Heating system inspection concepts:

Basic concepts you need to understand in order to inspect and diagnose heating system condition:

This heating system inspection article and other articles at this website explain Heating System Inspection Concepts - how to prepare for and control the heating system inspection process to assure that the inspection is complete and accurate.

Page top photo: an antique but still-in-use gravity type heating system at a New York home that we inspected in the 1980's.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Inspect Heating Systems - Example of An Approach to the Forensic Inspection of Any Complex System

This document presents a detailed methodology for inspecting, diagnosing, & repairing defects on residential heating systems with attention to inspection methods selected to assure completeness, accuracy, and the maximum level of defect detection.

Photograph of  a modern oil-fired heating boiler

The heating system inspection methodology described here serves as a guide to the forensic diagnostic inspection of any complex system where the highest probability of detecting important safety or operating defects is important.

We describe organized procedures for inspecting complex systems for defects, without losing the ability to discover unexpected problems as well.

© Copyright Daniel Friedman 2012 - 2015 all rights reserved - - Tri-State ASHI Home Inspection Education Seminar - Initial Presentation November 6-7, 1993 -- Last update 08/03/2012

How to Relate Heating System Inspection Procedures to Home Inspection Standards of Practice

This presentation follows a procedure for inspecting, using heating system operating sequence as a method to assure that all important system components are considered. A version of the ASHI Standards of Home Inspection Practice (readers should check most recent Standards version for changes) is mapped into this heating system inspection procedure but does not guide the actual inspection sequence.

The organization of home inspection standards is not intended as a guide to an inspection sequence nor as a guide to heating system inspection reports. Home Inspection Standards requirements during the inspection of a home heating system are identified in italics in the text below.

HEATING INSPECTION CONCEPTS - How to Select an Inspection Methodology for Heating System Inspection & Diagnosis

Step 1: Select a Heating System Inspection Road Map to Guide the Inspection Sequence

 a heating boiler cad cell relay switchIn order to be as thorough, accurate, and safe as possible, a heating system inspector should use a well-defined order of discovery which assures that s/he examines all important heating system components.

Several possible heating system inspection "road maps" can be used for this purpose.

Two approaches inspect the heating equipment by physical layout of components, or by inspecting the heating system in the detailed order that it will operate during the heating system operating cycle.

Of these "heating system inspection road maps", the first of these inspection methods is physically convenient, that is: inspect each heating system component where each is located in each building area, and this is the most common approach in use in the field.

But but it is the second option, heating boiler or furnace operating sequence, that best assures that the inspector considers proper system operation and that s/he identifies all of the system components.

Thinking thorough the sequence of steps in operation of a home heating system requires that the inspector understand how heating systems work. An inspector who cannot follow this sequence does not understand heating system operation and is rather likely to miss important system defects.

So how should a heating system be inspected?

For efficiency the inspector may decide to examine each system component as s/he enters the area of the building where that component resides. So all heater components in the basement or crawl space are examined in one pass while the inspector is in that area, and so on.

But in thinking about the completeness and accuracy of the heating system check the inspector should also think through the system's operating sequence, using the components identified in that sequence to assure that s/he has not omitted something important.

Why is this second thought pattern needed?

Because it is always easier to inspect and think about a building component that we see than to think about a component that is simply absent. In other words, if there is no temperature or pressure relief valve to see On a boiler, the inspector may fail to think about whether or not this is a serious safety hazard for the particular installation.

How to Inspect a Heating System using Physical Location of Components

This approach broadens the scope of the heating system inspection and it may aid in heating system defect recognition or problem diagnosis, for example by observing that a heating boiler is located in a small, air-tight room (possible combustion air problems), or that the furnace is quite close to the oil storage tank.

How to Inspect a Heating System Using the Sequence of Heating System Operation

This approach to heating system inspection Identifies most components of heating systems or of other mechanical systems and is most likely to give the most complete list system parts. It helps assure that all critical components are considered. Actual observation of heating system operation is important in enabling the inspector to identify malfunctions. The heating boiler or furnace inspector's field procedure should include this aid.

A detailed example of the steps in the sequence of operation of a heating system along with a detailed list of heating system components is provided below at Sample Inspection Procedure for Heating Equipment.

The Importance of Reporting to the Client the Significance of Heating System Defects

A superficial heating system inspection may simply identify the type of system present and perhaps the presence of obvious visual anomalies such as leaks. B

ut an astute inspector understands more thoroughly the implications for safety or function of the defects that s/he observes and thus is more likely to inspect the heating system more thoroughly and is more likely to report the inspection findings in a meaningful way to the client.

It is essential that a heating system inspector clearly communicate to the client the significance of the inspection results. I

n other words, the client should be given to understand the need for action, or urgent action, the presence of unsafe conditions, or the indications that costly repairs or replacement are likely to be needed immediately or in the coming year or before next heating season.

The Importance of Thinking about the Possible Significance of Home Inspection Observations

Here are two examples of the difference between simply reporting a home inspection observation neutrally and thinking about the significance of a home inspection observation in a way that might lead to discovery of something important about a heating system.

Example Outdoor Inspection Observation: drip lines below roof eaves

Observation:

The heating system inspector, before entering the home, observes outside that there are deep drip lines in the soil below the home's roof eaves. Drip lines indicate that there has been long term poor control of roof runoff.

