Building Inspection, Diagnosis & Repair Info

How radiant heat works, importance of radiant angle (C) Daniel Friedman Radiant Heat Night Setback Temperatures

How to use (or not use) night time thermostat setback temperatures for radiant slab heating systems.

This article discusses the maximum, minimum, & recommended night set-back temperatures for radiant heated floor systems.

This article series explains radiant heat temperature settings at the boiler, radiant heat temperature settings in the tubing, maximum temperature for radiant-heated floor surfaces energy efficiencies of radiant floor heating, heat loss rates into earth below radiant heated floor slabs, and we provide operating temperature comparisons for types of radiant heating.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Night Time Setback Recommendations for Radiant Heat Slab Systems

Honeywell digital room thermostat (C) Daniel FriedmanBottom line: using a night time temperature setback for a radiant heat floor slab system might save energy costs but achieving significant savings may require a large setback that in turn risks occupant comfort if the radiant heat system takes too-long to return to comfortable temperatures the next morning.

While sources and studies report a 10-15% gas heat cost savings (as an example) for conventional heating systems, most of the independent, expert sources we reviewed were of the opinion that a night setback for radiant heat high mass floor systems is not useful and is not recommended!

Example: For a super-insulated home, the US DOE points out that (for typical hydronic heating systems)

Photo: Honeywell T8700B/C programmable room thermostat that can support heating and/or cooling control. Click the image to see the T8700 B IO manual. More T8700 manuals are in our Honeywell thermostat manuals and wiring page given at the end of this article.

Setback for super-insulated homes should be avoided.

Because the heating loads are so small, the potential savings from operating in setback mode would be minuscule compared to the extra cost of the baseboard needed to recover quickly. - US DOE 2014

We recommend that you experiment with your building and night setback temperatures to find how much you can set back the indoor temperature at night for a given outdoor temperature. Notice how long it takes for your indoor space temperature to return to its comfort zone.

If you want to try for energy savings by using a night setback with an in-slab radiant heat floor system, to avoid an hours-long recovery period in the morning,

start with a small night setback of just 2-3 deg F for a radiant heated concrete floor slab.

This is much less than a recommended 16 deg. setback for more conventional heating systems, e.g. in the U.K.

And a very aggressive temperature setback, say from 66 deg F. down to 50 deg F. in a very cold climate may mean that the building temperature never recovers adequately in the following day.

A second risk for some radiant heat slab systems is that the operator overheats the slab to try to return to comfortable temperature quickly.

In our test cabin in northern Minnesota, when the cabin is unoccupied for weeks or longer we keep the indoor temperature in the high 40s F - just to prevent frost heave damage.

But on return of occupants in this poorly-built radiant heat slab it takes three to five days for the floor temperatures to warm enough for comfortable barefoot or socked-foot walking.

The optimum night temperature setback for radiant heat slab systems varies by building and climate conditions.

If the night time setback temperature drop for a radiant heat slab system is too great, it may take several hours to bring back comfortable indoor temperatures the next morning.

An automatic thermostat that learns the time necessary to return the building to its target daytime temperature can handle this task for you. The result, for a poorly-insulated slab or building will be a relatively-short night setback period and thus a smaller night-time energy cost savings.

A very well insulated slab and building may keep enough neat overnight that even with a thermostat set-back for night time hours the building temperature can drop very little. In this case the worry of wasting energy by causing the heater to work too hard for too long in the morning won't occur.

Radiant Slab Floor Heat Nighttime Temperature Setback Settings Research

Nest thermostat

  • General heating systems setback advice is at

    THERMOSTAT SETBACK ADVICE
  • Arena, Lois B., MEASURE GUIDELINE: CONDENSING BOILERS—OPTIMIZING EFFICIENCY AND RESPONSE TIME DURING SETBACK OPERATION [PDF] (2014) NREL, The National Renewable Energy Laboratory, by Steven Winter Associates, Inc. of the Consortium for Advanced Residential Buildings (CARB),

    Excerpt:

    4.1.2 Who Shouldn’t Use Nighttime Setback

    For any home with a hydronic heating system, if the answer to any of the following questions is “yes,” the project is probably not right for nighttime setback and should be maintained under constant temperature operation.

    1. Does the home have a boiler that cannot modulate its output?

    2. Is the home insulated to levels significantly better than the 2009 IECC?

    3. Is the heat emitter radiant flooring or radiant panels?

    4. Are the walls or floor of the conditioned space constructed with concrete? If yes, is that concrete uninsulated to the interior?

    5. Do the occupants expect/desire a recovery time shorter than 1 hour?
    Koenig, Kenneth. "Gas furnace size requirements for residential heating using thermostat night setback." ASHRAE J.;(United States) 84, no. 2 (1978).

    Abstract:
    The effects of night setback of thermostats and of furnace sizing on both energy savings and temperature recovery times were studied using a digital computer program to simulate in detail a system consisting of a residential structure, its environment, gas-fired hot air heating equipment, and thermostat.

    The results show that the optimum furnace size and level of setback depends on the relative importance placed on energy savings and short recovery.

    It is recommended that the use of night setback be encouraged as a means to reduce energy consumption.

    In applications where the furnace is fixed and greatly oversized, setback should be as high as possible until the morning recovery becomes objectionable.

    Alternatively, setback should be no more than 5/sup 0/C in cases where the homeowner may take undesirable action to eliminate prolonged recovery on very cold days.
  • Meier, Alan, Cecilia Aragon, Therese Peffer, Marco Pritoni. THERMOSTAT INTERFACE AND USABILITY: A SURVEY [PDF] Lawrence Berkeley National Laboratory, Environmental Energy Technologies Division September 2010, (2011).
  • NC SETBACK TEMPERATURE CONTROL [PDF] North Carolina DEQ, retrieved 2023/05/31, original source: deq.nc.gov/environmental-assistance-and-customer-service/ias-energy-efficiency/opportunities/setback-temperature-control/download

    Excerpts: DOE projects an energy cost reduction of 5% - 12% with a 3°F to 10°F setback and a 9% - 18% energy cost reduction with a 10°F to 20°F setback.

    Setbacks temperatures are often dependent on recovery time of the hvac equipment capacity to reestablish the normal occupied building temperature prior to people arriving for work or students for school.

    The worst case scenario is when a sustained extreme temperature excursion below (winter) or above (summer) the setback temperature for a short period of time (several days).

    Under these conditions hvac capacity will determine the transitional time to reach occupied building setpoint and thus probably an earlier start in the morning for ramping to the accepted room temperature.
  • PM Magazine, BEAUTIFUL HEAT SETS BASELINES FOR RESIDENTIAL RADIANT HEAT EFFICIENCY IN CANADA [PDF] (2014) Plumbing & Mechanical Magazine, 2401 W. Big Beaver Rd., Suite 700, Troy, MI 48084 USA Tel: 248-362-3700 - retrieved 2023/05/31, original source: pmmag.com/articles/99852-beautiful-heat-sets-baselines-for-residential-radiant-heat-efficiency-in-canada

    Excerpts:

    Beautiful Heat, Canada’s not-for-profit association dedicated to educating Canadians about the option of residential radiant heat, recently engaged ICF Marbek to complete an Energy and Comfort Study, measuring energy consumption of radiant heat vs. forced-air systems.

    Based on the results from energy simulations of different home types in six regions of Canada, annual energy savings of up to 18% could be realized with radiant heat.

    It is important to note that energy savings as a result of radiant system multi-zoning in residential buildings are a direct function of occupant behaviour; and therefore, the calculated savings will vary significantly for each based on the thermostat setback setting.

    In order to capture the possible range of energy savings, ICF Marbek modeled each house with the following two setback setting scenarios: 

    • Minimum setback temperature: 1° C reduction during the night for “Living” and “Basement” zones and during the day for “Bedrooms” zone.  

    • Aggressive setback temperature: 4° C reduction during the night for “Living” and “Basement” zones and during the day- for “Bedrooms” zone.

    Energy savings for a radiant system multi-zone system in two-story homes in Toronto and Edmonton are expected to be in the range of 11 GJ to 26 GJ, depending on thermostat setting in which the occupant is continuously managing the thermostat setback temperature.

    This corresponds to a range of 10% to 18% of the total baseline energy consumption.

    Multi-zoning setup in two-story homes in Toronto and Edmonton can increase the potential energy savings resulting from the use of radiant heating system, by a range of 1% to 6% of baseline consumption, depending on the thermostat setting in the different zones.

  • Radiant Floor Co. Radiant Floor DESIGN & INSTALLATION MANUAL 11th Ed. (2007) Radiant Floor Company Barton, Vermont Fax: 1-802-525-3940 1- 866-WARM-TOES 1-866-927-6863 1-802-525-1132 www.radiantcompany.com retrieved 2019/09/20 original source: https://www.radiantcompany.com/wp-content/uploads/radiantcompanymanual.pdf
  • RADIANT HEAT MISTAKES - Additional radiant heat and tubing installation design criteria
  • UK Underfloor Heating, SHOULD my UNDERFLOOR HEATING BE LEFT ON ALL DAY [PDF] (2016) U&K Underfloor Heating, retrieved 2023/05/31, original source: https://www.ukunderfloorheating.co.uk/should-my-underfloor-heating-be-left-on-all-day/
  • US DOE, HYDRONIC SYSTEMS: DESIGNING for SETBACK OPERATION [PDF] (2014) U.S. Department of Energy, retrieved 2023/05/31, original source: energy.gov/sites/prod/files/2014/06/f16/ba_case_study_hydronic_setback.pdf
  • Watson, Richard D., ADVANTAGES of RADIANT HEAT [PDF] (1992) - retrieved 2023/05/31, original source https://www.radiantec.com/about-radiant-heating/technical-description/ (this website page was reprinted from Fine Homebuilding)

    Excerpt:
    When applied to the sizing of a radiant system, conventional heat-loss analysis often includes a reduction in design temperature from 70°F to 65°F and a 10% to 25% reduction in building air infiltration, exfiltration, stratification and glass heat loss. The average 65°F radiant comfort temperature with 59°F day/night setback should reduce building heat load by 25% to 35% over convective systems.
  • WBDG, RADIANT FLOOR HEATING, COMMERCIAL [PDF] NIBS, National Institute of Building Science, 1090 Vermont Avenue, NW, Suite 700 , Washington, DC 20005-4950 USA TEl: (202) 289-7800, WBDG, Whole Building Design Guide, - retrieved 2023/05/31, original source: https://www.wbdg.org/FFC/ARMYCOE/TECHNOTE/technote15.pdf

    Excerpt:

    High mass radiant floor heating systems do not typically respond quickly to a change in load due to the thermal mass of the floor. Therefore, night setback control is not feasible for high mass floor radiant heating systems, unless long durations of unoccupied spaces occur such as in a chapel.

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Radiant heat garage floor © D Friedman at InspectApedia.com

Should I adjust the temp of the heated water when it is warmer outside?

Wondering if I should adjust the temp of the heated water when it is warmer outside if not using thermostat with slab sensor.
I ended up pushing temp to 120F when it was -25F here last month to keep house warm as the 110-115F range had the unit running longer.

Now that it is around freezing, wondering if should drop the temp to avoid swinging temps in the house as by time wall mounted thermostat registers the temp there is a lot of thermal mass built up.

Since appears many around here were not told to place a sensor at bottom of slab and are using typical thermostat to control temps we might need a guide to thermal masses, and advice on temp ranges of our heaters based on outside air temps? On 2021-03-24 by Craig

Photo: our friend Steven is showing the layout of radiant heat tubing in the slab of a radiant heated garage floor in Minneapolis., MN.

Reply by (mod) -

@Craig, I don't have an authoritative answer (and am looking for one) but in general, you can push the floor temp up if it's so cold out that your radiant heat isn't keeping up;

The end of the day the determining factor in my experience is how well the slab was insulated under the floor.

by craig

@Craig, the main building being the finned pex, 2 runs per floor joist. cabin had basement inside perimeter of cabin, so cannot reach 3 feet on long sides, 8 feet in rear or 3 feet in front.

I installed where I could access and put the aluminum fins so there was something under it, and it worked, you could certainly feel areas without the run under old cabin, no socks or shoes required like in previous winters.. though clarify..

Thanks.. the slab was well insulated, a union worker poured it, has 2" high density all around perimeter, bottom, into footings, then around outside and 6 feet outwards on a slope around it,,

My main issue is using most of this mass to heat entire building, ran pex under floor in main cabin, 26x16 with about 50% coverage, then 2 runs under the 16' addition, I think mentioned in an earlier comment last fall.

It made it through winter fine bumped up to 120, very comfortable, just noticed wasn't running as often and would swing 2 degrees over after shutdown when was 1 tops before.

So dropped from 120 to 110 to see how that works out, if still bounces over, without cooking or sunlight, will drop to 100, what I think I started out with in beginning.

I know my issues would not be issues if had full slab with 4 zones and a temp sensor in the slab, but as stated I talked to at least 10 others in area who none have this sensor, nor was it mentioned to them by any installer, it isn't that popular around here possibly due to cost of concrete up here.. thanks again if you find out something..

Followup by (mod) - temperature overshoot with radiant heat floor

@Craig, if the temperature overshoot is a problem you might check to see if you could install a thermostat that uses a heat anticipator.

What's the safest and most efficient temperature setting at your room thermostat

Our reader Stan asked: What's the safest temperature for me to use as a night-time setback?

Moderator reply: it depends ...

Safest: I cannot offer an answer Stan - I'm not sure which safety venue is of concern: over-stressing the heating system itself - which of course varies by type of heat source and type of radiant heat distribution - or do you mean safe - not to burn someone's feet?

Safe against hot feet: The latter would not be affected by thermostat setting but is controlled by the radiant heat system controls and mixing valves.

Most efficient: that too depends on what kind of heating system source you are using. And are we confusing "efficiency" versus minimizing heating costs?

Electric heat, in terms of energy use, is often considered the most-efficient in that nearly 100% of the energy put into the heating system comes out as heat into the occupied space.

Economy: using less heat, keeping a building cooler, uses less energy so spends less money on heating; that's not exactly an efficiency measure.

Freeze protection: it's true that in any home there is risk of frozen water pipes if building temperatures fall too low. Just how serious is that risk and what's a safe temperature depends entirely on the specific building, its climate, construction, insulation, air leaks and other factors.

If this is your concern, take a look at our freeze protection advice that begins at WINTERIZE A BUILDING 

So clarify what we're supposed to discuss here: efficient heat transfer? Economy of operation?

General answer: the room thermostat does not directly control the temperature limits on the heating boiler - those are set by an aquastat on the boiler itself.

See details at AQUASTAT HI LO DIFF SETTINGS where you'll see that we never set the aquastat above 200F

If you were asking about the heat level of the radiant heat floor or ceiling itself, those are given in the article above on this page - please take a look.


...

Continue reading at THERMOSTAT SETBACK ADVICE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

RADIANT HEAT TEMPERATURE NIGHT SETBACK at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to RADIANT HEAT

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website



Comments & Questions are Welcome Here

If you posted comments here and no longer see what you wrote, please check for your comment in the Reader Q&A found above on this page.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • The Radiant Panel Association [Website] Radiant Panel Association - Radiant Professionals Alliance 8512 Oswego Road Suite 180 Baldwinsville, New York 13027 Phone (315) 303-4735 Fax (315) 303-5559 http://www.radiantpanelassociation.org/www.radiantpanelassociation.org/i4a/pages/index.cfm?pageid=1 offers design guidelines at http://www.radiantpanelassociation.org/i4a/pages/index.cfm?pageid=115 including these

    Radiant heat slab insulation R-value and coverage details:

    Application#, Minimum R-Value, and Insulation Coverage

    The following insulation alternatives are given for Slab on Grade construction:

    Alternate #1 [(Ti-To)x0.125)=R-value, with coverage from perimeter to below frost line ["Ti-To" means we calculate the necessary R-value as (Ratio of indoor to outdoor temperature) x 0.125]

    Alternate #2 R-value=5, with coverage 4' horizontal or vertical at perimeter

    Alternate #3 R-value=5, with coverage under entire slab and slab edge [this is our preferred design for a cold northern climate]

    The Radiant Panel Association offers education and publications in radiant heat design. See radiantpanelassociation.org

    Here's their page on hydronic floors: http://www.radiantpanelassociation.org/i4a/pages/index.cfm?pageid=99 where you'll see some vague "source temperature required" graphs that give relative but not absolute temperatures.
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates'Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment

    Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRG in the order payment page "Promo/Redemption" space.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT