Metal chimney fire clearance codes & specifications: this article describes the basic fire clearance requirements for four types of manufactured metal chimneys: B-vents, L-vents, Class A chimneys, and 650C Chimneys.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This article series on chimneys, chimney construction, and chimney safety provide detailed suggestions describing how to perform a thorough visual inspection of chimneys for safety and other defects.
In addition to the requirement for safety fire clearance from rooftops and other building components, separate metal chimneys that are too close to one another may cause damage resulting in poor chimney performance or an unsafe chimney.
Carson Dunlop Associates [at REVIEWERS] sketch at left shows that metal chimneys should be at least 16 inches apart to avoid damage.
See CLASS A CHIMNEYS, MetalBestos™
Carson Dunlop's sketch summarizes combustible clearance requirements for the three main types of metal chimneys:
Sketch courtesy Carson Dunlop.
Clearances for Listed Flue Vent Connectors for Gas-Fired Heating Appliances Minimum Distance from Combustible Materials |
||||
---|---|---|---|---|
Equipment | B-Vents | L-Vents | Single-Wall Metal Pipe | Factory-Built Chimneys |
B-Vents: Listed equipment w/ draft hood & equipment listed for use with B-Vents |
as listed | as listed | 6-inches | as listed |
Residential gas boilers/furnaces, gas conversion burner, draft hood |
6-inches | 6-inches | 9-inches | as listed |
L-Vents: Residential appliances listed for use with L-Vents |
not permitted | as listed | 9-inches | as listed |
Incinerators - residential |
not permitted | 9-inches | 18-inches | as listed |
Listed gas fired toilets |
not permitted | as listed | as listed | as listed |
Unlisted residential appliances with draft hood |
not permitted | 6-inches | 9-inches | as listed |
Residential & low-heat equipment other than items above |
not permitted | 9-inches | 18-inches | as listed |
Medium heat equipment |
not permitted | not permitted | 36-inches | as listed |
Watch out: "as listed" where shown in the table above means that the acceptable fire clearance distances for those chimney types must match or comply with the manufacturer's instructions; those clearance spacings are normally found in at least two locations:
We include an example here: the embossed stamping on a Selkirk B-vent for gas appliances that specifies a minimum of 1-inch clearance to combustibles.
Also see the chimney codes listed below.
I am installing a pellet boiler and will need a second metal chimney as I am leaving my oil burner as a backup. I live in Maine. The only place I would like the metal asbestos chimney would run 40” away from my oil tank. Do you know what the code is on this? I am having a heck of a time getting any answers regarding this? - R. B. Windham ME 2/27/2014
Insulated metal chimneys typically require a one-inch clearance from combustibles.
I think the reason you're not finding an answer to your question is that we're mixing up different constraints and safety concerns:
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2019-10-07 by (mod) - What is the original specification for clearances from the outer wall to combustibles for our fireplace and its chimney?
R Conn
Thanks for a really important metal chimney fire clearance safety question.
In the article above on this page we give typical fire clearance distances for the most-common types of metal flues and chimneys.
Watch out: Beyond that I'm way too chicken to bet your life and money and fire risk on a guessed answer. Instead, let's take a look at the specific metal chimney product you have installed; there will be embossed stampings or data tags on the metal flue product that give its brand and model and clearance minimums.
I don't know what Majestic fireplace model you have installed nor what fuel it's burning nor a thing about the surrounding construction; so the required clearance distances could vary.
For example, the MAJESTIC IO Manual for the Ashland Wood Burning Fireplace, 36" model [PDF] Majestic Products A Brand of Hearth & Home Technologies Inc.
Corporate Office
7571 215th Street West
Lakeville, MN 55044
Customer Service:1 (877) 486-9123 retrieved 2019/10/07 original source: https://downloads.hearthnhome.com/installManuals/Ashland%2036_ASH36_Installation%20Manual_4059-909.pdf warns
Comply with all minimum clearances to combustibles as specified. Failure to comply may
cause house fire.
and continues to give clearance distances at 40 spots in the manual .The sketch below is excerpted from that manual.
Below is a similar example showing the data tag on an Ameri-Vent Type B Gas Vent from American Metal Products, manufactured in Mexico and UL Listed.
On 2019-10-06 by R Conn - clearance distances for our Majestic Fireplace
I have a majestic fireplace installed in our home, I believe it was put in during the early to mid 70’s. It has a 3 wall metal chimney, it is not insulated, but air cooled between the 2’nd and 3’rd structures.
I believe the inside is stainless. The outside is galvanized. It is straight up a chimney chase inside the home. There is an insulated attic above the fireplace where the chimney penetrates then up through the roof with another roof mounted chase.
It appears to be in excellent condition. I’m having the home re-insulated, with high density cellulose.
It appears the original installation allows about 1.5” if clearance in a framed pass through the ceiling, in other words the current fiberglass insulation is about 1.5” away, leaving the lower chimney chase able to breath or release heat.
However it also allows cold air into that chamber during the winter, and we can feel the chase is very cold. It is not insulated very well, think fiberglass batts that have gaps.
What is the original specification for clearances from the outer wall to combustibles. is it 1” or 2”. I assume no contact is recommended. Thank you, Rick, Michigan
On 2017-11-23 by (mod) -
Pat,
Indeed this is a common complaint that we hear from readers: smoke and odors from a neighbour's chimney.
There are in most communities building regulations about distances from property lines or from nearby buildings that may help sort out what the neighbour is required to do.
In addition we give distances to adjacent buildings, windows, etc. in the "Other Key Articles" listed above on this page.
On 2017-11-23 by Pat
Our next door neighbor has about a 3 foot high metal chimney that vents their oil burner (they moved it to the garage). It's on their lower (garage) roof, and way below the height of their upper roof ridge line from the main part pf the house.
It's also right next to our bedroom windows. We're concerned about fumes, not to mention it's very noisy.
On 2017-04-13 by (mod) -
Anon:
Fire stops or fire blocking where?
The final legal approval of your fireplace installation is of course your local building official.
On 2017-04-13 by Anonymous
on a house with no occupied area above fireplace unit and only a vaulted are fire stops required for wood burner with pipe rated and supplied with unit 20' approx
(Feb 6, 2013) bill.fletchis@gmail.com said:
Can insulation be put next to the metal chimney in the attic area for a gas furnace
Bill, some metal chimneys require an air space while others are rated for zero clearance. What kind of flue is this?
If it's a B-vent, typically you need to leave a 1" clearance around the vent - take a look at the "listed" clearance for your particular product - you'll see that advice in the table above.
Let me know what you find or email me the B-vent product name, specs, or any details you can and we'll research it together.
...
Continue reading at FIRE CLEARANCES INDOORS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
FIRE CLEARANCES, METAL CHIMNEYS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.