Implications:

especially if the home is heated by a furnace located in the basement or crawl space, watch out for signs of rusting of the furnace heat exchanger, particularly in steel hot-air furnaces. A rusted and thus leaky furnace heat exchanger is a possibly dangerous condition, risking high Carbon Monoxide CO levels in the building - a condition that can lead to a fatality - someone could die.

Action: look inside for corroborating clues first of water entry and second of rust on the furnace or its components. Test or recommend testing of heat exchanger for leaks and safety.

An Example of Neutral (irresponsible) home inspection reporting of heating system condition:

Outside

we observed roof overflow or drip lines below the house eaves.

Inside,

A BrandX natural-gas fired 90,000 BTUH steel hot air furnace heating system is installed.

The system appears to be 20 years old. In response to turning up the heat we observed that the system operated normally: heat came out of the air supply registers.

(Our inspection excludes heating system disassembly and therefore cannot examine the condition of the furnace interior components. You should have the system inspected by a qualified technician.

An Example of More-responsible home inspection reporting of heating system condition:

Outside

we observed roof overflow or drip lines below the house eaves.

This means that water has been spilling by the house foundation for a long time, that roof gutters and downspouts are needed, and that the home may have been exposed to a history of water entry or leaks which in turn could cause problems indoors.

Inside,

A BrandX natural-gas fired 90,000 BTUH steel hot air furnace heating system is installed.

The system appears to be 20 years old and based on age alone is likely to be at or near the end of its useful life - significant expense will be involved when furnace replacement is needed.

In response to turning up the heat we observed that the system operated normally: heat came out of the air supply registers.

Our inspection excludes heating system disassembly and therefore cannot examine the condition of the furnace interior components.

However, we observed heavy rust on the bottom of the furnace and other evidence of a history of water entry in the basement.

furnace exposed to these conditions is at extra risk of hidden rust damage such which could include a leaky heat exchanger.

If the heat exchanger is leaking this heating system would be unsafe, should not be used, and would almost certainly require immediate replacement - a significant expense.

We recommend that before completing purchase of the home, and certainly before using the system in the coming heating system, you should have the furnace inspected and tested by a qualified technician, and you should specifically ask the technician to make a thorough inspection and test of the furnace heat exchanger for leaks and safety.

For effective examination of any complex structure, the professional uses all of these tools

Addressing the question of completeness of coverage of components, for a thought-guide to inspecting heating equipment we selected Sequence of Operation as a model.

It is the possible significance of a home inspection observation that leads a good inspector to examine the property further for confirmation or refutation of the presence of a possibly serious building defect.

We discuss this concept of thinking carefully about and pursuing possible implications of home inspection observations as a way to assure that an inspection is thorough and as a means to minimize the chances of missing an important condition at a property, in these articles:

Step 2: Select a Heating System Inspection Viewpoint to Maximize Defect Detection

When inspecting heating systems, while a dramatic and obvious visual clue such as severe rust on a furnace may catch our attention (beware of attention capture errors which make you miss something else), we usually start with broad views, examine further with detailed views, and again make final checks with a broad view.

For home inspections in general because many building systems and conditions affect one another (no gutters, wet basement, rusted furnace, dangerous conditions), a broad view is appropriate for most topics, even where a detailed examination is always made.

Step 3: Observe, Record, & Report Actual or Probable Heating System Defects

What sort of defects should you look for when inspecting a heating system?

What do your heating system inspection observations actually mean?

Examples of Small Heating System Clues with Big Heating System Implications

PREPARATION - How to Prepare in Order to Assure a Thorough Heating System Inspection

Here we explain how to prepare for and control the inspection process.

When inspecting any building or building component the inspector should generally proceed in this simple order: Look, Think, Understand/Speculate-wait, Write, Speak.

We've found that if we start talking too soon we often have to change our mind about the importance of what we've seen as further inspection and new clues produce more data.

We've found that if we start talking before we've written down our observations, there is a real risk that our final notes and report may be incomplete and may not coincide perfectly with what we said to the client during the inspection.

Any substantive differences in observations or conclusions between the onsite oral report and the written inspection report are an invitation to misunderstanding or worse.

Before the Heating Inspection

Prior education & experience of the inspector: a good heating system inspector prepares by knowledge (education and experience) and attitude (for whom ins the inspector working and how diligent is the inspector going to be?).

An inspector who schedules many inspections in a given day is unlikely to have the time nor the ability to attend to those details that make for a competent and responsible job.

at the Office - when the inspection order is taken Obtain Advance Information

Driving to the inspection

What to Do When Arriving at a Building Inspection

On arriving at a building inspection in preparation for inspection of the heating system or any other building or building system or component here are some steps that aid in assuring that the inspector's attention will be fully focused on the job at hand:

CONTROL ATTENTION - How to Focus Attention to Assure a Thorough Heating System Inspection

The Heating System or Home Inspector MUST Control the Inspection Process

How to pay close attention for hours at a time: without the audible use of Zen mantras or other eyebrow-raising behavior the inspector must be calm, relaxed, and completely focused on the process of inspection.

How to Pay Attention During the Heating System Inspection

Use techniques to stay focused, to avoid mistakes,

How to avoid heating system errors and omissions:

Heating System Inspection Final Check Thought Process

...





ADVERTISEMENT





...

Continue reading at HEATING INSPECTION PROCEDURE-GENERAL or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

HEATING INSPECTION CONCEPTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide #200 for Residential Hydronic Heating Systems, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested