Building Inspection, Diagnosis & Repair Info

 a flue gas spill switchFlue Gas Spillage Switches on Gas or Oil Fired Equipment

  • POST a QUESTION or COMMENT about gas fired heating equipment spill switches: diagnosis, repair, replacement, function, safety features

Guide to flue gas spill switches on gas or oil fired heating equipment:

What is a flue gas spill switch or gas spillage detector? How do flue gas or draft hood spill switches work? Where should spill switches be installed? How are spill switches tested?

What causes nuisance or legitimate flue gas spill switches to trip? How do we correct un-wanted loss of heat due to flue gas spill detector switch operation or nuisance tripping?

Here we explain the installation, function, & troubleshooting Flue Gas Spill Switches and we provide a Guide to inspecting Furnace or Boiler Flue Gas Spill Switches on gas fired equipment such as heating boilers, warm air furnaces, water heaters.

We describe the Purpose, Inspection, Repair Troubleshooting Guide for flue gas spill switches which are installed at dampers or burners on gas fired equipment.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Guide to Furnace or Boiler Flue Gas Spill Switches on gas fired equipment - Purpose, Inspection, Repair

Photograph of a flue gas spill switch sensor

Article Contents:

This article discusses flue gas spillage detectors used on gas or oil fired heating equipment found in buildings.

 

What is a furnace, boiler, or water heater flue gas spill switch?

Flue gas spill switch installation kit sold by Zoro cited & discussed at InspectApedia.com

Spillage detector switches monitor temperature or actual gas content of flue gases that might spill from the vent or draft hood or burner area of a gas fired heating appliance.

When unsafe spillage occurs the switch operates to turn off the heating appliance using one of several methods. Most flue gas spillage or thermal safety switches must be re-set manually though a few models include an automatic reset feature.

Synonyms for flue gas spill switch include thermal sensor switch, thermal safety switch, and blocked vent safety switch.

Since escaping combustion gases in a building are dangerous (forming a potentially fatal carbon monoxide hazard), if the sensor gets hot from flue gases flowing past its surface, it is designed to turn off the fuel supply to the gas burner. Some flue gas spillage detectors operate to close the gas supply to the heating appliance.

A spill switch may be found at the draft hood on any modern gas fired appliance, such as a heating furnace (hot air heat), a heating boiler (hot water heat or steam heat), or a water heater.

Similar gas detection or safety device are also used on gas log fireplaces and on coal fired heating systems as well as in industrial applications.

Some flue gas spill detectors actively detect flue gases or carbon monoxide but the simplest models respond to temperature by detecting the hot gases associated with flue gases on gas fired heating equipment. This little flue gas spillage sensor sensor, or two or more of them, form an important safety device that feels the heat of escaping combustion gases that ought to be going up the flue or chimney.

What causes unsafe flue gas spillage:

Bachrach Corporation, a manufacturer of heating system test equipment opines that gas fired equipment is more likely to have flue gas spillage from a blocked chimney than from building depressurization due to inadequate combustion air supply.

We're not sure what data supports that view but more details are atReferences or Citations where the effects on flue gas spillage due to building depressurization are discussed.

One author warns that even where CO was not detected in some building depressurization studies other harmful flue gases such as NOX may be present.

Certainly home inspectors find many heating appliances installed in tiny closets with no outside combustion air and a door that, when shut, blocks off air to the appliance.

We have also observed that gas fired heating equipment operated just fine in a building until a new owner installed a whole house ventilation fan system.

Where are combustion gas spillage switches installed?

Photograph of a flue gas spill switch sensor

In the photo above a spill switch was not installed but had been simply left loose, disconnected, atop the water heater.

Combustion gas or flue gas spill switches are usually installed at the edge of the gas fired appliance draft hood. Some appliances may also have a spill switch installed at the gas burner opening itself.

This photo shows a spill switch at a gas fired water heater draft hood. In the somewhat blurry photo of dog hair blocking a heater draft hood (above) you can also make out the spill switch and its wire at the right edge of the draft hood in that photo.

Watch out: as we explain in more detail just below

at FLUE GAS SPILL DETECTOR MALFUNCTIONS,

an improperly installed or improperly-located spillage switch detector can cause either nuisance tripping (spill switch shuts off heat when it should not) or unsafe operation (spill switch fails to detect dangerous flue gas spillage).

Watch out: also to be sure to select the proper spillage switch for the type of heater you are protecting. For example, Tjernlund's spillage switch instructions include additional details for spillage switch use on water heaters and on furnaces and boilers, from which we excerpt:

Gas fired water heaters:

Millivolt water heaters require the Tjernlund Model JA-1 (P/N 950-0470), Thermocouple Junction Adapter (ordered separately). Connect ends of six foot cable to spade connections on Thermocouple Adapter.

Gas fired boilers & furnaces: Splice ends of six foot cable in a series circuit between the thermostat and gas valve or burner control.

Using cable routing tabs from wire routing packet, attach 6’ cable to appliance maintaining a safe distance from hot surfaces, e.g. appliance vent pipe and hot water pipes. - Tjernlund's,

retrieved 12/10/1997, original source cited in detail

at FLUE GAS SPILL SWITCH SOURCES & SELECTION

Oil fired boilers & furnaces:

select the proper thermal switch for the heating equipment you are protecting, then see the instructions for the specific switch;

See OIL BURNER FLUE GAS SPILLAGE SWITCHES

What goes wrong with flue gas spillage detection switches

Missing flue gas spill switches: we've seen these switches removed from modern water heaters, gas boilers, or gas furnaces when they were originally installed.

If you see holes drilled into the edge of a draft hood or other marks indicating that a device has been removed, or if you see the devices themselves lying loose, perhaps on or near the equipment, an expert service technician should examine the heater promptly as it may be unsafe.

Improperly-installed flue gas spill switch:

if the spillage switch sensing area is in contact with metal surfaces such as the flue or the draft hood, the heat of that metal may cause the switch to malfunction.

The flue spillage switch sensor should be mounted so that it monitors the temperature of gases spilling out of the heating appliance such as at the draft hood, vent, or chimney or on some systems near the gas burners.

Misplaced flue spillage switches:

similarly to the improperly installed spill switches whose temperature sensor should not touch metal surfaces of the heating system, the spill switch needs to be installed in the proper location so that if a chimney blockage or some other operating problem causes combustion gases to spill out of the appliance into the building, the flow of flue gases, while still warm, will pass over the switch sensor.

There may be other flue spillage switches which sense carbon monoxide (CO) or other gases directly and without depending on the gas temperature.

Older heaters with no flue spill switch:

On older heating systems these safety switches may not be installed at all. A

spill switch or a set of them can be added to almost any gas fired appliance, but it is likely that the gas control valve/regulator will need to be replaced too, since the old regulator may not have a point to which the spill switch's sensor wire can be connected to tell the valve to close.

Flue gas spill switch operating failure:

While a spill switch could simply fail to sense passing hot gases and thus not perform its safety function of turning off the heater, or while such as switch might simply fail internally, forcing the heater to turn off when it should not, in our experience these are rare events.

We do not have at hand industry failure rates for this device but we suspect that installation errors or omissions are far more common.

Flue Gas Spillage Switch or Thermal Switches Available for Oil Fired Heating Equipment

Can and or should spill switches be installed on a oil fired furnace barometirc damper?

Our reader asked:

Can and or should spill switches be installed on a oil fired furnace barometirc damper? - 12 Sept 2015 shell@scrantonlink.com

Answer: yes thermal switches can be selected to protect various types of oil fired heating equipment including furnaces, boilers, steam boilers, and water heaters

Yes, there are flue gas spillage switches designed for the (usually higher) temperature range produced by oil fired heating equipment and that can be mounted at a barometric damper on an oil fired heating flue.

Most thermal safety switches operate by being wired in series with the electrical power circuit supplying the burner (gas or oil). When the thermal safety switch has been exposed to a specific temperature for a specific time the switch "opens" to turn off the burner.

The spill switches discussed at the article series beginning

at FLUE GAS SPILL SWITCH TRIPPING & RESET

discuss both oil and gas fired heating equipment flue gas spillage devices.

Watch out:  Because most flue spillage sensors detect heat rather than the specific gases that might be emitted from the heating equipment the safety switch must be matched to

Field Controls, for example, offers such devices. The term usually used is "thermal switch" or "thermal switches for oil fired heating equipment".

These flue gas spillage devices sense heat, must be selected for the proper fuel and application (or else your system would be unsafe as it'd not be properly protected), and are sold in both manual reset and automatic reset spill switch sensor switch forms.

Flue gas spillage or thermal switches also vary by their response time. You may have trouble with a too-fast-acting switch if in normal operation there is a brief burst of heat from a barometric damper - as happens on some oil fired heating equipment.

Field Controls Thermal switch models include FTS-4, FTS-6, GSK250-M (for steam boilers), GSJ0160-M for draft-induced furnaces, and about eight other models. You'll see that it is essential to choose the proper thermals sensor switch.

Contact Field Controls at Field Controls, 2630 Airport Road, Kinston, NC 28504 USA, Phone: 252.522.3031 Fax: 252.522.0214 sales@fieldcontrols.com Website: fieldcontrols.com Thermal safety switch specifications source: http://www.fieldcontrols.com/thermal-safety-switches retrieved 12 Sept 2015

Content for id "Research" Goes Here

Flue Gas Spill Detector History & Patent Research

Research on Flue Gas Spillage Sensors

 

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Spill detector switch was activated while I was spray-painting in the basement

I had done some spray painting in the cellar, where my gas-fired boiler is located, I opened a cellar window, and activated the whole-house fan to draw the unpleasant smell out of the cellar upstairs and out of the house.

There wasn't enough air flow through the small window, and the spillage detector was activated.

No problems after reset after several days. On 2018-04-29 by ColdinNewJersey

by (mod) - OPINION - sounds normal

That sounds like a reasonable diagnosis.


Safety concern if the temperature sensing fule gas spill switch is for too-high a temperature?

I got a new Williamson gas-fired steam boiler GSA-150 with 210 degF spill switch Weil-Mclain 510-300-013WT.

This cut off temperature seems to be borderline in my case since when I close the door in boiler room the switch trips in few hours. With open door it does not trip.

I had chimney checked- it's OK. My question is, is it worth changing the spill switch to a higher cut off temperature (which would be 240 oF from same product line)?

My concern is 240 oF is above water boiling poin t- will it ever reach it in case of chimney blockage? On 2018-01-30 by Lazar

by (mod) -

Lazar

Watch out: What you describe may be more dangerous than is immediately apparent.

If your gas burner is shutting off with your Boiler Room closed, it's quite possible that the system lacks adequate combustion air. That in turn risks potentially fatal carbon monoxide spillage in the building.

So there may not be a chimney problem but there may be a problem that the boiler room is not providing enough combustion air.

If my guess is correct changing the spill switch would be a dangerous mistake. The correct action would be to provide adequate combustion air.

by Lazar


Thank you for quick reply . The boiler shuts down by spill switch (when I press reset button it turns back on).

If the issue was lack of combustion air, would it raise temperature in the draft hood? Also, there is a supplemental horizontal pipe into outside (besides a pipe into chimney).

Reply by (mod) -

with the apology that for a system about which I have almost no information I can only guess at the most common or likely problem causes, I agree that there could be problems other than the lack of combustion air, including improper adjustment at the burner.

In any event I would be very reluctant to change a spill switch away from the manufacturer's specifications.

Watch out: And my opinion that would be unsafe. It sounds like it's time to get a trained service tech on site

What's wrong with a spill switch that has to be reset after each heat-on cycle?

My flue gas spill switch needs to be reset after each cycle. What's the remedy? On 2017-11-07 by Steve

Answer by (mod) -

Steve

You don't give the brand and model flue gas spill switch: some of these devices are deliberately designed to require a manual re-set, for life safety issues are involved.

The remedy is to

1. diagnose the problem: is there a flue gas spill that's tripping the switch?

2. Act on the diagnosis: if an expert monitoring the system at start-up, operating at full temperature, and at shut down finds on flue gas spillage then she'll probably recommend replacing the switch.

Watch out: you don't want to force the switch on as that could cause a fatal carbon monoxide spillage in the building.

On 2016-12-19 by Anonymous

show image of on and off swith for dunkirk boiler

Moderator Reply

The Dunkirk Boiler, as well as most heating equipment, will sport no special manufacturer, model, brand-specific "on-off" switch. Rather the on-off switch will be a standard electrical on-off switch mounted in two or more locations: at the boiler or even on it, and a second safety off-switch mounted outside of the boiler room typically near its entrance.

See ELECTRICAL POWER SWITCH FOR HEAT


Reader comments:

(Oct 31, 2011) bill the plumber said: great,got me started

(Feb 10, 2012) VERY GOOD INFO REGARDING SAFETY said: You would be surprised the number of homeowners who try to replace this without consulting and or using proffessional. When i sell one i suggest that they do.
Miguel / sales hvac

Question:

(Aug 14, 2012) paul burns

Had my CO2 levels checked in my gas boiler. My flue CO2 level was 2,266 ppm, and zero ppm ambient

Question: I checked and didn't find a carbon monoxide hazard

12/7/2014 Marge

I have checked for carbon monoxide and there doesn't seem to be any according to meter. I smell an unusual smell especially during heating season and very cold weather.

We have some symptoms of possible gases and also have heard of alderhydes that don't seem to have a smell, they are just there and can make you sick.

Do I call a chimney expert or a furnace man. Furnace seems to be working well, but will furnace guy help us with flue and draft problems. What do I ask for?

Reply:

Watch out:  as we warn in more detail at GAS DETECTOR WARNINGS you can have no confidence that just because your gas detector did not detect carbon monoxide that that dangerous gas was not previously present nor can you have confidence that it is not going to be produced and relased into the building again.

Changes such as in wind velocity, outdoor temperature, snow cover, doors or windows open or shut, fans on or off, can significantly change the way gas burning appliances are operated unless careful provisions were made for adequate combustion air and proper flue gas venting.

IF YOU SUSPECT CARBON MONOXIDE POISONING GO INTO FRESH AIR IMMEDIATELY and get others out of the building, then call your fire department or emergency services for help. Links on this page also direct the reader to carbon dioxide gas information in a separate document.

Once you are convinced that no emergency exists, I recommend asking for help by a senior gas heat service technician.

Question: whom do I ask for help with flue gases given that my check for carbon monoxide didn't find any problem?

(Dec 7, 2014) Marge

I have checked for carbon monoxide and there doesn't seem to be any according to meter. I smell an unusual smell especially during heating season and very cold weather.

We have some symptoms of possible gases and also have heard of alderhydes that don't seem to have a smell, they are just there and can make you sick. Do I call a chimney expert or a furnace man. Furnace seems to be working well, but will furnace guy help us with flue and draft problems. What do I ask for?

Reply:

Watch out: as we warn in more detail at GAS DETECTOR WARNINGS you can have no confidence that just because your gas detector did not detect carbon monoxide that that dangerous gas was not previously present nor can you have confidence that it is not going to be produced and relased into the building again.

Changes such as in wind velocity, outdoor temperature, snow cover, doors or windows open or shut, fans on or off, can significantly change the way gas burning appliances are operated unless careful provisions were made for adequate combustion air and proper flue gas venting.

Watch Out IF YOU SUSPECT CARBON MONOXIDE POISONING GO INTO FRESH AIR IMMEDIATELY and get others out of the building, then call your fire department or emergency services for help. Links on this page also direct the reader to carbon dioxide gas information in a separate document. 

Once you are convinced that no emergency exists, I recommend asking for help by a senior gas heat service technician.

Question: can keeping the heat set to a high temperature cause flue gas spillage?

Editor:

The flue gas sensor on our has fired steam boiler keeps tripping off every few days. We installed a new 6-inch chimney liner and a new GSK-3 180 degree flue gas spill sensor at the draft hood as well as a new thermocouple at the gas burner. The pilot light on this steam boiler is always on.

The building occupant wants to keep the heat set rather high, at nearly 80 degrees F because of current cold weather here in the Northeastern U.S.

Will this high temperature setting (and long boiler-on cycles) make the steam boiler overheat or cause flue gas spillage?

Could the flue gas spillage still be caused by the chimney? - Anonymous by request, 26 January 2015

Reply:

Watch out: No user control setting should be tripping off a flue gas spill sensor.

In fact longer boiler-on cycles should improve the draft at the chimney as the flue becomes heated.

It sounds to me as if there is a potentially dangerous, even fatal hazard in the building.

The problem could be in the heater or in the flue or in site conditions that are causing a downdraft.

I'd have the chimney inspected by a certified chimney sweep. Check that the flue size and height are properly matched to the steam boilers input BTUh rating as well as checking that the chimney is not blocked, has a proper cap, is routed properly, has no openings, leaks, nor improper flue sharing etc.

I'd be sure that my heating service company had made a careful inspection of the system's draft, combustion air supply etc.

Meanwhile, immediately, be certain that carbon monoxide detectors and smoke detectors are properly installed, located, and working in the building.

Reader Question: spill switch tripped and we have no hot water

(Nov 14, 2012) B said:
I have recently had two GSK-3 Thermal Safety Devices attached to my Rheem Guardian Fury hot water heater. I have not had hot water since the installation. The HVAC company is unable to get to my home for some time.

They are not from my gas provider. How do the devices work? The little tab is able to be pushed in. It sounds as if that should not occur. Any info is appreciated. I have found your other info very helpful. Thanks

This question was originally posted at COMBUSTION AIR REQUIREMENTS

Reply:

B:

The flue gas spillage switch you cite includes a manually-resettable feature that is probably the "little tab" that you describe. When the switch has cooled the button or "tab" is pressed in to re-set the switch.

Watch out: because flue gas spillage can kill building occupants due fatal carbon monoxide gas, if a heating appliance has shut down for any reason during normal operation (as opposed to during testing) the cause of the failure must be investigated and corrected before resetting the safety-switch and turning the heating equipment back on.

Here are more details:

The Field Controls 46086400 GSK3 Gas Spillage Switch is a detector mounted on the draft hood of a gas or oil fired heating appliance such as a boiler or furnace and used to detect flue gas spillage. The switch is wired in series with the burner so that in the event that it detects flue gas spillage it will turn off the burner.

This gas spillage switch is actually a thermal sensor - it is detecting heat, not flue gases. Field Controls notes:

Installation of a spillage SAFETY Switch is recommended for LP and Natural gas fired systems with draft hoods, draft diverter, or gas barometric draft controls.

This device is installed to detect flue gas spillage caused by a blocked flue system and/or inadequate draft. This device MUST be installed by a qualified installer in accordance with the manufacturer's installation instructions. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.

Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.

CAUTION: Disconnect Electrical Power When Wiring Spillage Switch

This thermal switch can be re-set after it has tripped. The reset may be accomplished (on some switches) by pressing down a popped-up "button" component of the swtich. You have to wait 2-3 minutes for the switch to cool down, then re-set it.

Contact the manufacturer of the Field Controls GSK-3 / GSK-4, GSK-250M Flue Gas Spillage Sensing Kit at the address below, or click the link we provide to see the manual for this control.

 

Some Spill Switches on Gas or OIL Fired Equipment Include a Reset Switch or Button

This information is now found at FLUE GAS SPILL SWITCH SOURCES & MANUALS

Flue Gas Spill Detector Switch Brands, Choices & Selection Guides

This information is now found at FLUE GAS SPILL SWITCH SOURCES & MANUALS

Test the Flue Gas Spillage Switch Detector or Die Inadequate Combustion Air

This topic has moved to a separate article at SPILL SWITCH & COMBUSTION AIR TESTS

Where are all the heating system reset buttons? 

If you are looking for the main reset button on heating equipment you'll want to see

This article series answers most questions about central heating system troubleshooting, inspection, diagnosis, and repairs.

We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.

We include product safety recall and other heating system hazards.

Also see GAS PIPING, VALVES, CONTROLS for more details on how to inspect and test LP and natural gas piping, controls, valves, and tanks.

We continue to add to and update this text as new details are provided.

 


Thank you to our readers for their generous comments

Very helpful site! - On 2016-02-28 by Eric

...





ADVERTISEMENT





...

Continue reading at SPILL SWITCH & COMBUSTION AIR TESTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FLUE GAS SPILL SWITCH TRIPPING & RESET at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • NFPA 54: National Fuel Gas Code (2015), addresses heating appliance combstion air ventilation specifications. NFPA 54, ANSI Z223.1 provides minimum safety requirements for the design and installation of fuel gas piping systems in homes and other buildings.
  • NFPA 85: Boiler and Combustion Systems Hazards Code: NFPA 85 contributes to operating safety and prevents explosions and implosions in boilers with greater than 12.5 MMBTUH, pulverized fuel systems, and heat recovery steam generators.
  • NFPA 87: Recommended Practice for Fluid Heaters, This recommended practice provides safety guidance for fluid heaters and related equipment to minimize fire and explosion hazards that can endanger the fluid heater, the building, or personnel
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT