InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS

AFUE DEFINITION, RATINGS
AGE of AIR CONDITIONERS & HEAT PUMPS
AGE of HEATERS, BOILERS, FURNACES
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR FILTERS for HVAC SYSTEMS

AIR HANDLER / BLOWER UNITS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
APPLIANCE EFFICIENCY RATINGS
ASBESTOS IDENTIFICATION IN buildings

BACKDRAFTING HEATING EQUIPMENT
BACKFLOW PREVENTERS
BAROMETRIC DAMPERS
BASEBOARD HEAT

BIOGAS PRODUCTION & USE
BLEVE EXPLOSIONS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BLUE vs YELLOW COMBUSTION FLAMES
BLUERAY Recall

BOILERS, HEATING
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  BOILER COMPONENTS & PARTS
  BOILER CONTROLS & SWITCHES
  Air Bleeder Valves
  Air Scoops Purgers Separators
  AQUASTAT CONTROL Functions
  Boiler Pressure Controls & Settings
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  DIAGNOSE & FIX BOILER
  DRAFT REGULATORS, BAROMETRIC DAMPERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  OIL LINE QUICK STOP VALVES
  OIL LINE SAFETY VALVES
  Pressure Gauges, Boilers
  Pressure & Temperature Settings, Controls
  RELIEF VALVES - TP VALVES
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Reset Switch
  Water Feeder Valves, Hydronic Boiler
  Zone Valves

BOILER LEAKS CORROSION STAINS
BOILER LEAKS, HOW TO LOCATE
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PRESSURE & TEMPERATURE SETTINGS
BOOKSTORE - InspectAPedia
BUILDING SAFETY HAZARDS GUIDE

CAPACITORS for HARD STARTING MOTORS
CARBON DIOXIDE - CO2
CARBON MONOXIDE - CO
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
CHINESE DRYWALL HAZARDS
CIRCULATOR PUMPS & RELAYS
COOL OFF HEAT, Thermostat Switch
COMBUSTION AIR
COMBUSTION AIR for TIGHT buildings
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
COMPLETE COMBUSTION, Stoichiometric
CREOSOTE FIRE HAZARDS
CONDENSING BOILERS/FURNACES
CONDENSING BOILERS/FURNACES DAMAGE
CONVECTOR HEATERS - HYDRONIC COILS

DEFINITION of Heating & Cooling Terms
DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
DIAGNOSE & FIX HEATING PROBLEMS-FURNACE
DIRECT VENTS / SIDE WALL VENTS
DIRECTORY of OIL TANK EXPERTS

DRAFT HOODS - gas fired
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

DUCT INSULATION - Asbestos PapeR
DUCT SYSTEM & DUCT DEFECTS

ELECTRIC HEAT
HOT WATER HEATERS
DRAFT MEASUREMENT, CHIMNEYS & FLUES
DRAFT REGULATORS, DAMPERS, BOOSTERS

DUCT SYSTEM & DUCT DEFECTS
DUST CONTAMINATION FROM HVAC?

ELECTRIC HEAT, DIAGNOSIS, REPAIR
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES

FILTERS, AIR for HVAC SYSTEMS
FILTERS, OIL on HEATING EQUIPMENT

FIRE SAFETY CONTROLS
FIREPLACES & HEARTHS
FLAME COLOR, BLUE vs YELLOW COMBUSTION
FLOODED HEATING EQUIPMENT REPAIR
FLOODED WATER HEATER REPAIR
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FUEL OIL TYPES & CHARACTERISTICS
FUEL UNIT, HEATING OIL PUMPS

FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE EFFICIENCY, HIGH vs MID
FURNACE HEAT EXCHANGER LEAKS
FURNACE OPERATION DETAILS
FURNACE OPERATING TEMPERATURES

GALVANIC SCALE & METAL CORROSION
GAS BURNER Flame & Noise Defects
GAS FIRED WATER HEATERS
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
GEOTHERMAL HEATING SYSTEMS

HEAT EXCHANGER LEAKS
HEAT LOSS in buildings
HEAT LOSS DETECTION TOOLS
HEAT LOSS INDICATORS
HEAT LOSS PREVENTION PRIORITIES
HEAT LOSS R U & K VALUE CALCULATION
HEAT PUMPS, DiAGNOSIS, REPAIR
HEAT TAPES & CABLES on Roofs for Ice Dams
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL - OLD, USEABLE?
HEATING OIL PIPING TROUBLES
HEATING OIL SHELF LIFE
HEATING OIL SLUDGE
HEATING OIL USAGE RATE
HEATING SMALL LOADS
HEATING SYSTEM INSPECT DIAGNOSE REPAIR
HEATING SYSTEM NOISES
HEATING SYSTEM SERVICE & MAINTENANCE
HEATING SYSTEM TYPES
HIGH EFFICIENCY BOILERS/FURNACES
HOT WATER HEATERS
HOT WATER IMPROVEMENT

INSULATION INSPECTION & IMPROVEMENT

LP & Natural Gas Safety Hazards

MANUALS & PARTS GUIDES - HVAC
MIXING / ANTI-SCALD VALVES
MOTOR OVERLOAD RESET SWITCH

Natural Gas Combustion
NO HEAT - BOILER
NO HEAT - FURNACE
NOISE / SOUND DIAGNOSIS & CURE
NOISE AIR CONDITIONER / HEAT PUMP
NOISE, DUCT VIBRATION DAMPENERS
NOISE, HEATING SYSTEMS
NOISE, PLUMBING
NOISE, WATER HEATER

ODORS & SMELLS DIAGNOSIS & CURE
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER FUEL UNIT
OIL BURNER INSPECTION & REPAIR
OIL BURNER NOISE SMOKE ODORS
OIL BURNER NOZZLE & ELECTRODES
OIL BURNERS, RETENTION HEAD
OIL BURNER SOOT & PUFFBACKS
OIL FILTERS on HEATING EQUIPMENT
OIL FILTER MISSING
OIL FUEL TYPES & CHARACTERISTICS
OIL & GAS PIPING
OIL LINE CLOGGING FIX
OIL LINE QUICK STOP VALVES
OIL LINE SAFETY VALVES
OIL ODORS, LEAKY OIL TANK PIPING
OIL PUMP FUEL UNIT
OIL SPILL CLEANUP / PREVENTION
OIL TANKS

PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
PASCAL CALCULATIONS

RADIANT BARRIERS
RADIANT HEAT
RADIANT HEAT Floor Mistakes to Avoid
RADIANT HEAT TEMPERATURES
RADIANT SLAB FLOORING CHOICES
RADIANT SLAB TUBING & FLUID CHOICES
RADIATORS
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - TP Valves on Boilers
RELIEF VALVES - STEAM TP VALVES
RELIEF VALVES - Water Heaters
RELIEF VALVES - Water Tanks
Reset Switch - Heater Primary Control
Reset Switch Broken - Quick Repair
Reset Switch - Electric Motors
Reset Switch - Stack Relays

SAFETY, HEATING INSPECTION
SAFETY,HOME HEATING TIPS
Safety Recalls, Chimneys, Vents, Heaters
SPILL SWITCHES
STACK RELAY SWITCHES

STAIN DIAGNOSIS on BUILDING INTERIORS

STEAM HEATING SYSTEMS
  AQUASTAT CONTROL Functions
  BACKDRAFTING HEATING EQUIPMENT
  BACKFLOW PREVENTER VALVE, HEATING SYS
  BANGING HEATING PIPES RADIATORS
  CAD CELL RELAY SWITCH
  CHECK VALVES, HEATING SYSTEM
  Chemical treatments, Boiler
  Circulator Pumps & Relays
  COMBUSTION GASES & PARTICLE HAZARDS
  CONDENSATE RETURN PIPES, PUMPS, STEAM
  DIAGNOSE & FIX BOILER
  DRAFT HOODS - gas fired
  DRAFT MEASUREMENT, CHIMNEYS & FLUES
  DRAFT REGULATORS, DAMPERS, BOOSTERS
  ELECTRIC MOTOR OVERLOAD RESET SWITCH
  ELECTRICAL POWER SWITCH FOR HEAT
  Expansion Tanks
  FIRE SAFETY CONTROLS
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  MIXING / ANTI-SCALD VALVES
  Pressure & Temperature Settings, Controls
  Pressure Switch, Steam Boiler
  RELIEF VALVES - TP VALVES
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  Steam Vents
  LOW WATER CUTOFF CONTROLS
  WATER FEEDER Valves, Steam

TANKLESS COILS
THERMAL EXPANSION of MATERIALS
THERMAL MASS in buildings
THERMAL TRACKING & HEAT LOSS
THERMOSTATS, HEATING / COOLING
Transite Pipe Chimneys & FlueS

VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com

WATER HEATERS
WATER HEATER SAFETY
WATER HEATERS for HOME HEATING USE?
WATER HEATER NOISES
WATER HEATER SCALE - De-Liming Procedure
WATER HEATER SCALE PREVENTION
WINTERIZE A BUILDING
WOOD, COAL STOVES & FIREPLACES
WOOD STOVE SAFETY

ZONE VALVES

More Information

Photograph of  a modern oil-fired heating boilerHow to Diagnose & Fix Loss of Heat on Oil or Gas Fired Hot Water Heating Boiler Systems
InspectAPedia®  -      

  • How to diagnose loss of heat for heating boilers, hydronic heat systems, baseboards, radiators
  • Troubleshooting heating boiler oil or gas burners & controls
  • Troubleshooting heating systems using LP gas (propane) or natural gas
  • How to inspect & repair central hot water heating boilers - hydronic heating
  • Baseboard, radiator, convector heat inspection, defects, repairs
  • Questions & answers about how to fix a heating boiler that is not working - how to diagnose the loss of heat in a building when the heat source is an oil or gas fired boiler

Heating boiler problem diagnosis and repair guide - no heat or loss of heat calls: Here we explain how to recognize & diagnose no-heat problems with residential heating boilers, including loss of heat, heating boiler noises, leaks, odors, or smoke, and high heating costs. This article explains the diagnosis and correction of no heat conditions for water or hydronic or hot water or radiator or baseboard hot water heating systems. This website answers questions about all types of heating systems, advising on troubleshooting, inspection, diagnosis, and repairs.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

To Diagnose a "no heat" call the Homeowner or Heating System Inspector Must Know the Equipment

We describe how to inspect residential heating systems to inform home owners, buyers, and home inspectors of common heating system defects. The articles at this website describe how to recognize common heating system operating or safety defects, and how to save money on home heating costs.

If you don't know whether your heat is provided by a furnace (hot air) or boiler (hot water), or whether your fuel is oil, gas, or electric, and whether your heat is hot water, steam, or warm air, see HEATING SYSTEM TYPES.

If your heat is produced by a warm air furnace and you have no heat, instead of the article found here you should see HEATING LOSS DIAGNOSIS-FURNACES.

Hot Water Heating System: Once you confirm that your heat is made by hot water (a heating boiler) you might want to review hot water or "hydronic" heating systems at BOILER COMPONENTS & PARTS and BOILER OPERATION DETAILS where we describe the parts and operating sequence of hot water heating systems.

Note: some hybrid or mixed heating systems combine both hot water and hot air to heat a building, such as water to air systems which use a heating boiler (oil, gas, or electric) to heat water which circulates through (and inside of) a heat exchanger (that looks like a car radiator) - described at HEATING SYSTEM TYPES.

Types of Defects and Problems with Hot Water Heating Boilers - Hydronic Heating Systems, Loss of Heat, Noises, Leaks

What sort of defects should you look for when inspecting a heating system?

  • Loss of heat in your building? - boiler or furnace won't operate, or system operates but heat is not produced in the living area - we outline a step by step diagnostic procedure for "no heat" conditions just below.
  • Improper Heating System Function: noises, odors, soot, unreliability, inadequate heat distribution
  • Unsafe conditions on the heating system
  • Missing Heating System Components: safety controls, operating aids
  • Unreliable heating systems or heating systems at or near the end of their useful life
  • Improper Heating System Construction/Installation
  • Heating System Damage: leaks, mechanical damage
  • Clues of potential other heating system defects: leaks, corrosion, stains, abnormal temperature or pressure, high heating fuel bills
  • No domestic hot water for washing and bathing? This is not usually a home heating system problem, but if your hot water is made by a tankless coil and a gas or oil fired heating boiler, the problem could be with the heating boiler itself. If your water heater is not working, find your water heater type at WATER HEATERS.

How to Diagnose Loss of Heat With Oil-Fired or Gas-Fired Hot Water or Warm Air Heating Systems

If the heating boiler oil burner is not turning on at all check the causes listed on this page. We'll take you through photo-illustrated step by step things to do when you have no heat and you need to determine what's wrong. First let's review these simple "no heat" concepts .

NO HEAT: BURNER OFF, SAFETY NOT TRIPPED: - Oil or gas burner has stopped, no safety switch is tripped

1. Is the thermostat calling for heat? check that the room thermostat setting is at least 5 degrees above the actual room temperature. See THERMOSTATS.

2. No electrical power: check that all of the switches that power on the oil or gas burner are in the "on" position. Check heating circuit fuses & circuit breakers, not just the wall switch. We discuss this in detail just below.

3. Is there fuel in the oil tank or LP gas tank? Check your oil tank or LP gas tank tank gauge.

Out of heating oil? If the marker in your oil tank gauge reads 1/8 full or less, or is at the bottom or out of sight you are probably out of oil. If your oil tank is buried, and if you do not have an indoor (remote) fuel level gauge, the oil level is checked in the tank by removing the tank filler pipe cap and using a long (clean) stick (or in emergency a clean string and weight) to measure the depth of heating oil in the tank.

Remember that a problem with the oil piping, oil filter, or fuel unit can also cause no oil to be delivered to the oil burner even if plenty of oil is in the tank. See OIL BURNER FUEL UNIT for some helpful diagnostics & also OIL & GAS PIPING.

Out of LP liquid propane gas
? Check the gauge on your propane tank. If the reading is 10% or less you are out of fuel.

4. Electric motor problem at the burner or blower fan: Check that an electric motor (for the oil burner, gas burner, or blower assembly) reset switch may have tripped. See our notes above about electric motors, and see Reset Switch - Electric Motors.

5. Aquastat or cad cell control or relay trouble: if you hear or have ever heard buzzing from any heating system control that includes a relay switch, watch out for a control cover that is in contact with a relay switch in the unit. If the cover is lightly touching the relay switch the control may simply buzz when the relay is trying to move. But a too-tight control cover can also prevent a relay from operating, leading to loss of heat. Simply pulling off the cover to let the relay move freely can immediately discover and "fix" this problem. Details and illustrations are at HEATING SYSTEM NOISES.

NO HEAT: BURNER HAS TURNED OFF ON SAFETY: Oil or gas burner has stopped, the safety switch is "off" or "tripped"

If you are not sure how to find and check the safety control reset buttons on your heating system, we describe these controls in more detail just a bit further on in this article.

The burner on your heating boiler, furnace, or water heater has shut down, if a red "reset button" has popped up on the burner primary control or on an electric motor that operates the system. This condition is called "Safety Off".

Watch out: Before re-setting the safety switch or button, it's a good idea check the following five common causes of loss of heat leading to a Safety Off condition. Photos and details follow these short paragraphs.

How to press the heating system reset button: If you do not see anything wrong, you can try re-setting the heating system: press and hold the red reset button down for 3 seconds and release it. If the heating system has electricity it will try to re-start.

Watch out: If the system does not keep running smoothly don't keep pressing the reset button - that could flood the combustion chamber with unburned fuel, causing a dangerous puff-back. Just press the reset button once. If the heating system starts and runs ok, you still should request a service call, but you can have heat while you're waiting.

1. Heating fuel failures - out of oil in the oil tank, clogged oil filter, clogged oil nozzle, oil line has been bent, crimped, clogged, clogged oil pump strainer (fuel unit strainer), or inability of the fuel unit to pump oil (broken motor shaft, missing internal bypass plug on a two line oil tank system, an air leak in the oil inlet line, or a leaky foot valve in the oil tank causing loss of oil prime). if the oil tank is outdoors in freezing weather the oil in the tank or in an oil line may have become waxy or jelled.

2. Oil burner motor failure: the electric motor that runs the oil burner may itself have gone off on reset. Some causes of electric motor failure: one pipe oil system with the bypass plug installed in the fuel unit (oil pump) causing excessive pressure and stalling the motor; centrifugal motor switch sticking (try banging on the motor once); motor condenser burned out; motor stator or internal windings burned or shorted; motor bearing failure. Try re-starting the motor - see Reset Switch - Electric Motors

3. Oil burner ignition failure: the oil burner's ignition transformer terminals are loose; the electrodes on the burner nozzle are dirty or not set to the proper gap; the oil is contaminated and is hard to ignite; the ignition transformer has become weak or has burned out (look for tar oozing out of the ignition transformer container); the oil burner nozzle is clogged preventing oil from contacting the ignition spark arc; the ignition electrode(s) are grounded on the air tube of the burner;

4. Faulty heating system control operation: the safety sensor that checks that a good oil burner flame has been established is not working; a stack relay spring or cad cell eye may be dirty with soot; the stack temperature may be too low for the stack relay (boiler is under-fired); the oil burner has been cycling on and off to frequently (a problem with the thermostat).

5. Irregular stack temperatures: in the flue can cause oil burner draft and temperature or control problems. Downdrafts (missing chimney cap), insufficient draft due to chimney problems, or fluctuating oil burner flame may be at fault. Also see CHIMNEY INSPECTION DIAGNOSIS REPAIR.

-- some of this material is paraphrased from Audel.

Oil Burner Operating Problems: Oil or Gas Burner rough, noisy, smoky, smelly

The heating burner operates but not properly. See OIL BURNER NOISE SMOKE ODORS

Next let's check each cause of no heat in detail; if your system uses warm air heat instead of water or steam, review the check-items just below before going to HEATING LOSS DIAGNOSIS-FURNACES.

SAFETY WARNING: If a heating system oil burner has been deliberately "shut down" and you don't know when or by whom this step was taken, beware of turning the heating system back on without an inspection and safety check by an expert technician.

Heaing system emergency switch (C) Daniel Friedman
  • Electrical power to the heating boiler or oil burner is OFF: check the circuit breaker or fuse supplying power to the unit; check the service switch at the furnace or air handler, and if the system is air conditioning or a heat pump, check the service switch outside at the compressor/condenser unit to be sure it is "on".

    Make sure that electrical power is on for all of the heating system components. Check local switches at the boiler, wall mounted boiler switches at the stairwell down to the basement or utility room or in other areas, and check the circuit breakers or fuses in the electrical panel.

Is the heating boiler turned on? Is there electric power to all of the heating system components such as an oil burner at the boiler and power to the circulator pumps?


Photograph of an oil fired heater stack relay
  • Oil Burner safety reset switch is OFF or TRIPPED: the heating or air conditioning system may have been turned off on reset - see our "off on reset" and other advice at  CAD CELL RELAY SWITCH (modern equipment).

    LP and natural gas fired heating equipment and water heaters also have safety controls including temperature limit controls and gas spillage sensors (see list of reset switches below).

    For gas heat, turn off electrical power to the gas fired heater using the service switch. Wait two minutes and turn the electricity back on. See ELECTRICAL POWER SWITCH FOR HEAT. This will reset most gas heating equipment.

    For oil heat:
    are you sure there is no safety or reset button tripped?

Where are all the heating system reset buttons? If you are looking for the main reset button on heating equipment you'll want to see: AQUASTAT CONTROL Functions and CAD CELL RELAY SWITCH (hot water boilers and some water heaters), Stack Relay Switch on older oil fired boilers and furnaces, SPILL SWITCHES (gas fired equipment), and also Low Water Cutoff Controls on steam heating systems. At ELECTRIC MOTOR OVERLOAD RESET SWITCH we discuss the thermal overload switch and reset button that is found on many electric motors including those operating air conditioning fans, heating system oil burners, and furnace blowers and motors.

A Stack relay switch may be installed on the flue vent connector and may be in the "safety - off" position. To identify and reset this control see   Stack Relay Switch. Stack relays are found on older oil fired furnaces and boilers.

  • Check the heating fuel supply again: if it is a gas furnace, is the gas turned on? If your gas is from bottled or LP gas, is the tank empty? If it is an oil fired heating furnace, check the gauge on the oil tank. Are you out of oil? See OIL TANK GAUGES.

    If you're out of oil or gas call your oil or gas company and request an emergency delivery. For oil systems, usually the delivery person will also need to enter the building to bleed air from the oil lines in order to get the oil burner operating again. For gas fired heating equipment the driver may want all gas appliances turned off in the building during delivery.

Still no heat? Once you have assured that you have heating fuel and that electrical power is turned on to the heating unit, if you still don't have heat check these controls:

  • Thermostat is in the "off" position or is set to a temperature that does not call for heating (or cooling) See FAN AUTO ON Thermostat Switch for details about what turns the blower fan on and off.
  • Flue gas spill switch: If your heating boiler is gas-fired (natural gas or "bottled" LP gas), a flue gas spillage switch may have shut the system down after sensing possibly dangerous flue gases (that can contain fatal carbon monoxide). See   Spill Switches. This switch will not normally be found on oil fired heating equipment.
  • Is there fuel for the boiler ?: check the oil tank gauge (see OIL TANK GAUGES for tips on how to find, read,and test the oil tank gauge. If the heating boiler is fired by natural or LP gas and not oil, check that no one has shut the gas supply valves.

    Oil burner motor coupling: another cause of an oil burner starting to run but never igniting at all may be a broken or slipping coupling (or a frozen coupling) between the oil burner motor and the fuel unit. In this case the burner starts in response to a call for heat, but there will be no ignition whatsoever because no oil is being delivered to the nozzle assembly.

    Other reasons for no oil flow to the oil burner include: an oil safety valve that has been "closed" (someone turned it the wrong way), low oil or no oil in the heating oil tank (the tank may not be completely empty but oil may be below the oil pickup line if the oil lines are exiting at the top of the tank), a clogged oil filter or fuel unit strainer, a clogged oil burner nozzle, a air leak in the heating oil supply piping, or a crimp or clog or restriction in the oil piping. If you recently ran out of oil and then got a delivery, and if your system uses a single oil line between tank and burner, the line or fuel unit may be air bound and needs to be bled. [8]

  • Is the thermostat calling for heat? and is the temperature at the thermostat lower than the thermostat setting?

  • Does the oil burner start but then shut off? Is the system "off on reset"? if so the red "reset" button will have popped up on the oil burner control (or possibly on an electric motor operating the oil burner) and the system has an operating problem and needs service. It may be possible to re-start an oil burner that has turned itself off by pressing the red reset button ONCE.

    If the heating boiler or furnace re-starts and runs acceptably, you can have heat while waiting for the service technician but the system still needs inspection, service, and possibly other repairs before it can operate safely and reliably. If you push the reset button and the burner does not start and keep running for five minutes or more, DO NOT try again as you may flood the system with oil and make restarting difficult and dangerous.


  • Is the oil burner motor off on reset? See MOTOR OVERLOAD RESET SWITCH

  • Boilers-Hydronic Heat: Is hot water water circulating?

    • Check the hot water circulator: Test to see if the circulator is operating Feeling the hot water distribution piping (Watch out it should be HOT!). Feeling the piping can indicate if circulator is running or not -- a quick change in temperature means the circulator works; slow change in temperature may occur if the circulator does not work but hot water is circulating by convection.
    • Check for a bad zone valve or bad circulator pump relay. If the building has more than one heating zone it probably uses either multiple circulator pumps, each of which is operated by a circulator relay switch that is in turn operated by a wall thermostat, or it uses multiple zone valves, each of which is operated by a thermostat. A bad circulator motor or pump, a bad circulator relay (or even a circulator relay cover that is pressed against and jamming the relay switch), or a stuck zone valve (common on some models) will prevent heating water from circulating in that zone while other zones may work fine.

    • Check hot water baseboards: if some baseboards are hot and others cold, are they all on the same heating zone? If not, are all of the thermostats turned up? If some heating baseboards are hot and others cold and we're sure that they're on the same zone, then the system is probably air-blocked. A heating circulator pump is capable of pushing water around in the loop of heating baseboard but is often not capable of overcoming a section of baseboard that contains a large bubble of air.

      It's necessary to remove such air blocks. If air blocking has been recurrent a previous owner may have installed air bleeders at strategic points. The bleeder can be opened slightly and carefully, to permit air to escape. As soon as water starts coming out of an air bleeder valve it can be closed. Automatic air purge devices are available and are usually installed right at the heating boiler but sometimes additional ones are needed at higher levels in the building.

    • Check hot water radiators or convectors: if some radiators or wall convectors are hot and others are cold, and provided that the individual feed valves located at each of these devices is open (turned counterclockwise) the radiator or convector may be air blocked. Usually an individual air bleed valve is located on each of these devices.
  • Check the Oil Heating Equipment Safety Controls and Switches - see FIRE SAFETY CONTROLS for photos and details

How to Diagnose Soot or Noises during Heating System & Oil Burner Operation

For full details of this topic be sure to see OIL BURNER NOISE SMOKE ODORS.

  • Noises during oil burner startup - a "bang" or puffback which blows soot into the room through the barometric damper or through other equipment openings: the oil pump may not be shutting down properly at the end of an oil burn cycle, leaking incompletely burned oil into the combustion chamber. That oil ignites at startup causing a potentially dangerous puffback. Immediate service and repair are needed.

  • Soot and black marks in the living area can sometimes indicate an unsafe or poorly-functioning heating system but these marks can also be normal in some buildings depending on other conditions. Details about soot tracking are at THERMAL TRACKING.

    Watch out: Safety warning about soot: Sooting can occur with both gas fired and oil fired systems. Soot coming from a gas fired heater is probably indicating a very dangerous condition risking carbon monoxide poisoning. If a gas fired appliance is producing soot, it should be turned off and Immediate service is needed. See COMBUSTION AIR DEFECTS and also SOOT on OIL FIRED HEATING EQUIPMENT and GAS FIRED WATER HEATERS for safety warnings about soot at heating appliances.

  • Noises during oil burner startup - a "rumbling" sound (which usually continues all during operation" or a "stumbling" sound in the combustion chamber probably indicates that the system needs inspection and cleaning very soon. Some noise is normal however, but the normal sounds tend to be more smooth and continuous.

  • Noises during oil burner shut-down - a stumbling or rumbling after the oil burner motor has stopped, indicate that oil is continuing to leak into the combustion chamber and risks a dangerous puffback - see "Noises during oil burner startup" above. Immediate service is recommended.

  • Noises of shrieks or grinding coming from the electric motor or oil pump on the oil burner mean that immediate service is needed - probably a bearing is failing.

  • Startup problems: noises and clues of puff back: if you see flapping at the barometric damper or if you see or hear vibrations in the system, or if you see black soot on or near heating equipment the system may be unsafe and prompt service is needed

  • Noises from radiators or heating baseboards: clanking pipes or sharp snapping noises may be heard as a normal consequence of expansion of metals during the heating cycle. These noises can often be eliminated or reduced by careful routing of piping and by allowing room around heating pipes for expansion, but probably not eliminated in the case of hot water baseboards.

    Bubbling or rumbling noises
    in hot water heating piping can be caused by air in the heating lines. If the amount of air becomes excessive the system may be unable to circulate hot water and extra steps to bleed unwanted air will be required.

    Hissing sounds
    such as air escaping from radiators or other piping where air bleeder valves are installed are normal but should be brief and uncommon. If you constantly hear air hissing from radiator bleed valves double check that you understand what kind of heat you have - hissing from bleeder valves on steam heat radiators as heat is coming up in the building is normal.

How to Evaluate Heating Boiler Leaks & Corrosion

For full details of this topic be sure to see BOILER LEAKS CORROSION STAINS.

When observing evidence of leaks on a heating boiler, keep these points in mind:

  • Even serious leaks may never show up as "wet" spots: A boiler may be leaking but you may see no actual water: during the heating season the boiler may always be hot, causing small leaks on the boiler or on heating piping to simply evaporate. But such leaks will usually be visually very evident: look for a build-up of corrosion, green or white or other colored mineral salts, or look for rust or water stains on the equipment.

  • Internal heating boiler leaks: Some critical boiler leaks may be internal and not visible by simple inspection, such as a leak inside the boiler heat exchanger which may pass water into the combustion chamber. A service technician or a skilled home inspector should be able to spot evidence of these leaks.

  • Surface rust, light, superficial rusting, is generally repairable. Clean the area and fix the leak when the boiler is next serviced and monitor for any future leaks.

  • Exfoliation, or thick flaking rust on any boiler but particularly on a steel heating boiler is very serious, possibly not repairable, and risks loss of the boiler as well as sudden loss of heat in the building. Examples of this problem are at TANKLESS COILS

  • Leaks related to temperature or pressure: Some leaks occur only at peak operating temperature-e-g at relief valve. On some heating boilers such as some cast-iron units, leaks may occur between boiler sections when the system is cold - on these models some technicians prefer to keep a little heat in the boiler year-round to avoid this problem. Leaks between boiler sections may be repairable but if left unattended can destroy the equipment.

A Catalog of Common Heating System Leak Points - Where to Watch for Heating System Leaks

  • Tankless Coil mounting plate - see rust stains below and around plate - see TANKLESS COILS
  • Pipe fittings anywhere in the system, including in water supply piping to a boiler, hot water distribution piping, or at face of coil plate - mineral salts and stains may show even a small leak though no water may be visible (it evaporates quickly on hot heating system components)
  • Leaks around bolt openings - suspect hidden damage
  • Leaks between sections of a cast iron boiler
  • Leaks at the circulating pump mounting flanges
  • Leaks at the boiler temperature/pressure relief valve. This leak may be very dangerous as corrosion from water passing through the valve may prevent its safe operation in an emergency. Prompt expert inspection and repair are needed. Watch for leaks below the valve's mouth or discharge pipe (a pipe should extend from the relief valve to a few inches from the floor) or watch for corrosion at the tip of the discharge pipe. Gently feel inside the tip of this pipe to see if it's wet. DO NOT TRY TO TEST or open or operate the relief valve itself.
    Safety warning: a leaky relief valve indicates an potentially very dangerous condition; prompt service is needed.
  • Leaks at air bleeder valves - at the boiler or remote where such bleeders are placed on heating piping or baseboards or radiators
  • Leaks at radiator control valves or between radiator sections
  • Leaks at heating baseboards, at poorly-soldered copper pipe fittings on finned copper baseboard heating systems
  • Leaks due to frozen and burst piping or in extreme cases, frozen and burst heating boilers themselves. Freezing pipes produce very distinctive types of damage such as splits or separation at solder joints.

How to Recognize & Diagnose Inadequate Combustion Air for Oil-Fired Heating Systems

For full details of this topic, also see Inadequate Combustion Air

Heating system combustion air sketch

Lack of adequate combustion air can result in improper system operation, sooting, increased heating cost, damage to oil burner components (back pressure heat can destroy an ignition transformer), higher and more frequent heating service costs, loss of heat, noises, smoke, and potentially, the production of carbon monoxide or other flue or combustion gases which escape into the building - potentially dangerous

Safety warning: The sketch shown here, courtesy of Carson Dunlop, explains how dangerous furnace back-drafting can occur when there is insufficient combustion air. These conditions can not only release flue gases into the occupied space, but they are likely to cause the production of potentially fatal carbon monoxide.

We've seen heating equipment that seemed to work just fine during its adjustment because the service technician was working with the door to the furnace or boiler room open. But when she left the system and closed the furnace room door, suddenly there was insufficient combustion air.

Also see Unsafe Air Conditioning or Heating Duct Openings which describes the risks of reduced combustion air on hot air heating systems when certain return air duct defects are present, and also see CARBON MONOXIDE - CO and CHIMNEY INSPECTION DIAGNOSIS REPAIR

A Guide to Heating Equipment Malfunctions & Their Implications

  • Noises & soot buildup can lead to a potentially dangerous puffback which can damage the heating equipment and blow soot and smoke throughout the building.
  • Leaks on hot water heating systems are never acceptable, anywhere. Leaking relief valves need immediate attention and repair (Leaking relief valve could be due to water-logged expansion tank, improper control settings (temperature too high), improper automatic water feeder operation (pressure too high), or defective valve (leaky). True, you only have to report the valve. Did you miss problems at the other components?) Corroded relief valves also need to be test by a service technician and repaired or replaced
  • Relief Valves: Do not touch the heating boiler or water heater temperature or pressure relief valve - it may open and fail to shut down. A relief valve which does not work is dangerous since the system is missing an important safety device. Should an over pressure or over temperature condition develop for other reasons, the boiler could explode.
  • Corrosion on heating system parts: Do not pick at corrosion as you may start a catastrophic, un-stoppable leak requiring total system shut-down. Leaks left un repaired can destroy heating equipment.
  • Tankless coils for making hot water: If there is different water pressure/flow observed in the kitchen in which the hot water pressure is significantly less than cold, even before examining the building's mechanical systems you may speculate that a tankless coil installed may be installed. What other clues suggest that the local water supply may be hard in minerals and that there may be a risk of clogged piping? When the water supply is high in minerals, the hot water pipes or tankless coils clog up before cold water piping. Is a water softener installed? Is there known "hard" water--have mineral deposits clogged the coil? Are there "cleanout" plumbing fittings on the tankless coil piping? Does this suggest a history of clogging and acid-flush treatments? A clogged coil can be repaired or replaced. How severe was that rust you observed at the tankless coil mounting plate? Severe rust may mean that the boiler must be replaced.

Examples of Heating System Defects with Important Implications

  • Lack of adequate combustion air can result in improper system operation, sooting, loss of heat, noises, smoke, and potentially, the production of carbon monoxide or other flue or combustion gases which escape into the building - potentially dangerous
  • Leaky oil at an oil burner ignition transformer: watch for back pressure in combustion chamber--watch out for blocked heating flue or blocked chimney - these would be unsafe, or the heater may be unreliable. An unreliable heater can lead to frozen burst pipes and costly building damage. A blocked chimney could lead to a potentially fatal carbon monoxide hazard.
  • Unusual interior moisture conditions, noises, smoke, or odors during heating season--watch for blocked chimney or poor flue vent connections
  • Equipment recalls: Specific heating system problem brands Repco, Blueray etc.
    [Do not confuse Repco™ heating boilers, which had fire chamber and other failures, with other products (REPCO pumps, REPCO controls, REPCO water conditioners, or water treatment that carry the Repco name. Those products are distinct from REPCO heating boilers and are produced/distributed by the R.E. Prescott Company. Further, we are unaware of any remaining warranty or replacement support for failed or antiquated Repco heating boilers.]
  • Blueray Heating Boilers/Furnaces Safety Recall by the US CPSC, with additional history, photos, and technical details; Blue Flame Blue Ray
  • Carbon Dioxide Gas Toxicity
  • Carbon Monoxide Gas Toxicity, exposure limits, building inspection for CO hazards
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Home Inspection Report Language Library: Gas Fuel Piping or Tank Faults Basic advice - home inspection report language suggestions
  • Home Inspection Report Language Library: Buried Oil Tanks, Basic home buyer advice - home inspection report language suggestions
  • Home Inspection Report Language Library: Defects in Oil Tank Installations, Tanks, and Heating Oil Piping
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair

Questions & Answers regarding this article

Questions & answers about how to fix a heating boiler that is not working - how to diagnose the loss of heat in a building when the heat source is an oil or gas fired boiler

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

NO HEAT - BOILER / FURNACE DIAGNOSIS - see detailed links at page left and in the article above

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • R.E. Prescott Company, a producer of other REPCO™ residential and industrial products as well as a provider of design-build engineering services is at 10 Railroad Avenue, Exeter, NH 03833. Tel: 603-722-04321 or 888-786-7482. Trish O'Keefe from Prescott informed us (10/7/2009) that their company had nothing to do with the failed Repco heating boilers discussed at InspectAPedia.com. She wrote:
    • Our company manufactures & distributes residential water treatment equipment, including our Repco line of conditioners. We have a plumbing & heating supply dept as well. We are mistaken for the Repco Boiler company on a regular basis, most frequently in Oct. and Nov.
    • Any information you could give me on the other Repco company would be appreciated. We've assumed it is no longer in business, and we'd like to know that for sure. Many callers want to know where to get replacement parts and I would be glad to direct them if I knew...plus there's always a chance they might be interested in a Crown Boiler instead.
  • Thanks to Bottini Fuel service manager Ron Thomas for discussing aquastat functions, low limit controls, oil burner short cycling causes, and boiler maintenance, reliability, and service contracts 4/13/2010. Bottini Fuel is a residential and commercial heating oil distributor and oil heat service company in Wappingers Falls, NY and with offices in other New York locations. Bottini Fuel, 2785 W Main St, Wappingers Falls NY, 12590-1576 (845) 297-5580 more contact information for Bottini Fuel
  • [8] Suntec Model A-7400 Fuel Unit Solenoid Dumping Pump,
    Suntec Industries Inc., 60 Aberdeen Drive - PO Box 5000 Glasgow, KY 42142-5000 - USA Tel : 270 651 7116 - Fax : 270 651 9276 e-Mail : info@suntecpumps.com and
    Suntec Industries France, 1 Rue Lavoisier - B.P. 102 F-21603 LONGVIC Cedex - FRANCE Tel : +33 (0)3 80 70 60 70 - Fax : +33 (0)3 80 70 61 11 e-Mail : information@suntec.fr, [copy on file as /heating/Oil pumps fuel units/Sunted_Solenoid_DumpingPPump.pdf] ,
    Also /Suntech_Solonoid_Safety_Valves.pdf (brochure)
    web search 4/19/12, original source: http://www.suntecpumps.com/Suntecus/PDFs/Form%202740%20
    -%20Solenoid%20Dumping%20Pump.pdf

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • DUST CONTAMINATION FROM HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Fuel Oil & Oil Heating Magazine, 3621 Hill Rd., Parsippany, NJ 07054, 973-331-9545
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • Links to our list of additional information on heating system inspection, repair, maintenance
  • ...

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com