Building heating system inspection procedures:

This article series gives detailed step by step procedures to be used during the inspection of a heating system in order to be thorough, organized, and accurate. We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Inspect Heating Systems - Example of An Approach to the Forensic Inspection of Any Complex System

The heating system inspection methodology described here serves as a guide to the forensic diagnostic inspection of any complex system where the highest probability of detecting important safety or operating defects is important.

We describe organized procedures for inspecting complex systems for defects, without losing the ability to discover unexpected problems as well.

© Copyright Daniel Friedman 2025-1993 all rights reserved -- Tri-State ASHI Home Inspection Education Seminar - Initial Presentation November 6-7, 1993 -- Last update 10/12/2025

How to Relate Heating System Inspection Procedures to Home Inspection Standards of Practice

This presentation follows a procedure for inspecting, using heating system operating sequence as a method to assure that all important system components are considered.

A version of the ASHI Standards of Home Inspection Practice (readers should check most recent Standards version for changes) is mapped into this heating system inspection procedure but does not guide the actual inspection sequence.

The organization of home inspection standards is not intended as a guide to an inspection sequence nor as a guide to heating system inspection reports. Home Inspection Standards requirements during the inspection of a home heating system are identified in italics in the text below.

HEATING INSPECTION PROCEDURE - A Detailed Step by Step Inspection Procedure for Heating Systems & Heating Equipment

Heating System Inspection: Outdoor Observations

Outdoor heating system inspection from a distance

Viewpoint #1:--Distant (from the heating equipment): walking around the house, from the ground, just looking, notice and record:

Type of Heating Equipment Installed

Age of the neighborhood, other inspections done in the area, age of the house, may suggest type and even the brand of equipment which may be in place. Builders of developments often purchased many of the same brand and model for all the houses there.

What Heating Fuel Is or Has Been in Use

ASHI 9.2.A.1 The inspector shall describe the energy source Identify probable fuel source: oil, gas, electric, coal, wood, solar Notice the oil filler and vent, spills, and whether or not there is easy access to the oil tank filler pipe.

Also notice any evidence of old, possibly abandoned oil tanks (abandoned oil lines, protruding pipes, age of property, depressions in the soil), or of changes from one type of fuel to another (coal bins). These have potentially major cost implications (improperly abandoned oil tanks) or safety concerns (changes of fuel, unsafe chimneys).

Venting and possible hazards noted from outside:

[Examples of "distant" implications] ASHI 9.1.A.4 chimneys, flues, and vents Look for, then at the chimney. Is there a chimney? If not is there electric heat, direct-vent equipment, or no heat? Thinking about what chimneys do lets you understand the implications of your observations. These items are examples, not a comprehensive list.

Heating System Chimney & Venting Observations Made From Outdoors

Here are examples of outdoor observations that should be noted: they provide important information about the type, condition, and safety of the heating system in a building.

If there is no chimney cap

Masonry chimneys

Old stone chimneys

Heating System Chimney & Oil or Gas Supply Observations Made From Outdoors

Heating System Inspection: Indoor Observations

Viewpoint #2--Distant view of the heating equipment from the living area.

Heating System Inspection In the living area

These observations and conclusions can be made quickly without needing to ask anyone anything, as soon as you enter the building:

Type of Heat Distribution
ASHI 9.1.A.7 the presence of an installed heat source in each room. ASHI 9.3.D.4 The inspector is not required to observe the uniformity of heat supply to various rooms.

Heating System Observations In the Utility Room

Viewpoint #3--Distant broad view of the heating equipment from the utility room. The equipment is directly in view but not yet closely examined.
ASHI 9.1.A. The Inspector shall observe permanently installed heating systems including: [items are listed later]
ASHI 9.2.A.2 The inspector shall describe heating equipment and distribution type

  1. Identify/confirm type of equipment
  2. Housekeeping, location of combustibles
  3. Air supply
  4. Sooty operation, odors, noises
  5. Evidence of recent maintenance
  6. Service tags vs filth atop the equipment or in the chimney was it really serviced?

Heating Boilers Detailed Inspection Guide

Viewpoint #4--Detailed close scrutiny of the equipment, after a few "sanity checks"
ASHI 9.1.A.1 The inspector shall observe ... heating equipment

Heating Boiler Inspection Before Operation

What are we looking at? Form a working definition that helps clients understand the system too: A system which heats the house. A steel, copper, or cast iron "box" of hot water, connected to a loop of pipe (and radiators or baseboards) which runs around through the living area. The same physical water stays in the boiler and is circulated by a pump so that heat is delivered to the living area. Burning oil makes hot gases which are used to heat the water before being exhausted outside. Pumps move fluids. Safety controls at various points protect against a number of potential hazards.

Heating Boiler Inspection by Sequence of Operation

Training in proper operation sequence of heating system equipment and in the function of its controls is a step towards technical correctness.

If you do not understand how a mechanical system works you cannot reliably expect to observe missing or defective components. T

his discussion is an exercise using sequence of operation to work for completeness. It is not technically exhaustive, it focuses on a specific example: oil-fired hot water, zoned, heating system.

Examine the accessible parts of the system.

Let your eye travel from component to component in the sequence of operation. Apply the inspection logic discussed earlier, at each step. Consider the implications should each component be missing, damaged, inoperative, leaky, noisy, sooty, repaired by an amateur, etc.

Think through the operating sequence

as you examine each component in that order. The following are the steps in one common set-up. This list is lengthy and detailed. The actual visual examination may take only a few minutes.

How a Heating System Works - 39 Steps in the Operation of a Heating System

For a complete and accurate inspection of a heating system, the inspector may think through the step by step description of how a heating boiler works.

In the reference cited just below we name each heating system component and what it does, in the order that heating system components operate during the heating cycle.

Items shown in [brackets] are ones which may not be present on some heating systems.

A complete, detailed, step by step description of how a heating boiler operates can be read

at BOILER OPERATION DETAILS

How to Inspect the Heating System Controls and Switches

While going through the detailed sequence in the operation of the heating boiler, the heating system inspector should watch for and inspect the condition of the heating boiler controls and safety devices (as required by ASHI 9.1.A.3 automatic safety controls). O

ur detailed description of heating system controls, what they do, how to set them, how to inspect them, is

at BOILER CONTROLS & SWITCHES

How to Inspect Heating Systems for Leaks, Rust, Corrosion Damage

The inspector must be particularly alert for evidence of leaks, corrosion, or other signs of damage to the heating system. O

ur detailed description of where to look for leaks on heating boilers and what those leaks or leak signs may mean can be found

at BOILER LEAKS CORROSION STAINS

How to Recognize Heating System Defects by the Implication of Clues

The heating system inspector must be alert for many signs of heating system malfunction or safety defects.

To inspect a heating system effectively, the inspector must understand the implications of what s/he is observing since otherwise an important clue may go unrecognized and a major heating system defect may go unreported.

We discuss the interpretation of heating system observations and clues further a

t Heating Equipment Malfunction & Implications.

For still more details about heating system malfunctions

see BOILER OPERATING PROBLEMS for an extensive list of heating system clues and what they mean for the safety, adequacy, or reliability of the heating system.

Heating Boiler Inspection Final Checkpoints

How to Operate Heating Equipment During an Inspection

After all visual inspection. Avoids running dangerous systems, permits explanation to client without background noise. Permits observations of operation anomalies.

ASHI 9.2.B. The inspector shall operate the system using normal operating controls such as using the thermostat

Heating System Operating Defects

Heating Equipment Malfunction & Implications

Heating System Operating Sequence Inspection Tips

If the furnace or boiler turns on immediately when the thermostat is turned-on or up from the living area what does this mean?

Alternative Heating System Controls

Heating System Component Malfunction Example

A pressure control set to 10 PSI indicates some operating problem with system, addressed by a service person who's trying to "force" steam into the house rather than debugging a problem, probably with piping or steam valves.

Service has been by someone unfamiliar with steam systems.

Absence of any sign that the occupants ever drain and clean the automatic water feeder suggests risk of inoperative key safety device.

Needs attention even if you see absolutely no problems. Modified piping? improperly sloped radiators?

A Guide to Hot Air Heating Furnace Inspections

Heating System Inspection Final Check Thought Process

Readers needing to find and fix un-wanted air leaks, heat losses, or other energy wasters should

see HEAT LOSS DETECTION TOOLS.

...





ADVERTISEMENT





...

Continue reading at HEATING SYSTEM INSPECTION DETAILS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

HEATING INSPECTION PROCEDURE-GENERAL at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • R.E. Prescott Company, a producer of other REPCO™ residential and industrial products as well as a provider of design-build engineering services is at 10 Railroad Avenue, Exeter, NH 03833. Tel: 603-722-04321 or 888-786-7482. Trish O'Keefe from Prescott informed us (10/7/2009) that their company had nothing to do with the failed Repco heating boilers discussed at InspectAPedia.com. She wrote:
    • Our company manufactures & distributes residential water treatment equipment, including our Repco line of conditioners. We have a plumbing & heating supply dept as well. We are mistaken for the Repco Boiler company on a regular basis, most frequently in Oct. and Nov.
    • Any information you could give me on the other Repco company would be appreciated. We've assumed it is no longer in business, and we'd like to know that for sure. Many callers want to know where to get replacement parts and I would be glad to direct them if I knew...plus there's always a chance they might be interested in a Crown Boiler instead
  • Information on Hydronic (hot water) Heating Boilers:
  • Information on Steam Heating Boilers & Steam Radiators
  • Information on warm air furnace heaters
  • Information on Radiant Heating: RADIANT HEAT FLOOR MISTAKES
  • Information on Electric Heat: ELECTRIC HEAT
  • Information on chimneys flues, vents, combustion air 
  • Information on Heat Pumps - HEAT PUMPS
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide #200 for Residential Hydronic Heating Systems, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested