Building Inspection, Diagnosis & Repair Info

Parts of a submersible pump water system that use both a pressure control switch and a second pump relay that actually turns on the submersible well pump  (C) Daniel Friedman at InspectApedia.comWater Pressure Diagnostic Table FAQs

Questions & answers about diagnosing problems with water pressure:

These FAQs help diagnose the reason that a water pump or well pump won't start, won't stop, or cycles on and off too often.

This article series provides a series of 3 tables giving step by step checklist for diagnosing water pressure, water pump, and water well problems. We give diagnostic and repair procedures for both municipal water supply problems and well water supply problems.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





FAQs on Diagnosing Poor Water Pressure from a Pump & Well System

These questions & answers about how to figure out why a water pump won't start running, won't stop running, or runs switching on and off too often were posted originally

at WATER PRESSURE TABLE 1: PUMP WON'T RUN, WON'T STOP, or CYCLES - so you will want to be sure to review that advice,

or start right at the beginning of our water pump troubleshooting tables: WATER PRESSURE PROBLEM DIAGNOSIS TABLE.

Article Index

...

Water Pressure Falls to Zero Before Pump Runs Q&A

Before water pump cuts in I lose all water for a couple of seconds

I installed a 40/60 pressure switch and set the captive air pressure at 38psi. Before water cuts in I lose all water for a couple of seconds and then it kicks in. Pressure gauge shows full air pressure. What do I have wrong, air pressure too high or low? On 2017-07-17 by Frank

Explanation and advice by (mod) -

Usually this is a problem of debris clogging at the switch and gauge. I would replace them and be sure no debris clogs the mounts,for those two components.

 

Explain sudden, complete, brief loss of all water pressure for 3-5 seconds

It has recently developed that occasionally all flow at all users will be lost for about 3-5 seconds. It occurs when one user is active (shower) and another turns on (toilet, sink). It may occur sometimes when only one user is active (shower or sink) but I have not been able to verify this.

The pressure switch seems to work OK, but the pressure gauge doesn't work well (must be tapped for the needle to move - I need to change it).

Is this likely to be an air tank problem or a pump problem or something else? I have reviewed the articles and have not found clear direction. - Gary 12/3/12

Reply:

Gary,

For a pump problem to explain what you describe I'd expect the water tank to have no water in it at all, or to be almost completely waterlogged, having no air charge at all. Otherwise the water tank would keep pressure flowing across pump turning on and off. So I don't suspect a water pressure tank problem.

If the water pressure tank is completely waterlogged, then it is not going to keep ANY water flowing on its own. In that case, as soon as you turn water on the pump comes on as well and runs almost constantly (depending on water usage rate); it may be that your pressure tank is almost completely waterlogged, so when the pump stops (though just briefly as the tank has so little air charge), water flow also stops.

...

Bad Water Pressure After Plumbing Work FAQs

After replacing a hot water tank we've got lost water pressure. Is it electrical, a clogged filter, bad tank bladder or what?

I have an outside well with an above ground pump. Until a year ago, when I replaced the gas hot water tank located in the attic, I had no well water pressure or water flow problems . The most I could complain about was the occasional specks of fine dirt in the garden tub.

Its one year later, and I have started to experience good pressure on hot and cold water for about a minute and half before the water slows and then stops.

I simply shut the faucets off and wait for about a 2 minute period and then turn them both back on and the water flows without interruption or loss of pressure.

In two recent times the outside sub panel breaker box which houses the A/C and the Well pump breakers, the Well pump breaker was tripped. Do I have an electrical issue (electric pump intermittent failure), a filter or bladder clog, or some other age or sediment related issue.

The well is 12 plus years old and delivers throughout the worse droughts here in NC. What should and could I do to fix this? - Vince NB, Charlotte NC

Reply: a clogged water filter stays clogged until it's replaced - it won't get better on its own. A stick tank bladder or control can, however give intermittent water pressure behavior

I'm not sure, Vince, but I don't think that a clogged filter will recover when water is shut off; a flapping bit of debris at a hot water tank or cold water pressure tank can behave that way. The tripping pump breaker is a clue that the pump motor may be failing or overheating. I'd check there.

 

Water pressure tank is empty after replacing our hot water heater. I think there is a sediment clog somewhere

I recently replaced my water heater without any problems and filled it according to standard practice. While refilling, I noticed a lot of sediment from the faucets, which is pretty common in this area every time water is cut off. I replaced my sediment filter but noticed the pressure tank is empty.

Water pressure of the house meets any single appliance demand, but it we try to run two fixtures at once, the water will cut off, about thirty seconds, then turn on again. My current well level is relatively high. My guess is that I have a sediment clog preventing the tank from filling.

Would you please offer your insight and perhaps supply a link if this specific issue has already been addressed? Thank you. - Kevin

Reply:

Kevin:

I agree that your diagnosis sounds reasonable - if water is not entering your water pressure tank a symptom will be short cycling on and off of the water pump. The sediment you report could have clogged the water entry port at the tank.

Provided your water tank is not waterlogged (lacking any air charge) you could try forcing water into the pressure tank by temporarily holding the pressure control relay closed to pump water to say 70 psi to see if you can force through a blockage at the tank entry.

WATCH OUT not to over pressurize your tank and blow it up (you can be hurt or killed) and Watch out: not to get shocked - there are live wires in the pressure control switch.

See SHORT CYCLING WATER PUMP, and if you confirm that the water tank is not taking in water, you'll probably need to drain the tank,

then make sure it's air charge is correct (WATER TANK AIR, HOW TO ADD)

 

Lost water pressure after changing pressure tank

I just replaced my "non-pressurized" cold water tank with a "pressure tank". Now, when the pump reaches the low, on pressure, my water slows way down and my pressure drops. What could be causing this? It did not do this prior to the tank change. - Anon

Reply: check for sediment clogging of the pressure control switch; check for wiring errors if you touched wiring connections.

Particularly if your new pressure tank installation did not include a new pressure control switch, the tank change out may have stirred debris that has clogged the sensor port on your pressure switch.

Clogging occurs in the small diameter mounting tube (typically 1/8" NPT) that connects the pressure control switch to the water supply piping at the tank bottom, or at the still smaller orifice at the bottom of the pressure control switch. A quick fix is to simply replace these parts.

...

Bad Water Pressure Caused by Control Failures Q&A

Bad well pump control box, relay switch, or pressure switch can give water pressure problems

I found your articles extremely helpful for trying to diagnose my poor water pressure/quantity problem. They helped me to understand how my system works and to figure out that our problem wasn't with the pressure tank or pressure switch.

I did, however, figure out on my own that the problem was with the control box/relay switch (your articles did help me figure out what the heck that box was and what it did, though).

It was an easy fix once I diagnosed the problem. Maybe there should be more mention of the control box and that being a potential cause of poor water pressure.

I'm glad I didn't believe the well technician who thought our well was running dry! - Dawn T.

Reply: tracking down a bad well pump relay switch

Dawn thanks for the nice note, and I'm so glad our information was helpful.

If you would take a moment to let me know what you did to track down the problem to the "control box relay"

(I am guessing you mean the pump control relay switch) I'll be glad to write up and add that information as it would certainly help other readers. Some photos of the equipment you are discussing would be very valuable too. Use the CONTACT link found on our pages to send me photos or more suggestions.

Thanks so much

 

Sudden loss of water pressure, adding air to the pressure tank didn't help

I have a 7yr old submersible that feeds our whole house. Turned a faucet on and it has low pressure. Worked fine hours prior. Never had low pressure so never checked air pressure in bladder tank. I looked at the PSI gauge and it reads 10psi. The tank seems empty or close to it.

When turning the breaker on and off I hear a gurgling in the pipes tool. The contacts look perfect, I put some air in the tank with a hand pump but nothing changed. I have low low pressure but don't want the pump running so i turned it off for the night. its of course 2am now.

I have read the website and still cannot figure out where to start diagnosing this mess. It happened suddenly so that scares me but do have some although very low pressure. It just seems like the pump is on low speed and just pumps to the house an not the tank.

Does the piping have a valve in it or just the pipe that goes up to the switch box and the spigot for the PSI gauge? Other than that don't see why the tank wouldn't get filled. any help on this would be awesome. Thanks

my email is 3010ict @ Gmail - King Ray

Answer by (mod) track down why the well pump is not turning on

KingRay it sounds as if your pump is not coming on, or if it is running, that it is not reaching pressure, either because of a control problem or perhaps low water level in the well.

Try going to the table above and scan through the steps from the top of the table at WATER PRESSURE PROBLEM DIAGNOSIS TABLE (making sure there is electrical power, figuring out if the pump is turning on) to see what helps.

 

...

Abnormally High Water Pressure Q&A

Sudden water pressure spikes of 200 psi

I have an outside deep well that runs all outside irrigation. My pressure tanks are located in my barn about 50 yards from the well head.

The well produces 40 gal per minute. Irrigation lines run from my barn to around my house which is 150 to 200 yards away. The where the well and barn are located is a slightly higher elevation than the house.

Since installing the system 4 years ago, we have had periodic breaks in the lines between the well and barn. Guys were out this week to test pressure at various points. What we have discovered is that the pressure spikes for about 1 second, at just one spigot to 200 psi. any thoughts? - Rick Gilbert 11/5/11

Reply: dangerous condition, check pressure switch

Rick,

Watch out: A sudden pressure spike of 200 psi is very dangerous, likely to cause a burst pipe or burst water pressure tank - that can injure anyone nearby.

It sounds as if your pressure control switch is not properly sensing the water pressure and not turning off the pump; also check for a double error of both a debris clogged pressure switch and a waterlogged pressure tank.

...

What's Normal & What's "Weak" Water Pressure?

Inadequate water pressure when two things run at once - installer says it's normal

Recently replaced the well water pressure tank since we loose pressure when a toilet is flushed and faucet is turned on immediately after - we called the well people who did the installation, they came out and checked the equipment and told us everything is normal.

We never experienced this problem until they replaced the tank - any help will be greatly appreciated. thank you. - George 11/18/11

Reply: nonsense

I don't agree that it's normal to have inadequate water pressure when a toilet tank is filling and you turn on a nearby faucet.

If the cutoff pressure at the building is normal (40-50 psi) then you may have a clogged pipe problem.

...

Water Pressure vs Air or Water Leaks

Can an air leak in my submersible pump cause loss of water pressure in my irrigation system - should I dump cream of wheat cereal into the well

I was told by someone that my loss of pressure when i run my lawn irrigation system is caused from air leak in my deep well submersible pump.

I was told to take the cap off and put a box of cream of wheats and 5 gallon bucket of water down the pipe. he said it would plug up the air leak and fix the problem. - Anon 2/5/12

Reply: absurd - don't do that

Anon:

The advice you received is in my opinion idiotic.

First of all a submersible pump is normally under water, so it's not going to suffer an air leak at the pump; if the pump is NOT under-water and thus is picking up air, that means that the well flow rate itself is inadequate - that's a well problem not a pump problem. If that were the case you'd see air coming out of faucets or sprinklers.

Second, dumping goop into a well is not going to fix the well. The best you can hope for is that your cream of wheat clogs up and ruins your pump itself.

Do not dump cream of wheat, nor oatmeal, nor any other gobbeldygoop into your well.

If there are leaks in the well piping anywhere from the well pump to the final sprinkler heads, yes, when the system is running the pressure will be worse than previously.

See

...

Water Pressure Worsening or Zero Q&A

Water pressure just gets worse and worse

We have progressively less water pressure as time goes by. We also have a water softener system. Our water pressure tank read 20psi. Any ideas want is wrong? - Jim Jones 2/18/12

Reply:

I suspect that your pipes are clogging with mineral deposits - check the water pressure tank at the point when the pump has just shut off; you should see 30-50 psi. If not then the problem is pump or control switch; If yes the problem is not system pressure but rather poor flow.

 

Nearby fruit trees dropped the local water table, now we run out of water

1 hp shallow well jet pump for home shallow well 70-140'. pump was giving 60-70psi easy at first but nearby orange groves keep drain the local wells. Have to shut off pump when they water for frost or during dry season then re prime a day later to stop over heating.

we have one bladder tank but no reservoir tank. hot water tank is in house also shut off when well shut off. now pump can only barely reach 50, so we lowered the shut off by turning the big spring. the bladder tank doesn't seem to have much water in it but it does seem to have air, but don't know how much is suppose to be in that tank of air or water.

has the running dry for a hour or 3 before we noticed the well went dry damaged the impeller or is the problem with the pump they are only about a year old or could it be a problem with the well.

what has been done so far:
adjusted shut off, re primed pump, redid any screw on pipe seal with plumbers tape that seemed to have an air leak pipe seal have to be redone if the well goes dry and the pump gets hot until no water drips and no air leak can be heard

the pump is a Goulds pump ITT j plus jet pump
model c48a95a06-j10 b0865194
rpm 3450
amps13.016.5
the guys that installed it decided that it the well didn't need the jet adapter and did the non-jet install. - Arachia 3/21/12

Reply:

In general, the choices are to improve well yield, drill a new well, or add large capacity water storage at the property and fill those tanks slowly without exceeding your well's flow rate.

First see

After replacing a submersible pump we can't get water pressure, do we need a new tank?

We just replaced a submersible pump (well is about 350 ft deep). When we turned it back on the pressure on the gauge goes up to 50 and turns off and drops down to about 30 but doesn't build back up. Do we need a new pressure tank? - Roger 5/1/12

Reply: check first for a debris-clogged pressure switch

Roger, if the pressure does not return after falling in your water system then either the pump is not turning on when it should or there is a well piping leak or a control problem.

The water pressure tank smooths the flow of delivery of water as the pump cycles on and off and avoids rapid pump on-off cycling, but it does not determine system pressure.

Try checking for dirt or debris clogging at both the gauge and the pressure control switch, or just replace them.

 

Dug Well in the Philippines is not giving enough water - what can we do ?

we just built a well for my family back home in the Philippines but until now is not done yet. they already dig 85 ft.

it works but the water running for 30 t0 45 minutes then it stop. they thought that there is no enough water. they dig more until they reach 110 ft but still do the same. please help us what's the problem? the Pipes, pump or the water level? thank you! -Jean 5/21/12

Reply:

Jean, by looking into the well you will see where in the course of the depth of the well shaft water is entering.

Digging deeper, if it does NOT get lucky enough to disclose new water entry points, is not going to increase the well flow rate.

It can, however, increase the volume of water stored in the well and thus give a reserve of water for daily use. Beyond those general remarks, you need someone on scene to determine if you have a well pipe or pump problem.

 

Diagnose our sudden water pressure & flow problems

I all of a sudden started having pressure/flow problems. If I am running one fixture and turn on another I lose pressure to the other. For example if I run the shower and the washer starts to fill, the shower will lose all flow. Garden hose being turned on will do the same thing, or just any other faucet in the house.

Often my pressure in a single faucet/shower will be OK, but not great, other times I will have excellent pressure like before. I seldom have enough water pressure at my outdoor spigots for my hoses to run a sprinkler. I have an approx. 15 year old submersible that seems to be working fine, if I open the ball valve where the water comes into the house from the pump I can fill a 6 gallon water can in a very short time with high pressure and it doesn't seem to slow at all before I have to close the valve.

I have replaced the water pressure switch with the next higher switch, with no real improvement. I do have an approx. 4' tall bladder tank that I increased the air pressure to so it would match the new pressure switch. I'm at a loss, but it would be nice to be able to run a sprinkler again, or not have to run downstairs to shut off the washer before getting in the shower. None of this was a problem until recently, any suggestions would be helpful. - Dan 7/10/12

Reply:

Dan, if water pressure reaches a normal level at pump shut-off when you are not running any water in the building, say 40 or 50 psi, then the pump is capable of delivering adequate pressure and the problem is elsewhere.

Examples of possible problems in this case include

  • low well flow recovery rate - the well itself can't keep up with the building demand regardless of pump capacity
  • clogged building water supply piping, faucet strainers, shower heads

...

Is Bad Water Pressure Due to a Weak or Inadequate Pump?

Having trouble getting water pumped out of a cistern

Help! I have a cistern with 1 1/2 inch plastic piping and a 1HP (non-self priming) pump. Water is drawn up 6ft vertically, approx. 30 ft horizontally and down 6 ft to the pump & pressure tank. It is an additional 20 ft to my house. The system was new 3 yrs ago. When it works, it works fine.

The problem is it will work perfectly for a few weeks/months then the pump will not shut off causing a loss/or no pressure to the house. It is incredibly difficult to prime the pump. Once it is running it usually works fine for a few days, weeks etc. I have replaced the pressure switch twice and the pressure tank.

The recent pressure switch change was a couple of weeks ago and it features an automatic shut off component so the pump won't burn out. Lately when the pump won't shut off I have been whacking the switch and everything starts working again (generally for a few days). I have had several plumbers make adjustments.

Comments range from: air leak somewhere in the line, adjust pressure switch, to insufficient power to overcome check valve. I am unable to make a logical decision what to do. Also if there is an air leak at a joint would silicon be sufficient to fix the problem or should it be replaced? I am considering buying a 1.5 HP self-priming pump? - Mike 11/9/12

Reply:

Mike,
A 1hp pump ought to be able to lift 6ft, but a bad foot valve or check valve could be losing prime. Sometimes a bad check valve will stick open, but just on occasion, making the problem intermittent, but more likely after a longer period of disuse.

Keep us posted.

 

...

Why is cold water pressure bad in my master bath shower

I have a newly built home and my master bath shower has very poor cold water pressure.

Hot water works fine and all other cold water still runs like a champ for the other shower and faucets. The water pressure was fine for a week and now it has stopped to a slow drizzle all of a sudden. On 2015-03-18 by james

by (mod) - poor cold water pressure at one bathroom shower: two likely causes

James

I would look for a clog or blockage in the cold water piping or valves serving that bath. If cold flow is poor at all fixtures then the trouble is not a fixture stop valve but more likely piping, an elbow, or valve bringing cold water to the bath.

Examine the piping system beginning from a point at which the problem bath water supply is still common with the water supply to other areas of the home where cold water flow is fine. From that point follow the piping. You may find a clogged valve or depending on the type of piping material a clogged brass elbow or connection.

Alternatively I would look closely at the anti-scald valve or hot water tempering valve that may be hidden behind the faceplate of your bath/shower control.

If someone turned the internal adjustment fully over to HOT then you may get weak cold-only flow out of that bath or shower control.

...

Steps in diagnosing why well water system has begun to give poor water pressure

I have a water well system that recently has poor water pressure.

The house is vacant, so we turn of the breaker to the well when we are not there. The problem is suddenly we have a drastic drop in water pressure. I have done some tests and can't figure out the problem.

The tank pressure is 45psi. I changed the pressure switch settings and the pump comes on at 30psi and goes off at 60psi. The only thing that did was let the pressure in the house last 3 minutes instead of one before the pressure goes bad and winds up to a trickle or totally stopping.

The spigot on the pump house has wonderful pressure all the time and the spigot in the hot water heater shed has excellent pressure always. The hot water heater is gas. I did notice one of the 2 filters had a slow dripping leak. Never had a pressure problem before until recently recently.

Am about to start digging up water line to check for breaks, but how can there be a break if it has great pressure all the way to hot water heater. I don't know what to do next, can someone please help me out here ?? (Jan 26, 2014) chris polte

Reply:

Chris,

Starting with some arm-waving and speculation, since I trust you've looked through the water pressure loss checklist above:

Something to check is the loss of prime - when we leave a water system off there may have been a slow leak - say a running toilet - that kept cycling the pump from time to time - enough to keep it primed.
Usually loss of prime means NO water rather than reduced pressure but still I'd watch what happens to the pressure gauge AFTER you've turned off the water.

Another ugly possibility is that the well flow rate has deteriorated - seasonally or permanently.

Make sure I understand this clearly before we continue: do you mean that water will run continuously but at lower pressure? Or do you mean you are running out of water?

Reader follow-up

What I mean is this, the water flows great at the spigot at the pump house and the one in the hot water shed, no loss of pressure at either of these.

The loss of pressure happens when you turn something on inside the house.

Within the last few days, when you turn on for example the kitchen sink, pressure would be fine at 1st, then it would trickle down to almost stopping in about a minute and a half. I increased the settings on the pressure switch to shut off at 60psi rather than 40psi and now the pressure lasts around 3 minutes before it losses pressure.

I thought about the well drying up, but if that was the case the spigots would lose pressure to wouldn't they ??

Reply by (mod) [DF]:

Quite correct about well dry up.

Sounds as if there is a clog or a partly shut valve, clogged filter, or an in house pressure tank bladder problem

chris polte said: when you drain the pressure tank, shouldn't there still be some air pressure in the tank ?

When you drain the pressure tank, shouldn't there still be some air pressure in the tank ?

When I drained mine and checked the pressure it said 0. When I refilled it said 50psi. Also the pump kicks off at 60psi and watching the pressure gauge, it slowly goes down to 50psi and holds there, and the tank is still at 50psi

Is this maybe due to a bad bladder ?

Reply by mod

Yes Chris.

In short, when we drain the pressure tank we are emptying it of water and allowing air to enter at atmospheric pressure. So you are starting with an empty tank at 1 ATM which technically would be about 14.6 psi

BUT your water tank pressure gauge is just not that sensitive, and is designed and calibrated to read water pressure in the piping. So your water tank gauge will read 0 when the tank is fully emptied of water and open to the air.

That's where we want to start.

When you then turn the pump back on, the air in the tank is pressurized as water enters the tank.

When the pump kicks off at 60 PSI and PROVIDED that no water is running in the house AND that the tank itself and its fittings are not leaking,

THEN we should see 60 PSI on the gauge - or something close to 60.

(These water pressure gauges are not precise lab instruments and also because of pumping effects often when the pump switch cuts off at your set pressure of 60 the gauge pressure will drop just a few psi.

The fact that you see pressure dropping slowly down to 50 argues that there is water running or a leak somewhere.

Try shutting water off into the building - downstream from the pressure tank and its controls - that is between the pressure tank outlet that feeds the house and the rest of house piping there should be a main shutoff valve.

Then go in to the house and open a faucet.

After a brief spurt of water you should see nothing coming out. If you do, then the main shutoff at the tank is a little leaky OR water is running by gravity from upper floor piping backwards into the lower floor faucet you opened. (so maybe try this upstairs, or wait and see if the flow stops).

If you do NOT see any water flowing in the house then the main shutoff valve between house and tank is good.

Then if you STILL see tank pressure dropping I'm guessing a check valve or foot valve or well piping are leaky.

Keep us posted.

...

Continue reading  at WATER PRESSURE PROBLEM DIAGNOSIS TABLE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see WATER PRESSURE PROBLEM DIAGNOSIS TABLE FAQs-2 - more recent questions and answers about fixing water pumps

Or see these

Recommended Articles

Suggested citation for this web page

WATER PRESSURE PROBLEM DIAGNOSIS TABLE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about how best to diagnose the cause of poor building water pressure or lost water pressure.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT