Oil Burner Inspection FAQs-2
FAQs on how to inspect, diagnose & repair oil burners, set #2.
This article series answers commonly-asked questions about the inspection, troubleshooting & repair of oil burners such as those used on oil-fired heating boilers or furnaces.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These oil burner inspection, troubleshooting & repair questions and answers posted recently at this diagnostic article: OIL BURNER INSPECTION - see the diagnostic procedures outlined there.
Below is our index to questions and answers about how to make a visual inspection of an oil burner for signs of trouble.
...
Tip: see the diagnosis and repair advice at
I have an Oneida royal smoke came out and bad oder fired it back up seems too run fine what should I do if it happens again On 2017-01-04 by carol pfarner
Answer by (mod) - what to do if smoke comes out of the oil burner and it smells
Carol:
Watch out: I'd call for a service technician to inspect and repair the system before you have a puffback explosion(see PUFFBACKS, OIL BURNER) or lose heat.
You may also need the chimney inspected and perhaps cleaned, or of course there can be other causes, even a loose wire or connection.
...
Tip: also see our discussion of burn marks on furnaces & boilers at HEATING BOILER INSPECTION GUIDE
Hi,
Got two NuWay burners NOL 100 and one of the doors is getting very hot, noticed the heat and colour around the sight glass tube on the boiler door. Switched the boiler off and opened up, checked the nozzles, Solinoids, air flow, insulation on the back of the door, diffuser plate.
All seems ok but boiler a little sooty. Could it be back pressure and need a clean?
Any help would be appreciated. On 2016-03-14 by Luke
by (mod) - overheating boiler, burn marks
Watch out:Sounds unsafe to me - I suspect a burner problem or a venting problem and backpressure in the combustion chamber.
I'd be inclined to shut off the system and call for professional cleaning and adjustment of the system asap.
Watch out:BE SURE YOU HAVE WORKING SMOKE & FIRE ALARMS properly located and installed.by Luke
I have the boiler locked off and just running off one. Going to go through it all on summer shut down. Will let you know the out come
Thanks for the comment
...
Tip: see these key oil burner diagnostic articles for an oil burner that won't start, won't keep running, or that hesitates or starts & stops when it shouldn't
Hi there, very nice website with lots of info. I have a CMF100-PO furnace with a Wayne M-SRH1 oil burner.
If the current temp in the house is 60 and I set the T-stat to 70, the furnace will run and then stop and then immediately restart.
It will do this the whole time the furnace is going until the desired temp of 70 is reached. I tried a new T-stat with no luck. Any ideas? On 2016-02-20 by Derek
by (mod) -
Derek
Presuming we are really talking about a forced warm air furnace (not a hot water heating system or "boiler") then I suspect that your plenum is overheating, turning off the unit.Watch the fan limit control on the air handler.
If it is turning to the HI cut off temp then that's the problem. If so look for a dirty air filter or crimped duct work.
I have a hot oil furnace that heats my house and also supplies the house with hot water.
We ran out of fuel and filled the tank back up, we bleed the line and all seemed well. The problem is the hot water portion of the furnace is working, but I'm getting no hot oil heat in my home.
When I reset the furnace it kicks on for a few seconds and then nothing. You can feel heat coming from the furnace just not through the pipes. Is there a possible solution? On 2016-02-19 by Anthony
by (mod) -
If you have hot water from a tankless coil in the boiler then the boiler is working.
You can confirm that by observing the boiler, seeing that it runs when boiler temperature drops (say because you're running hot water), and see that its temperature rises - it's hot.
It's working.
That tells us that a circulator or circulator relay isn't running, a zone valve isn't opening, or the hot water heating pipes may be airbound.
Search InspectApdia for NO HEAT DIAGNOSIS for more detailed help, or see
Replaced nozzele filter and reset electrodes. I cleaned the eye . i
t restarts with the restart button then runs all day with no problem
after that it dosent restart.
no leaks coiuld this be electrical?
On 2016-01-24 by dsantusby (mod) - oil burner runs for a day then quits
DS
Typically the oil burner will not need to run continuously all day - only in the most extremely cold weather might that occur; rather it turns on and off as needed. Possibly after being off for a longer interval at night (lower thermostat settings, for example), the system may cool down more than during the day.That lower temp could, in unusual cases, result in an open electrical connection, but that would not be expected to trip the reset button.
More likely the system is having trouble starting and is going off on reset.
It needs inspection and repair by a trained service tech, looking for an oil leak, air in the lines, improperly set electrodes, a control problem.
...
...
Continue reading at OIL BURNER INSPECTION - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
OIL BURNER INSPECTION & REPAIR FAQs-2 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.