Building Inspection, Diagnosis & Repair Info

Steam pressure gauge and pressure control switch on a WeilMcLain Model 68 steam boiler (C) Daniel FriedmanSteam Boiler Pressures & Gauges

Steam heating boiler gauges: this article describes the pressure or sometimes combination & temperature gauges found on most steam heating systems. The steam boiler gauge gives helpful pressure readings that tell us if the boiler is operating normally.

We also give a brief history of the Bourdon tube, a key pressure sensing and recording device invented by Eugene Bourdon, in France, and patented in 1852.

The steam boiler pressure readings at a boiler can help diagnose problems abnormally high pressure levels that often mean problems with the steam heat distribution system or its piping. We give normal low-pressure steam heating boiler pressure numbers and we explain what variations from these data signify.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Steam Boiler Pressure Gauge and Normal Pressure Ranges

Steam pressure gauge on a steam boiler

Pressure and Temperature gauge on steam heating boilers: Residential steam heating systems are almost always designed to operate at very low pressures, perhaps around .5 psi - that' s 1/2 of one psi.

You can see these pressures in our page top photo - both on the gauge and on the pressure controller.

You should see similar settings on the pressure gauge (at left in our photograph) and on the steam pressure control switch (the gray box at right in our photo) on your boiler.

The controls in this photo are discussed in detail

at STEAM HEATING SYSTEMS

and in detail STEAM PRESSURE CONTROL

and at STEAM PRESSURE GAUGE - this page

Article Contents

What Are the Normal Hot and Cold Operating Pressures of Residential Steam Heating Boilers?

Steam pressure gauge and pressure control switch on a WeilMcLain Model 68 steam boiler (C) Daniel FriedmanResidential steam heating systems are almost always designed to operate at very low pressures, perhaps around .5 psi - that' s 1/2 of one psi.

[Click to enlarge any image]

Take a look at our photo of a steam boiler pressure gauge shown here. If you enlarge the image you'll see that the steam pressure gauge on this Weil McLain Model 68 steam boiler reads about 0.5 psi - a setting consistent with the pressure set and shown on the scale on the steam pressure control to the right of the gauge.

If your residential steam boiler is operating at higher pressures than about 0.5 psi, that may be an indication that a service technician or owner was having trouble getting heat distributed through the building.

Rather than finding and fixing the problem, someone is trying to "force" the steam around the system.

Take a look at the dial setting on your gauge or

see PRESSURE CONTROL, STEAM BOILERS

An experienced steam heat service technician will look at the operating pressure of your steam heating boiler and if it is not set to a normal level, the technician will look for the reason.

Causes of High Steam Pressure Problems

Examples of problems that can affect the flow of steam heat through the system, leading to attempts to over pressurized the system include

For details about radiator problems see RADIATORS

and see LEAKS at BASEBOARD, CONVECTOR, RADIATOR.

Also see HEATING LOSS DIAGNOSIS-BOILERS.

More about steam boiler gauges is at STEAM PRESSURE GAUGE.

Steam Pressure Gauges on Condensate Receivers

Condensate return sysem on steam heat © D Friedman at InspectApedia.com

At the right side of our photo of a remote building steam condensate receiver and pump system we see a steam pressure gauge that is used by the service technician to monitor pressure in the steam heating system.

This added information can be helpful when a central steam plant is feeding steam to multiple buildings.

In this case the photo shows a condensate receiver and pump in a Poughkeepsie New York building that is across a major street and several thousand feet from a central steam plant.

The steam gauge shown in the photo at left is installed with an isolating valve - that blue handle below the gauge itself.

The handle is in the "open" position - allowing steam pressure to be read as you can see that the handle is parallel to the connecting piping.

Watch out: some technicians leave the isolating valve or handle for remote gauges in the closed position when the gauge is not in use.

This is a "safe" position that protects from pressure, steam, or condensate loss should the gauge become damaged.

See CONDENSATE RETURN PIPES, PUMPS, STEAM for details about steam condensate return systems & controls.

Steam Boiler Sight Glass Gauge: When & How Much Water to Add to the Steam Boiler

Steam boiler sight glass

If your steam boiler has an automatic water feeder you should see the water level always close to the fill-mark and the automatic water makeup valve will normally do this job for you.

When to add water to the steam boiler

Watch out: If your steam boiler has only a manual valve for adding water, until you know the system's rate of water usage,

you should check the water level at least once a week during the heating season.

You'll want to add water whenever the sight glass shows that the water level has dropped to the "add" mark and you should always see some water in the sight glass.

How much water to add to the steam boiler

The sight glass on a steam boiler,

 combined with a mark or gauge usually placed on the sight glass or on the boiler body behind the glass, will show the proper level to which the steam boiler should be re-filled when it's low on water.

See SIGHT GLASS, STEAM BOILER for details of this component.

 

Cause of Abnormally High Pressure in a Residential Steam Boiler?

As we said earlier, the usual operating pressure range for a residential steam boiler will be between 0.2 psi and 0.5 psi.

You should see that setting on your pressure control and also on the steam boiler pressure gauge.

The discussion below describes a reader's steam boiler that appeared to be set to 8 psi - unusually high. Most-often when we see a residential boiler running at higher psi we suspect that there is a steam delivery problem somewhere in the building.

Watch out: it's a bad idea when someone pushes up the steam pressure to try to "solve" lack of adequate heat.

Often a better repair is to find and fix a bad steam vent on one or more steam radiators or to find and fix improper steam pipe routing or condensate return pipe routing.

Why does my steam boiler burner start and stop without showing movement in the steam pressure gauge

Our InspectApedia reader wrote:

@Inspectapedia Com Moderator, [Shown above] is the gauge I was talking about.

This photo shows where the new gauge is added and this is the data tag and other photos I include here show more about my Weil McLain steam boiler.

On my boiler the burner runs for 45 minutes at a call for heat.

The Honeywell 404a never trips. The thermostat reaches 74 degrees and shuts off the boiler.

During this process now and then I do see the boiler stop and then start again.

Since the Honeywell control is not working, The question which control is making those stops and restarts?

Should not I worry that the steam boiler pressure gauge is not give any indication of change when the boiler is on for so long? On 2022-04-11 by Wayne

Answer by Inspectapedia Com Moderator

@Wayne,

The solution to a residential steam boiler pressure gauge that never changes pressure reading is to replace gauge itself.

Explanation:

It's common for the pressure gauge on older boilers to become debris clogged, as rust and sediment and mineral deposits are common in steam heating systems where new water is introduced by a water feeder or manually as some water is "consumed" during normal steam heating system operation - exiting in the form of steam at radiator steam vents.

The pressure sensing orifice that sends pressure into the steam boiler gauge is tiny and easily clogged.

Fooling with the Honeywell PressureTrol will have nothing to do with the root cause if the problem is gauge sensor port clogging.

It's the room thermostat that calls for heat and that turns the boiler on and off, and it's boiler steam pressure entering the bourdon tube of the steam boiler pressure gauge that should move the gauge reading.

Remember too that your residential steam boiler operates across a very low range of pressures, say from about 0.5 psi to 1 psi, so it won't take much debris clogging to cause the steam boiler pressure gauge to stop responding to pressure changes.

You may also need the boiler and piping cleaned and you might need to use steam boiler water conditioning products.

Examples of diagnosing and repairing steam boiler debris clogging are at

STEAM BOILER FLOODING / SURGING REPAIR 

and at

BANGING HEATING PIPES RADIATORS

More details:

The operating pressure range of your boiler is going to be controlled by the pressure control that you described.

Your boiler's pressure would be normally operate (when the boiler is on in response to a call for heat) at or slightly above cut in pressure (0.5 psi) set on the control.

Are you saying that you were sure the pressure gauge wouldn't show any pressure change or is that your observation?

And is it possible that your pressure gauge doesn't show small changes in that operating pressure range?

Keep in mind that it's the room thermostat that calls for heat that turns your steam boiler on and off.

So when the room temperature rises enough to satisfy the thermostat, the boiler will turn off, completely independently of the steam pressure sensed by the Honeywell 404a Pressure Trol controller. - Daniel Friedman

Followup by Wayne

@Inspectapedia Com Moderator, Thank you for your prompt reply. I have a Weil McLain Steam boiler. It runs but I don't see any movement from the glass pressure gauge.

I searched you tube and most of the suggestion is the pigtail being clogged. I cleaned it. Still does not move. I got a new gauge. Still does not move. To me it seams the boiler is only controlled by the thermostat.

The thermostat calls for heat, the boiler starts. Once reaches the desired temperature, the thermostat sends signal to shut it off. In between the burning process is on/off.

My question is: Which control is calling to stop and then start again since the Honeywell 404a is not doing the cut in and cut out.?

Reading this article makes me feel better.

My take (the gauge did not move) is that the steam boilers are operating between 0.2 psi to 0.5 psi.

But knowing this raise another question in my head, and that is: is the Honeywell 404a control installed there for in case there is abnormal conditions? meaning somehow, for some reason when the pressure goes higher?

On the other hand, I am still worried because I don't know for sure my boiler is operating withing those range. I don't know if all these safety controls are working properly in good condition.

I know the low water cut off works, the Honeywell 404a if I push with my finger it will shut off the boiler so the electric circuit is there and will work if the pressure rises.

by Inspectapedia Com Moderator - a further look at the steam boiler pressure control: Honeywell R404A

Clogging can also occur inside the steam boiler itself, including at the opening to the tube feeding boiler pressure into the steam gauge.

Watch out: here is what Weil McClain says:

If you are a homeowner and are experiencing a problem with your Weil-McLain equipment, the first step you must take is to contact your installer or locate an HVAC contractor in your area. Website: https://www.weil-mclain.com/contact-us/

Honeywell 404a Steam Boiler controller - Honeywell PA4044A1033 Pressure Trol HVAC Control at InspectApedia.com

[Editor's note: Above: is a Honeywell PA404A1033 Pressure Trol HVAC Control typically called the Honeywell 404A.

In normal operation, the pressure gauge will not move since the residential low steam boiler operates between 0.2 to 0.5 or about one-half PSI (read on the right-hand vertical scale on this control).

For a typical one or two story residential home, the "low pressure" steam boiler CUT IN pressure is set to 0.5 psi, and the differential (not visible in the photo but present as a "Differential Dial" shown as a thumbwheel inside of this control) is set at 1 psi. ]

@ Wayne ,

It's no surprise and not extremely worrying that the pressure gauge isn't responding or showing you that small pressure increase in your steam boiler when it runs.

The residential steam boiler operates at such low pressure that the most-accurate pressure gauge would be one operating in the 1-5 psi range. Other gauges showing a much higher pressure range, OR gauge whose pressure inlet is rust and debris clogged won't show a thing.

Most important for safety

  • there must be a pressure relief valve installed on the boiler. If the relief valve is leaking water then the boiler pressure may be too high and the system unsafe.
  • the steam boiler water supply must be maintained - check the water level in the sight glass; most boilers use an automatic water feed valve.
It sounds as if your thermostat is turning the boiler on and off.

The pressure control is a safety device, not the main boiler operating control.

Shown above in this discussion is a Honeywell (now Resideo_(Honeywell) A404A1025 Pressuretrol Controller w/ Subtractive: 1 psi to 5 psi Differential Pressure - the manufacturer and vendors describe its function as follows: (excerpt)

The PA404A is a pressure actuated high limit, safety control for steam heating boilers; it breaks an electrical circuit to shut down the burner if steam pressure rises above a safe level.

That's an example control - it may not match yours exactly.

See

RESIDEO (HONEYWELL) P404A,B STEAM HEAT HIGH LIMIT CONTROL MANUAL [PDF]

In the instructions you will see the illustration we give below - that is typical for a residential steam boiler.

Please see details about this control found at our Recommended Article listed above on this page:

PRESSURE CONTROL, STEAM BOILERS

This control is used on a wide range of HVAC systems which may explain why there may be some confusion about its settings. The example illustration below is for a Honeywell (Resideo) PA404B control and discusses a FAN cut-on and off point.

Honeywell 404B Pressure controller operating a fan, not a steam boiler - at InspectApedia.com

Do post photos (one per comment) of your steam boiler gauge and of your steam boiler pressure control, as well as of the steam boiler itself and of its data tag, and we may be able to comment further.

by Wayne Details of the Honeywell R404A Pressure Control on a residential steam boiler

I cleaned the pigtail.

I replaced the original Honeywell 404a gauge with a new gauge. I don't see the gauge move.

Weil McLean steam boiler pressure gauge (C) InspectApedia.com Wayne

My thought was: The Honeywell Cut In safety control is behind this gauge, if the gauge does not register pressure then that control is useless. I have to make sure this branch works as supposed to. I clean the track from the union to the inside of the boiler too but there was still no movement on the gauge.

I thought to add the new gauge to the relieve valve branch where the main pressuretrol is, and run for about 22 minutes this time and I still don't see any movement on neither gauges.



I think I saw the new Resideo video from youtube by Mr. Gordon.

He said this control comes preset from the factory to 8 psi for some reason and after the technician leaves is the owners time to bring down to 0.5 psi .

On 2022-04-13 by Wayne

@Inspectapedia Com Moderator, Thank you. From your replies I think the stops and restarts of the burner might be the thermostat has reached the desired temperature so it stops and when it goes down it calls for heat again.

The only thing is the temperature in the room where the thermal stat is situated changes quite quickly. That will explain the ghost control, the puzzle in my head.

P.S. Another issue is during the day the steam boiler runs and stops. Pipes in the basement and some of the first floor will get hot but the heat does not quite get up to the third floor.

My thermostat has 4 settings. Wake Leave Return and Sleep.

The Wake setting has no problem because there is a lot of time for the temperature to drop and this will make the burner run a long time to get to the desired temperature. The same for Returns.

The problem is the Leave. For example, you set the Leave from 10:00 am and the Return set to 6:00 pm. What happens is the burner will go on and off just to keep warm the basement or the first at maximum. Before for the heat to get to the third floor, the process is already off because the thermostat has already reached the desired temperature.

What are the options here?

On 2022-04-13 by Moderator - residential Weil McLean steam boiler pressure gauge at 8 psi?

@Wayne,

Watch out: I've never seen a residential steam boiler pressure control that came Factory preset 8 PSI. That would be way too high.

Steam Heat service technicians and installers certainly would be expected to know that.

Watch out: A normal setting of the pressure control on a residential steam boiler is around 0.5 psi - on the right-hand scale on this control.

When we see residential steam boiler pressure controls that are set to high pressures, it's often a sign of a desperate move to try to push heat to upper floors rather than find and fix the actual trouble in the steam piping itself or in the steam radiators or steam vents.

Years ago when we encountered this problem in a building the solution was to move the thermostat to the floor that previously wasn't getting enough heat.

Bottom line: the Honeywell 404a PressureTrol shows theCUT-IN pressure to which the control is set NOT the actual pressure inside the boiler.

It is a fundamental mistake - a misunderstanding perhaps - to expect to see the indicator lever on the Honeywell 404a Pressure Trol controller move as your steam boiler heats up and its internal pressure rises.

The little silver T-shaped indicator bar shows what the pressure controller is SET at, NOT what the boiler's internal pressure IS.

Honeywell 404a Steam Boiler controller - Honeywell PA4044A1033 Pressure Trol HVAC Control indicator bar at InspectApedia.com

Watch out: The Honeywell 404A PressureTrol indicator CUT IN is set to .5 KG/CM2 on the left hand scale - or a bit under 8 psi on the right hand scale which is much too high for a typical residential steam boiler operating pressure where it would be usually set to hear the bottom of the scale - around 0.5 psi - pointed-to by the yellow arrow on the right-hand vertical PSI scale in our illustration below.

The manual for this control RESIDEO (HONEYWELL) P404A,B STEAM HEAT HIGH LIMIT CONTROL MANUAL [PDF] has additional illustrations showing the indicator set where it should be for a residential steam boiler, along with wiring and other instructions for each of the applications or uses of this control.

Followup by Wayne

Steam boiler pressure control (C) Inspectapedia.com Wayne

@Inspectapedia Com Moderator, Thank you. Very Appreciate your time, and sharing all this expertise with me.

Moderator comment:

Wayne, about your control choices including the replacement Honeywell Vaporstat controller shown above and below, see details at PRESSURE CONTROL, STEAM BOILERS

Honeywell Vaporstat steam boiler pressure controller at InspectApedia.com

Watch out: the example pressures shown on this Honeywell Vaporstat steam boiler control may be too high for your steam boiler.

 

History & Mechanism of Bourdon Tube Pressure Gauges

On 2019-09-03 by (mod) - possible to open the gauge in order to place a small servo which could then be programmed to move the dial arm?

Klein patent illustrates a bourdon tube and mechanism to operate the steam pressure gauge needle (C) Daniel Friedman at InspectApedia.comHow interesting, Tim. We look forward to seeing your recreation.

Typically a steam pressure gauge is operated by a type of bourdon tube that is wound into a spiral that responds to pressure and thence moves the needle pointer. I suspect you'll want to, in essence, gut the gauge, keeping just the needle and display. Then you can attach your servo to the needle axle.

You could experiment with trying to deform the tube with a servo but I'm not optimistic about that approach.

A representative illustration of the internals of a steam boiler pressure gauge using a bourdon tube is found in this patent by Maximilan Klein and assigned to US Gauge Company, - Maximilian, Klein. "Steam gauge." U.S. Patent 2,186,872, issued January 9, 1940.

You'll see that there is a small mechanism that converts movement of the Bourdon tube (patented in 1852) into a rotating mechanical movement to which you can attach a tiny servo.

The Klein patent from 1940 illustrates the ratchet and arm mechanism attached to the end of the Bourdon tube used to generate a movement in the steam pressure gauge corresponding to changes in steam pressure.

[Click to enlarge any image]

Farley improved on Bourdon's design as explained in his patent dated just a few years later in 1860.

Farley Bourdoun Tube Pressure Gauge patent from 1860 cited and discussed at InspectApedia.com

Ninety years later and of course informed by other inventors from the interim, Thomas A. Green et als improved on Farley's use of the bourdon tube and patented an indicating gage that converted changes in pressure to a vertical scale gauge rather than requiring a circular pressure indicator.

Green US Patent 2,874,573 used a bourdon tube but converted the gage movement to a linear scale - cited & discussed at InspectApedia.com

 

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

OK to modify a vintage steam pressure control for Recreation of the Tower of Terror basement with boilers and a steam pressure gauge.

I am looking to do a recreation of the Tower of Terror basement with boilers and a steam pressure gauge.

I have found vintage steam pressure gauges and I am wondering if it would be possible to open the gauge in order to place a small servo which could then be programmed to move the dial arm. On 2019-09-03 by Tim -

Moderator reply: Bad Idea, Don't Try it

Watch out: In my OPINION it is potentially very dangerous to try an amateur modification or redesign of ANY heating control, risking creating, in the worst case, a BLEVE explosion that can destroy the building and kill people.

 

What is the best price for a steam pressure gauge

What is the best price for this gauge - On 2018-09-21 by Ankita

Reply by (mod) -

Ankita

Steam boiler pressure gauges of the type used in low-pressure residential steam heating systems sell in the range of about

$18. to $35. USD.

But if you are asking at what "best price" WE can supply you with a pressure gauge, the answer is none whatsoever.

We don't sell anything,

InspectAPedia.com is an independent publisher of building, environmental, and forensic inspection, diagnosis, and repair information provided free to the public - we have no business nor financial connection with any manufacturer or service provider discussed at our website. We do not sell products nor services.

What is the usual pressure on a residential steam gauge vs medium pressure vs high pressure?

High and low pressure steam gauges at Pratt -(C) Daniel Friedman at InspectApedia.comSteam pressure low presure medium . high presure psi are what? On 2018-01-12 by Santoshkumar .parmarsteam

Answer by (mod) - Typical steam boiler pressures on residential low pressure systems

For residential low pressure steam systems

< 0.3 psi typical residential operating steam pressure

> 0.5 psi in a residential steam boiler might a steam delivery problem being solved improperly by pushing steam pressure up

1 psi maximum residential operating steam pressure

Low pressure steam boilers are designed to withstand pressures UP TO 15 psi. At pressures above 15 psi the boiler would be unsafe.

High pressure steam boilers operate above 15 psi of steam pressure, and may be considerably higher. Inside a high pressure steam boiler water pressure may be 160 psig or higher.

In the article above on this page see the section titled

What are the normal hot and cold operating pressures of residential steam heating boilers?

See details at STEAM BOILER PRESSURE

For details about and examples of high pressure steam boiler operations see

STEAM BOILERS GENERATORS CONTROLS, PRATT

 

What does negative boiler pressure in a steam boiler mean?

Just turned on the steam boiler last night. This morning the system is not running and the pressure gauge is reading - negative 10. What could be the issue here? On 2016-11-10 by JH

Reply by (mod) - boiler leak, lost water, repair needed

JH your boiler has cooled down AND there may be no water feeder working to add make-up water to the boiler so as it cooled it has formed a partial vacuum.

Watch out: DO NOT try to get this boiler to run before its water system has been repaired. Doing so would be unsafe as lacking water the boiler can be damaged or even destroyed if you keep running its burner.

How do I fix a sight glass clog on my steam boiler?

I skim the water from my steam boiler and I know the sight glass has gotten dirty but the water is not coming out fast. I think there is a clog in the system between the sight glass the the water drain gauge, how can I fix this or figure out where the clog is? On 2014-11-25 by Faith

Answer by (mod) - debris or sediment may clog the boiler sight glass or drain

Faith

Commonly, as sediment settles in containers like boilers, the clog may be right at the drain valve.

Because of hot water and scalding hazards I'd prefer that you hired a trained service tech to clean the drain or if necessary replace the drain valve.

Details are at SIGHT GLASS, STEAM BOILER 

and

SIGHT GLASS REPLACEMENT 

When is a steam condensate return pump needed?

in a residential home with three floors of heating space. when or should you use a condensation circulation pump in system On 2014-04-09 by a.j.

Explanation by (mod) -

AJ

We only need a condensate return pump in a steam system when there are heating locations that collect condensate that cannot return to the boiler by gravity. We never "circulate" condensate, and we don't normally need condensate pumps to return steam heat condensate from upper floors to a steam boiler located below.

 

My steam boiler pressure is zero and my radiators are cold - is that normal?

I have a steam boiler and my gauge reads 0 is this normal for a low pressure system some of my radiators are dead cold - On 2021-01-27 by Anonymous

Answer by danjoefriedman (mod) - No

Anon

Normal residential steam boiler pressures will be very low, between about 0.2 and 0.5 psi.

Why don't some of my steam radiators get hot?

my boiler is on but I do not get all the radiators get hot,they just get warm does not matter how long the boiler goes on.any idea. Please help me anyone >thank you On 2014-02-11 by ALEX

Answer by (mod) -

Alex,

Start with our cold steam radiator repair procedures at

Also, in the ARTICLE INDEX we have several diagnostic articles under the topic of "Radiators" - those ought to help you out; we don't know from just your question if the problem is complicated or something simple like a closed radiator valve or bad steam radiator; another direction of investigation is a problem with condensate return from the radiators. Keep us posted;
Daniel

...

Continue reading at GAUGE REPLACEMENT, BOILER or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

STEAM BOILER GAUGES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to STEAM BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • [1] Power Technology and Engineering (formerly Hydrotechnical Construction), Volume 43, Number 4, 247-250, DOI: 10.1007/s10749-010-0105-4 - Thermal Power Stations, Temperature regime for damaged steam superheater coils, V. A. Bogachev (this is a PDF file - if you can't find contact SpringerLeak)
  • [2] "Deaerator", Wikipedia, web search 12/18/11. Quoting:

    The deaerators in the steam generating systems of most thermal power plants use low pressure steam obtained from an extraction point in their steam turbine system. However, the steam generators in many large industrial facilities such as petroleum refineries may use whatever low-pressure steam is available.
  • [3] Babcock & Wilcox Co. (2005). Steam: Its Generation and Use (41st ed.).
  • [4] Thomas C. Elliott, Kao Chen, Robert Swanekamp (coauthors) (1997). Standard Handbook of Powerplant Engineering (2nd edition ed.). McGraw-Hill Professional. ISBN: 0-07-019435-1.
  • Weil McLain Model 78 Boiler Manual, Boiler for gas, light oil, Gas/Light Oil fired Burners, Installation, Start-up, Parts, Maintenance instructions, Part No. 550-141-705/0600, Weil-McLain Administrative Office, 999 McClintock Drive, Suite 200, Burr Ridge, IL 60527 Tel: 855-248-1777
    Consumer Inquiries: 800-368-2492
    Technical Services: 800-526-6636 Technical Support for Contractors Only.

    If you are a homeowner and are experiencing a problem with your Weil-McLain equipment, the first step you must take is to contact your installer or locate an HVAC contractor in your area. Website: http://www.weil-mclain.com
  • Bell & Gossett Air Separators and other heating system components, Bell & Gossett, 8200 N. Austin Ave., Morton Grove IL 60053, USA - Tel 847 966-3700 Fax 847 965-8379.
  • Thanks to Bottini Fuel service manager Ron Thomas for discussing aquastat functions, low limit controls, oil burner short cycling causes, and boiler maintenance, reliability, and service contracts 4/13/2010. Bottini Fuel is a residential and commercial heating oil distributor and oil heat service company in Wappingers Falls, NY and with offices in other New York location
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT