending builders (who they correctly see as their actual customer) is an important detail and might be a contributor to some of the buckled or other fibre cement sided home complaints that keep cropping up.
OPINION: Few builders were English majors and fewer are inclined to read the manufacturer's installation details, less to follow them. There are quite a few products & systems (e.g. EIFS) for which the manufacturer writes an installation specification that enables them to defend against product complaints by finding that the product is almost never in total compliance with the specs.
A good design is for what people will do in construction, not what they should do. The fiber cement complaints, while probably doing less total building harm than the EIFS issue, have some similar features.
A builder might think that by using housewrap and flashing tape around openings, the abutment to trim or windows and doors is not a critical joint.
But a read of the requirement to keep the FC siding dry until installed offers a clue. After all, this is an exterior cladding.
Why can't fiber cement siding get wet?
Perhaps because the back-coating is not so water-resistant as the exposed face of the siding. In turn that means that water running down the sheathing against the siding back is likely to contribute to water absorption. If the siding went on really dry (as it ought but often does not) I might expect some buckling problems to ensue.
I wouldn't go so far as to say the builder is "intentionally" letting water behind the siding but rather that they're ignoring both the practices guide and the problems that may ensue.
The Hardie practices you sent, on discussing use of J-channels, focuses on directing water out from behind siding at the bottom of the vertical J's but omits a top J-channel detail that can send enormous amounts of water running down the exterior wall above a window or door into the space behind the vertical J-channel.
Specifically, the installer has to cut the top long, then trim its J-channel face, leaving 1" or more tabs of the J-channel bottom that are bent down over the *outside* of the vertical J-channel's interior "U". This detail keeps water collected by that top horizontal "gutter" from being sent into the wall behind the siding regardless of whether the siding is vinyl, aluminum or FC.
I'm neutral on Hardie's Optional rain screen suggestion for residential properties. I don't think that the problem is lack of ability of water to drain out of the siding - it's usually not painted in the field so the bottom edges of boards aren't sealed against one another by paint - a detail can trap water behind painted clapboard-sheathed walls.
I think that if housewrap and flashing tape are properly done we may still keep water out of the wall cavity itself. In that case it's the issue of wetting the siding back that's probably going to contribute to cosmetic complaints of buckling and bending. (There's a whole separate set of gripes about shrinkage of wet siding).
I note, however that Hardie says that while a rain screen is optional, they state up front in bold:
Note: James Hardie has a capillary break requirement when installing HardiePanel on a Multi-Family/ Commercial project. Please visit JamesHardieCommercial.com for further information. - Hardie FC Siding Best Practices cited above.
I've not personally seen a home with FC siding that used a furring applied siding mounting system over a rain screen.
Now you've gone and added another water intrusion point that I will have to add. Thanks; by this posting we'll welcome comments, information, field reports from other interested parties. Readers please use the page bottom COMMENTS BOX or find our email at page top or bottom CONTACT - Ed.
The peeling top coat on the siding shown above (Rhinebeck, NY) shows a white primer remaining in place on the fiber cement siding. The siding paint damage was largely due to excessive wetting from rain-splash.
The mechanical damage to fiber cement siding shown below is obviously from impact and is not a product defect. Just about any building siding material can be damaged by external events, though some products such as fiber cement siding, and asbestos cement shingle siding are more vulnerable to breakage compared with vinyl siding (which can still be punctured or broken under some conditions) or aluminum siding (which dents and which can still be punctured under certain conditions).
The repair for the damage shown above on a building in Rhinebeck, NY, requires that the damaged boards be removed and replaced.
Failure to repair punctures such as those we show means increased risk of wind-blown rain leakage into the wall structure.
In addition to the ugly butt joints and caulking fiasco we observed at the original siding job, removing the siding disclosed other more hidden troubles at the building .
In fact, the progoma; siding had so many installation errors, missing flashing, crooked, trim rot around windows and doors, building leaks, that a patch job was in our opinion and that of the owner and contractor, likely to lead to a lifetime of aggravation for the building owners.
Our photos below illustrate what we found when taking a closer look at this installation: leaks at window tops and rotted trim everywhere on the building. This was a ten-year-old home.
My definition of non-destructive rot-inspection is if I can push my finger into the wood trim, it was already severely rotted - I didn't cause damage to the building. (Photo below).
At below left we can see why conventional brick mold window trim will be rotted on a fairly new house: the omission of head flashing over windows and doors combines with the soft common pine finger-jointed brick mold to rot and leak. And as you can see from my finger-poked rot hole above and at left, water would also have been entering the wall behind the siding.
In our photograph at above right you can see that the original siding installers (that was not by Galow Homes), the fellows were not quite sure about the truism that "water runs down hill" - the building house wrap was installed "upside down" with lower segments lapped outside or on top of upper segments, guaranteeing that any leaks past the siding itself would find a ready path behind the protective housewrap barrier and into the building walls.
The miracle of modern housewrap materials is not so wonderful if the product is not properly installed. In the photo below the contractor is demonstrating "backwards" installed housewrap that would readily admit water behind the wrap itself.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
Wavy hardie board. How do you fix? On 2020-08-12 by Jim
Answer by (mod) - how to fix & prevent wavy HardieBoard Siding
From your photo I'd say most-likely the siding was cut a bit too long, failing to leave room at the siding board ends to allow for thermal expansion. The only solution:
Remove the buckled fiberboard siding, check how it was nailed, check the clearances allowed at the ends of the boards at vertical trim, and if board is badly cupped you may need to replace it.
Watch out: when re-installing new or relaxed clapboard siding, including fiber cement siding like your James HardieBoard, be sure to leave 1/8" clearance at board ends to handle thermal and moisture expansion.More repair details for your FC siding are at
More details specific to Hardieboard are at
My house was built six years ago with hardie board siding and trim. The trim is starting to crack at the nail sites and it is also pulling away from the siding. What might cause this problem? How can it be fixed?
The house is located in Greeneville, Tennessee. The cracked siding doesn't appear to be specific to any side or part of the house. I will send pictures ASAP. On 2020-06-02 by Patricia Cascone
by (mod) -
Patricia
I'd like to see some sharp closeup photos of the damage (you can post one photo per comment). Also you'll want to know just what type of nail was used and how they were driven (power nailer, hammer, set in or driven flush &c.)It's possible that the wrong trim nails were used, for example too large in diameter, for the trim material.
Take a look at
One of customers has brought to my attention that his Hardiboard is cracking, it was installed by the home owner about 5 yrs. Ago any suggestions on cause? On 2020-01-02 by Richard Howard
Suggestions by (mod) -
Richard
I'd like to see photos of the cracked Hardiboard and to know the country and city of installation;
Sometimes we see thermal or moisture-related movement in siding that might stress boards and could explain both buckling and cracking, especially if the siding was tightly-butted against vertical trim such as at windows or doors; it'd be diagnostic to see which boards are cracked, the location of the cracks, differences on different sides of the building (sun, weather exposure differences etc.)
We had Fiber Cement Siding installed on our home in 2013. It is beautiful and has none of the problems described above.
Except for one unusual problem. We have a metal roof on the second story and a metal roof that surrounds an 8' veranda porch.
The siding on the second floor appears over the years to have been effected by rain dripping off the roof or back-splashing onto the siding that has caused gray streaks in wide areas of the siding.
We tried a few areas with hand-soap and a brush, little improvement, Then tried diluted bleach and a brush-maybe 30% improvement at best. The "graying" of the paint on the siding is now noticeable from the road. If you are able to expand the pictures, you can see the gray areas. Please help with any ideas you may have, Thank you, Joe Jeffers San Angelo, Texas
Sent an email with pictures regarding issue On 2018-07-16 by wtpa@WCC.NET
Advice on fiber cement siding stains by (mod) -
WTPA:
Regarding the diagnosis of dark stains that appear to be coming through the paint on your fiber cement sided home, attacking, removing, or preventing stains will benefit from a better guess at their origin and nature.
I looked at your photos, and though information is very limited as they're distant and not sharp, I can see a pattern of dark areas that are clearly not due to rain splash-up: they are much too high on the siding and they are not in the splash-up pattern.
At SIDING DAMAGE by SPLASHBACK https://inspectapedia.com/BestPractices/Siding_Splashback_Damage.phpyou'll see the characteristic regular horizontal line marking the top of rain-splash-up effects on the lower portion of building walls, in a regular pattern consistent with the location of the eaves of the spilling-roof line above.
From the pattern one must suspect some other "stain" cause. Without a closer look on-site by someone experienced with paint failures and building staining, I'm sorry to say my diagnosis cannot be more than speculation.
Mold growth in or under a paint coating is a possible cause: it would be diagnostic to know if the siding was ever painted on-site.
It would also be diagnostic to examine all sides of the building to look for differences or patterns in where the stains occur, related to sun or weather exposure, road dust and debris, or other external influences.
To post a photo at any InspectApedia page, simply begin a comment in the comment box, then click the "add image" button, and select the image file from its location on your computer; or if from your smartphone you are viewing InspectApedia.com pages such as SIDING, FIBER CEMENT DEFECTS (where I'll re-post one of your photos to permit helpful comments from other readers) you can also post a photo from your smart phone either from its image library or, as you'll see, there's an option to take a new photo during the posting process.
At STAIN DIAGNOSIS on BUILDING EXTERIORS https://inspectapedia.com/exterior/Stains_on_Exteriors.php you'll find a catalog of stains and their common causes - that article is worth a look.
At CONSULTANTS & EXPERTS DIRECTORIES https://inspectapedia.com/Expert-Consultants-Directory.php you might find a home inspector or paint failures expert who can help you diagnose your home's particular condition.
Let us know what you're told and post some sharper photos if you can and we may be able to offer other comments.
The paint on our cement board siding is peeling in a few places where there is water splashing or running down.
We tried repainting once and it peeled again in a year. We would like to avoid replacing all of the siding on the house as our contractor suggests as the product is no longer available and the siding is attractive except where peeling.
We've had gutters installed to reduce or eliminate the water issue. Is there a product we could use as a base coat that would allow repainting of the areas and prevent peeling again? Thanks for your help. On 2017-06-02 by Bill Raboin
Investigation advice by (mod) -
Bill,
I'm not clear what sort of siding you have installed: shingles or boards, nor if the concern is just for painting vs a possible asbestos concern if the siding were to be power-washed or cut/sawn etc.
In my experience if we can remove loose paint and then use a primer/sealer that is recommended by the paint supplier as compatible with the top coat of paint, that will give the best results. Of course the surface has to be both clean and dry. The fiber cement shingle siding that I've painted held that paint very well.
I'd also look at the source of water damage: fixing gutters, for example.See our detailed advice
at PAINT FAILURE, DIAGNOSIS, CURE, PREVENTION
Can I replace rotting wood siding at ground level with fiber cement boards?
I just moved into a new house and the previous owners built some planter beds right up against the house. The soil and decorative stone came up about 3 inches onto the wood siding causing the wood siding to rot.
I want to replace the siding with fiber cement siding, but I'm curious to know if I replace the soil and decorative stone to the same hight as it was before, will the fiber cement siding also eventually rot as well?
I look foreword to hearing back from you. Thanks, On 2016-07-09 by Frank
Answer by (mod) - Just replacing siding that extends below grade level is a bad idea, here's why:
Frank:
Fiber cement siding won't "rot" butWatch out: any siding that extends below ground level will be water damaged, and worse, besides risking rot in the wall structure behind the siding, you are continuing to issue a platinum-engraved invitation to termites and carpenter ants to invade the building structure.
You'll need to either lower grade and slope it away from the building to get at least 6-8" between the siding bottom and ground level or you'll need to raise the masonry foundtion of the building by cutting out the wood portion of the bottom of the walls - I've done both repairs.
I have a new house with fiber cement siding on it. The siding has already started to buckle at the abutment of siding ends and some of the siding is loose and can be pulled away from the house.
The builder wants to nail the siding where it it buckling and loose. I feel that this will not solve the problem the result of bad installation.
I feel that the siding must be torn down and resided.Please comment.
Frank burke On 2016-04-09 by Anonymous
by (mod) - Diagnostic questions
Anon;
Please use the page bottom CONTACT link to send me some sharp photos and I'll ask some diagnostic questions and offer some opinions.
Watch out: I would not just nail down buckled siding; let's first understand what's going on. I would also not jump to tear it off.First we need to understand
What is the brand & product ID.
Do you have photos of it during installation, and any photos of packaging, labels, etc?
Also I'd like to see closeups of the points of abutment to vertical trim near where buckling is occurring, photos of the buckled siding looking up below the edge board, and in-situ photos of the building from a more distant view.
...
Continue reading at SIDING, FIBER CEMENT DEFECT DIAGNOSTIC QUESTIONS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
SIDING, FIBER CEMENT DEFECTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.