Detailed Step by Step Procedures for Inspecting Heating Systems
How to inspect a heating system for problems, safety hazards, operating snafus:
This article series presents a very detailed methodology for inspecting residential heating systems with focus on heating boilers and furnaces, on assuring
completeness, accuracy, and on maximum heating system defect detection.
The heating system inspection methodology involved is intended to be generalized to
the forensic diagnostic inspection of any complex system in order to have the highest probability of detecting
important safety or operating defects.
This sounds fancier than intended. Our object is to use an organized
procedure for inspecting for defects, without losing the ability to discover unexpected problems as well. The heating system methodology discussed here includes both details specific to heating boilers (the full outline at "Contents")
and more general complex-system inspection methods (listed immediately below).
© Copyright Daniel Friedman 2008-1993 all rights reserved -- Tri-State ASHI Seminar -- Last update 08/03/2010 - first presentation November 6-7, 1993
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
ADVERTISEMENT
Detailed Inspection Procedure for Heating Equipment
PREPARATION FOR HEATING INSPECTION - How to Prepare Properly to Assure a Thorough Heating System Inspection
These are steps in PREPARATION:
a good procedural order when inspecting any complex system involves these steps: Look (inspect, test, operate), Think, Understand/Speculate-wait,
Write, Speak.
Article Contents
Preparation Begins Before the Heating System Inspection
Prior education & experience - prepares for the inspection
by knowledge and attitude. Your inspection of heating equipment begins
at or before the present seminar.
At the office - when order is taken (*)
- Age of house--how old might the equipment be?
- Location (neighborhood)--is it a builder's development with all boilers of a particular problem-brand?
- Price range--is it a higher priced house likely to have more costly equipment/multiple systems?
- Type of house--large "H" ranch (one story) may have two separate furnaces
- Buyer's concerns--comments about heating system volunteered by client?
- House is occupied? winterized system, has it been left on?
- Was work done by seller or amateurs? IE: "the owner converted the basement" [and did heating and electrical work?]
Driving to the inspection
- Rested, healthy, attentive, mind on work?
- If not, recognize that extra effort will be needed to tune
your attention to the task about to begin.
- Do not perform an inspection if you are seriously ill or
distracted. Life-safety issues may be missed.
- Turn off the radio a mile or so before reaching the house.
- Think about the process.
- Tune your mind to the task at hand.
- Quiet time.
- Observe the neighborhood, age of houses, quality of maintenance,
heavy trees (funny winds and flue draft problems or squirrels in chimneys).
CONTROL ATTENTION - How to Focus Attention to Assure a Thorough Heating System Inspection or other Complex System Investigations
How to pay close attention for hours at a time: without the audible
use of Zen mantras or other eyebrow-raising behavior the inspector
must be calm, relaxed, and completely focused on the process of inspection.
Relaxation as an Aid to Attention During Heating System Inspection
On arriving at a building inspection in preparation for inspection of the
heating system or any other building or building system or component here are some
steps that aid in assuring that the inspector's attention will be fully focused
on the job at hand:
- Turn off the car ignition.
- Exhale fully.
- Calm yourself for a moment before getting out of the car,
before stepping into the sea of seller and buyer anxiety and sometimes
the cold acrid wind of realtor fear.
Take Control of the Inspection Process
- The inspector must be in control of the process.
- Do not permit distractions.
Focus must be on the house, then on clients to assure your explanations
are understood.
How to Pay Attention During the Heating System Inspection
- Home inspection is paying attention to everything, simultaneously.
Each observation at every step might reveal a key which will trigger an important discovery later in the inspection.
- The inspector must focus on a sequence of examination of minute details.
- Simultaneously the inspector must remain open to the unexpected
findings or ideas. The unexpected may be suggested by a detail under examination or it may intrude from the inspector's peripheral.
- It is easier to notice the presence of a defect of commission (leaking relief valve) than a defect of omission (no relief valve installed).
"Psychology and nothing," Eliot Hearst, American Scientist, Sept.-Oct. 1991 pp 432-443. Every home inspector can improve his/her inspection technique by reading this article. Recognizing and learning from absence, deletion, and nonoccurrence are surprisingly difficult. Thinking through sequences of construction or of operation of equipment can help find omissions.
Use techniques to stay focused, to avoid mistakes,
How to avoid heating system errors and omissions:
- Balance Inspection Procedure & Randomness:
Practice a balance between an orderly method or procedure
which assures completeness and sufficient random steps in the process to avoid becoming routinized.
When an inspection is done by "routine" or "habit" the inspector sees only what is in the habitual mental "list".
- Do not rely only on written heating system inspection checklists:
Otherwise the inspector will observe only what's on the checklist and may miss glaring defects. Inspect the house and use your checklist to record it easily. Do not fit the house to the checklist.
- Deliberately vary the inspection order and routine:
once an inspectors heating system inspection procedure is well established and familiar s/he should deliberately vary some of its components at every inspection. Change an order, reverse a sequence.
Outdoor Points of Heating System Inspection
Outdoor heating system inspection from a distance
Viewpoint #1:--Distant (from the heating equipment): walking
around the house, from the ground, just looking, notice and record:
Type of Heating Equipment Installed
Age of the neighborhood, other inspections done in the area, age of
the house, may suggest type and even the brand of equipment which
may be in place. Builders of developments often purchased many of
the same brand and model for all the houses there.
What Heating Fuel Is or Has Been in Use
ASHI 9.2.A.1 The inspector shall describe the energy source Identify probable fuel source: oil, gas, electric, coal, wood, solar
Notice the oil filler and vent, spills, and whether or not there is easy access to
the oil tank filler pipe.
Also notice any evidence of old, possibly abandoned oil tanks (abandoned oil lines, protruding pipes, age of property, depressions in the soil), or
of changes from one type of fuel to another (coal bins). These have potentially major cost implications (improperly abandoned oil tanks)
or safety concerns (changes of fuel, unsafe chimneys).
Venting and possible hazards noted from outside:
[Examples of "distant" implications]
ASHI 9.1.A.4 chimneys, flues, and vents Look for, then at the chimney. Is there a chimney?
If not is there electric heat, direct-vent equipment, or no heat?
Thinking about what chimneys do lets you
understand the implications
of your observations. These items are examples, not a comprehensive
list.
If there is no chimney cap
- is flue blocked by debris?
- has wind-blown rain damaged the masonry interior?
- has wind-blown rain run down chimney into flue vent piping and on into the equipment?
- Did it cause rust damage? Fire chamber damage?
Masonry chimneys
- damaged flue liner? Damage by condensation, frost, acid rain, sulphation (especially with gas-burning equipment)
- Loose bricks?
- Unlined single-wythe brick flues (still common in large cities)--if damaged, risk of fire, leaking flue gases, blocked flues. Look further in the attic and assure there's a cleanout or suggest vent connector be pulled to check for blockage.
Old stone chimneys
- often stop at foundation, heaters were added, connected in to very base of chimney - easily blocked by fallen debris.
- Signs of history of water entry (risk unsafe flue: blocked, fire risks - falling debris
- possible damaged heating equipment (more likely for furnaces than boilers)
More information is at CHIMNEY INSPECTION DIAGNOSIS REPAIR.
Potential Heating System Problems Seen from Outdoors
- buried oil storage tanks or abandoned or leaky above ground or underground oil storage tanks
- indoor tanks used outside
- risks of water entering fuel from location of filler
- fuel spills
- leaks
- ease of access to filler pipe
- oil filler pipe left in place when the house converted
to gas? (Potential very serious problem if oil is delivered by mistake.)
More information: see Oil Tanks Home which includes articles on spotting buried and abandoned or leaky oil storage tanks as well as oil tank leak reporting regulations and oil tank testing and abandonment advice.
Heating System Operation notes taken from outside:
- Sooty chimney top or soot stains on roof: system has not
been operating properly (see CHIMNEY INSPECTION DIAGNOSIS REPAIR.)
- Soot washed off: system may have been repaired/replaced
- Soot heavy and fresh or smoky exhaust seen, system currently
needs service or repair
- Watch out for Repco™ boilers which run sooty as they
crash and can cause fatalities; watch for other recalled or unsafe heating equipment. See
Safety Recalls
- BLUE vs YELLOW COMBUSTION FLAMES
- BLUERAY Recall
- CHIMNEYS & Flues - Asbestos Transite
- Goodman HTPV RECALL
- Lennox PULSE FURNACE SAFETY WARNING
- Weil McLain RECALL
[Do not confuse Repco™ heating boilers, which had fire chamber and other failures, with other products (REPCO pumps, REPCO controls, REPCO water conditioners, or water treatment that carry the Repco name.
Those products are distinct from REPCO heating boilers and are produced/distributed by the R.E. Prescott Company. Further, we are unaware of any remaining warranty or replacement support for failed or antiquated Repco heating boilers.]
- Heat seen rising from heating flue in July - the house
may have a tankless coil for domestic hot water. If not, is the primary
control set up properly?
- Is there a separate oil-fired water heater using same flue?
What's running making that exhaust? Reserve questions for later.
...
Continue reading at INDOOR INSPECTION of HEATING SYSTEM or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
Recommended Articles
Suggested citation for this web page
HEATING SYSTEM INSPECTION DETAILS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Share this article:
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
Citations & References
In addition to any citations in the article above, a full list is available on request.
- Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
- National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
- The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
- The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
- Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
- "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
- Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
- Installation Guide #200 for Residential Hydronic Heating Systems, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
- The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
- Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
- In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
CONTINUE READING or RECOMMENDED ARTICLES.