One Line Jet Pump (C) Daniel Friedman Water Pressure Diagnostic Table Q&A-6

Questions & answers about diagnosing problems with water pressure:

These FAQs help diagnose the reason that a water pump or well pump won't start, won't stop, or cycles on and off too often.

This article series provides a series of 3 tables giving step by step checklist for diagnosing water pressure, water pump, and water well problems. We give diagnostic and repair procedures for both municipal water supply problems and well water supply problems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





FAQs Poor Water Pressure from a Pump - set #6

These questions & answers about how to figure out why a water pump won't start running, won't stop running, or runs switching on and off too often were posted originally

at WATER PRESSURE TABLE 1: PUMP WON'T RUN, WON'T STOP, or CYCLES - so you will want to be sure to review that advice,

or start right at the top: WATER PRESSURE PROBLEM DIAGNOSIS TABLE.

Well Pump can't reach cutoff pressure and we hear gurgling sounds

Pressure gauge will only pump up to 40 then you can hear gurgling . I have replaced new pump, gauge , and points switch and it still doesn’t work.? On 2019-01-23 by Anji Gardner

Reply by (mod) - probably your well flow rate or water quantity is inadequate

My guess is that if you're hearing a gurgling sound near the end of the pump cycle and before you reach the cut-off pressure your water supply in the well is low or you have a poor well flow rate.

There could also be a leak in well piping below the water level that gets exposed as the water level in the well bore gets bumped down. That could be putting air into your system.

Why is well pump shutting off at 38 psi with a new 40/60 pressure switch?

I replaced my 40-60 psi pressure switch. pressurized the tank to 38 psi. Pump runs to 38 psi and shuts off. what the heck? On 2018-11-17 by Ed Kemp

Answer by (mod) - pump shuts off at "wrong pressure" - where to start

Have you checked the pressure with an independent gauge?

If the pressure gauge is accurate then I suspect that either the pressure control switch cutoff pressure has not been adjusted to the proper setting or your pump is overheating and shutting down on thermal overload.

See the well pump pressure control switch setting procedure at PUMP PRESSURE SWITCH STANDARD (PSI) SETTINGS 

 

Condominium complex water pressure system (C) InspectApedia.com Ganesan

Why are our water pressure pumps only pumping to very low pressure?

I’m working condominium maintenance .there condo four blocks only.all blocks rooftop her two pressure pumps just .

Last years November all blocks rooftop pressure pumps one damage and c and d block Multics pumps very low pressure why suddenly would it problem ? On 2018-09-23 by Technician Ganesan

[Photo shown above]

by (mod) - check voltage levels

Tech

If you can do so safely (without being shocked or killed) you'd check the supply voltage level to the pumps, then check the pumps themselves for a damaged impeller or motor.

Why did our water pressure suddenly fall to zero with still no water 24 hours later?

We live in a home out in the country with an underground well. Two nights ago water quit while in shower.

No water anywhere. 36 hours later I just checked faucet and had water with great pressure. Now 24 hrs later no water. What’s the problem? Braker not tripped. Also our water spits at times On 2018-09-14 by Grace

by (mod) - signs of running out of water or overheating well pump motor

Two common explanations are

a well with a very poor flow rate that is running out of water and then recovering over time when you stop drawing water,

or

a pump that's overheating and shutting off.

Check your pump motor to see if there is a popped-out reset button.

Details are at ELECTRIC MOTOR OVERLOAD RESET - topic home

Water pressure stops, then restarts after a few minutes - how do I fix it?

My water will stop after a few minutes and start after a few minutes and run quite a while. This happens each time. My tank has air, is not heavy so I don,t think it is waterlogged. How do I sign is and repair so as not to have interruptions in the water? On 2018-08-21 by Mike

by (mod) - water will stop after a few minutes and start after a few minutes and run quite a while.

Mike see this article

on INTERMITTENT LOSS OF WATER PRESSURE https://inspectapedia.com/water/Water_Pressure_Comes_Goes.php

To look at some diagnostics for the problem that you describe that is water pressure that seems to come and go at odd times.

An Earthworm shorted our well pump pressure switch - still having trouble

100ft deep well - submersable 1/2hp pump - 20/40 pressure switch.

When our water stopped running originally, I checked the pressure switch{ 20-40) and found that earth worm had commited suicide across the contacts.

Also noticed that the presure gauge had a small amount rust inside and out. I immediately replaced both, and nothing.

I came upon your site while researching the possible problem.

Following your various diagnosis and FAQ's, I have repaired a couple leaky pipes, checked for clogged tubes and tightened the fixture on the bottom of my pressure tank (which had to be pulled out of the mud btw) and had to add air to bring it up to the 18psi cut-off.

I checked and made sure that my wiring was correcct and that the pump (submersible) was recieving power, How this system was ever working before I'll never know. Still nothing, which lead to pulling the pump . Had to buy a new one but chose a 3/4hp instead and changed switch to a 30-50.

after these were installed, I searched and found a small leak right outside the well casing. Nothing... searched further and needed to readjust the pitless valve because a friend helped install the pump and didn't have the valve lined up. All this being said, when I try to get things going here's what happens.

To get any pressure at all I have to back fill water from an outside source throughan outside spout.

This brings tank Pressure up to the cut-off 28psi but no higher. As soon as I turn off the outside spout, and open a faucet in the house, pressure will start to fall thus making the switch come on. The switch contacts will stay together while all pressure will slowly lower until it reaches the low pressure protection pressure of 20psi, the the switch kicks off.

I have checked and found that when the switch truns on, the wiring at the well to the pump will jump. I have even used a multi meter to make sure that the pump was still getting power. I'm ready to give up. What am I missing? On 2018-07-08 by nardosmom01

by (mod) -

As we wrote by email this sounds like a leaky foot valve or check valve.

by nardosmom01

Will pull the pump tomorrow and let you know what happens. Btw, never received your email, but i appreciate your getting back to me here.

Pump stopped giving water after installing new pressure switvch

Just replaced the pump control and the pressure switch. Ran great for a few hours then all of the sudden.. nothing .

I manually turned the pressure switch on but when it builds up to 30psi i can still hear the pump running but the pressure does not rise if i sit there long enough it will get a spurt of water and go up to 35 psi then stop but the pump still is running .

Any clue on what might be going on? On 2018-06-27 by Clay

by (mod) -

Clay

This sounds as if the well is running out of water, or a check valve is sticking shut (unlikely).

How do I diagnose surging water pressure in one bathroom when others are normal?

Surging water pressure in my bathroom in the back of house, main bathroom, kitchen, and laundry room all normal what's wrong?

Our well was redone last spring, our control box replaced last winter. Could it be just a shower head On 2018-06-19 by Penny

Answer by (mod) -

What you describe is odd since usually surging water pressure is traced to a pump control or pressure tank problem that would affect the whole building.

However it's possible, depending on piping sizes, lengths, location of the surging fixture compared with other fixtures, that the problem could still be due to a short cycling well pump due to a waterlogged pressure tank.

Use an accomplice and two cellphones: let me know if while you see the pressure surging at your back bathroom the surge is related to the pump switching on and off- observed by the second person.

My pump is blowing fuses, I'm trying to fix it

Had water pressure, I unplugged pump, blew a fuse ...reset ...elect is back on but now pump won't pump water to the house....
What should I be doing to get it working again? On 2018-05-05 07:41:51.196512 by Kim

Answer by (mod) -

Watch out: I'm nervous that someone could be shocked or killed - if the pump wiring is shorted, for example. I hope you called an electrician.

...

Continue reading  at WATER PRESSURE PROBLEM DIAGNOSIS TABLE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WATER PRESSURE PROBLEM DIAGNOSIS TABLE FAQs-6 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about how best to diagnose the cause of poor building water pressure or lost water pressure.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.