Building Inspection, Diagnosis & Repair Info

L vent and B vent height requirements (C) Carson Dunlop Associates Fire Safety Clearance Requirements between Metal Chimneys & Combustible Materials

Metal chimney fire clearance codes & specifications: this article describes the basic fire clearance requirements for four types of manufactured metal chimneys: B-vents, L-vents, Class A chimneys, and 650C Chimneys.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Fire Safety Clearance Required from Combustibles for Metal Chimneys

Adjacent metal flue heights should vary (C) Carson Dunlop AssociatesThis article series on chimneys, chimney construction, and chimney safety provide detailed suggestions describing how to perform a thorough visual inspection of chimneys for safety and other defects.

Adjacent Metal Chimney Separation Requirements

In addition to the requirement for safety fire clearance from rooftops and other building components, separate metal chimneys that are too close to one another may cause damage resulting in poor chimney performance or an unsafe chimney.

Carson Dunlop Associates' sketch at left shows that metal chimneys should be at least 16 inches apart to avoid damage.

See CLASS A CHIMNEYS, MetalBestos™

Class A, B-Vent, & 650C Metal Chimney Fire Clearance Requirements

Carson Dunlop's sketch summarizes combustible clearance requirements for the three main types of metal chimneys:

Metal flue clearance requirements (C) Carson Dunlop Associates

Sketch courtesy Carson Dunlop.

Table of Clearances for Listed Flue Vent Connectors for Gas-Fired Heating Appliances

Clearances for Listed Flue Vent Connectors for Gas-Fired Heating Appliances
Minimum Distance from Combustible Materials

Equipment B-Vents L-Vents Single-Wall Metal Pipe Factory-Built Chimneys
B-Vents: Listed equipment w/ draft hood & equipment listed for use with B-Vents
as listed as listed 6-inches as listed
Residential gas boilers/furnaces, gas conversion burner, draft hood
6-inches 6-inches 9-inches as listed
L-Vents: Residential appliances listed for use with L-Vents
not permitted as listed 9-inches as listed
Incinerators - residential
not permitted 9-inches 18-inches as listed
Listed gas fired toilets
not permitted as listed as listed as listed
Unlisted residential appliances with draft hood
not permitted 6-inches 9-inches as listed
Residential & low-heat equipment other than items above
not permitted 9-inches 18-inches as listed
Medium heat equipment
not permitted not permitted 36-inches as listed

Notes to the metal chimney fire clearance table above

Watch out: "as listed" where shown in the table above means that the acceptable fire clearance distances for those chimney types must match or comply with the manufacturer's instructions; those clearance spacings are normally found in at least two locations:

  1. The installation instructions for the specific flue vent connector or metal chimney brand and model or product
  2. A stamping or label found right on the metal chimney product itself

We include an example here: the embossed stamping on a Selkirk B-vent for gas appliances that specifies a minimum of 1-inch clearance to combustibles.

Selkirk B-vent embossed notice on the chimmey gives minimum fire clearance distances (C) Daniel Friedman InspectApedia.com

Also see the chimney codes listed below.

Key Articles on Chimney, Flue, & Vent Clearances for Fire Safety & Building Code Compliance

What's the code on distance and clearance for MetalBestos chimneys & vents vs oil storage tanks?

Our reader asked:

I am installing a pellet boiler and will need a second metal chimney as I am leaving my oil burner as a backup. I live in Maine. The only place I would like the metal asbestos chimney would run 40” away from my oil tank. Do you know what the code is on this? I am having a heck of a time getting any answers regarding this? - R. B. Windham ME 2/27/2014

Reply:

Insulated metal chimneys typically require a one-inch clearance from combustibles.

I think the reason you're not finding an answer to your question is that we're mixing up different constraints and safety concerns:

  1. The required separation or clearance distances for flue vent connectors (generally single-wall uninsulated metal "flue pipes" or "stack pipes" that connect the heater to the chimney) - discussed
    at FLUE VENT CONNECTORS, HEATING EQUIPMENT
  2. The required separation of metal or insulated chimneys themselves from various building components or combustibles - discussed

    at FIRE CLEARANCES, METAL CHIMNEYS
    and for height above roofs

    at CHIMNEY HEIGHT & CLEARANCE CODE
  3. The required separation of heating appliances (like an oil burner) from heating oil storage (the oil tank) - discussed

    at ABOVE GROUND OIL STORAGE TANK (AST) INSPECTION

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

What are safe fire clearance distances for our Majestic Fireplace?

I have a majestic fireplace installed in our home, I believe it was put in during the early to mid 70’s. It has a 3 wall metal chimney, it is not insulated, but air cooled between the 2’nd and 3’rd structures.

I believe the inside is stainless. The outside is galvanized. It is straight up a chimney chase inside the home. There is an insulated attic above the fireplace where the chimney penetrates then up through the roof with another roof mounted chase.

It appears to be in excellent condition. I’m having the home re-insulated, with high density cellulose.

It appears the original installation allows about 1.5” if clearance in a framed pass through the ceiling, in other words the current fiberglass insulation is about 1.5” away, leaving the lower chimney chase able to breath or release heat.

However it also allows cold air into that chamber during the winter, and we can feel the chase is very cold. It is not insulated very well, think fiberglass batts that have gaps.

What is the original specification for clearances from the outer wall to combustibles. is it 1” or 2”. I assume no contact is recommended. Thank you, Rick, Michigan On 2019-10-06

Answer by (mod) - specification for clearances from the outer chimney wall to combustibles: minimum 1" is typical for B-vents

R Conn

Thanks for a really important metal chimney fire clearance safety question.

In the article above on this page we give typical fire clearance distances for the most-common types of metal flues and chimneys.

Watch out: Beyond that I'm way too chicken to bet your life and money and fire risk on a guessed answer. Instead, let's take a look at the specific metal chimney product you have installed; there will be embossed stampings or data tags on the metal flue product that give its brand and model and clearance minimums.

I don't know which Majestic fireplace model you have installed nor what fuel it's burning nor a thing about the surrounding construction; so the required clearance distances could vary.

For example, see the MAJESTIC IO Manual for the Ashland Wood Burning Fireplace, 36" model [PDF] Majestic Products A Brand of Hearth & Home Technologies Inc.

Majestic wood burning 36 inch Ashland Fireplace Dimensions and clearance distances - discussed and cited at Inspectapedia.com

Majestic, Corporate Office 7571 215th Street West Lakeville, MN 55044 Customer Service:1 (877) 486-9123 retrieved 2019/10/07 original source: https://downloads.hearthnhome.com/installManuals/Ashland%2036_ASH36_Installation%20Manual_4059-909.pdf

warns

Comply with all minimum clearances to combustibles as specified. Failure to comply may cause house fire.

and continues to give clearance distances at 40 spots in the manual .The sketch below is excerpted from that manual.

Below is a similar example showing the data tag on an Ameri-Vent Type B Gas Vent from American Metal Products, manufactured in Mexico and UL Listed.

Ameri-Vent 6EAL Type B Gas Vent fire clearance distance label (C) Daniel Friedman at InspectApedia.com

 

Our neighbor's chimney may be unsafe and its smoke and smells and noise bother us.

Our next door neighbor has about a 3 foot high metal chimney that vents their oil burner (they moved it to the garage).

It's on their lower (garage) roof, and way below the height of their upper roof ridge line from the main part pf the house.

It's also right next to our bedroom windows. We're concerned about fumes, not to mention it's very noisy. On 2017-11-23 by Pat

by (mod) -

Pat,

Indeed this is a common complaint that we hear from readers: smoke and odors from a neighbour's chimney.

There are in most communities building regulations about distances from property lines or from nearby buildings that may help sort out what the neighbour is required to do.

In addition we give distances to adjacent buildings, windows, etc. in the "Other Key Articles" listed above on this page.

 

Can I put insulation next to the metal chimney for a gas furnace?

Can insulation be put next to the metal chimney in the attic area for a gas furnace (Feb 6, 2013) bill.fletchis@gmail.com

Reply: probably not - usually you need an air gap

Bill, some metal chimneys require an air space while others are rated for zero clearance. What kind of flue is this?

If it's a B-vent, typically you need to leave a 1" clearance around the vent - take a look at the "listed" clearance for your particular product - you'll see that advice in the table above.

Let me know what you find or email me the B-vent product name, specs, or any details you can and we'll research it together.


...

Continue reading at FIRE CLEARANCES INDOORS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Fire Stopping & Fire Clearance Articles

Suggested citation for this web page

FIRE CLEARANCES, METAL CHIMNEYS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to CHIMNEYS & FLUES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Refviewers

In addition to any citations in the article above, a full list is available on request.

  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor [Website: /www.house-whisperer.com ] is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-873-8534 or by Email: johncranor@verizon.net
  • Thanks to Luke Barnes for suggesting that we add text regarding the hazards of shared chimney flues. USMA - Sept. 2008.
  • Thanks to Bryce Olson, New London, CT, for technical editing and correction of clearance distances - 03/2009
  • Thanks to reader Vic for technical editing and again, correction of clearance distances - 04/2009
  • NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, (2024) at the NFPA Bookstore, (Older NFPA editions and standards are found at the same bookstore)
  • NFPA #211-3.1 1988 - Specific to chimneys, fireplaces, vents and solid fuel burning appliances.
  • NFPA # 54-7.1 1992 - Specific to venting of equipment with fan-assisted combustion systems.
  • GAMA, VENTING TABLES, CATGORY I CENTRAL FURNACES [PDF] (1990 & 2000) Gas Appliance Manufacturers' Association,, includes also fan-assisted combustion system central furnaces.

    SPECIAL METAL-FAB UPDATE AS OF MARCH 2000 The venting tables within this booklet have now been included in the National Fuel Gas Code (NFPA 54/ANSI Z223.1-1999). That code may also be used to size venting systems for draft hood equipped central furnaces or for fan-assisted combustion system central furnaces.

    This booklet contains new venting tables designed specifically for use with Category I central furnaces.

    These tables are unique, in that, industry wide venting tables now exist for fan-assisted combustion system central furnaces. Venting tables for these types of appliances are not contained in the National Fuel Gas Code (NFPA 54/ANSI Z223.1-1988).

    All requirements contained in this booklet apply to both Category I drafthood equipped central furnaces as well as fan-assisted combustion system central furnaces. At no time should a venting system for a listed Category II, III, or IV central furnace be sized with these tables.

    The National Fuel Gas Code (NFPA 54/ANSI Z223.1-1988) may also be used to size venting systems for drafthood equipped central furnaces.

    However, at this time, the National Fuel Gas Code does not include alternate sizing methods for fan-assisted combustion systems.

    Therefore, until engineering data is developed to allow alternate sizing methods for Category I fanassisted central furnaces, the enclosed venting tables must be used for fan-assisted combustion system central furnaces.

    These tables apply to venting single appliances and common venting multiple appliances in both metal and masonry chimneys.
  • National Fuel Gas Code, an American National Standard, 4th ed. 1988 (newer edition is available) Secretariats, American Gas Association (AGA), 1515 Wilson Blvd., Arlington VA22209, and National Fire Protection Association (NFPA), Batterymarch Park, Quincy MA 02269. ANSI Z223.1-1988 - NFPA 54-1988. WARNING: be sure to check clearances and other safety guidelines in the latest edition of these standards.
  • ICC, Fire Inspector Guide Based on the 2021 International Fire Code [ICC Digital Subscription] International Code Council
  • Uniform Mechanical Code - UMC 1991, Sec 913 (a.) Masonry Chimneys, refers to Chapters 23, 29, and 37 of the Building Code.
  • New York 1984 Uniform Fire Prevention and Building Code, Article 10, Heating, Ventilating, and Air Conditioning Requirements
  • New York 1979 Uniform Fire Prevention & Building Code, The "requirement" for 8" of solid masonry OR for use of a flue liner was listed in the One and Two Family Dwelling Code for New York, in 1979, in Chapter 9, Chimneys and Fireplaces, New York 1979 Building and Fire Prevention Code:
  • "Chimneys and Vents," Mark J. Reinmiller, P.E., ASHI Technical Journal, Vol. 1 No. 2 July 1991 p. 34-38.
  • "Chimney Inspection Procedures & Codes," Donald V. Cohen was to be published in the first volume of the 1994 ASHI Technical Journal by D. Friedman, then editor/publisher of that publication, but the production of the ASHI Technical Journal was cancelled by ASHI President Patrick Porzio.

    Some of the content of Mr. Cohen's original submission has been included in this more complete chimney inspection article:

    CHIMNEY INSPECTION DIAGNOSIS REPAIR
  • Chimney Inspection Checklist, Carson Dunlop, Associates, Toronto, Ontario
  • Chimney & Stack Inspection Guidelines, American Society of Civil Engineers, [Book] 2003 ISBN: 9780784475423

    These guidelines address the inspection of chimneys and stacks. Each guideline assists owners in determining what level of inspection is appropriate to a particular chimney and provides common criteria so that all parties involved have a clear understanding of the scope of the inspection and the end product required.

    Each chimney or stack is a unique structure, subject to both aggressive operating and natural environments, and degradation over time.

    Such degradation may be managed via a prudent inspection program followed by maintenance work on any equipment or structure determined to be in need of attention. Sample inspection report specifications, sample field inspection data forms, and an example of a developed plan of a concrete chimney are included in the guidelines.

    This book provides a valuable guidance tool for chimney and stack inspections and also offers a set of references for these particular inspections.
  • NFPA 211: Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, (2024) at the NFPA Bookstore, (Older NFPA editions and standards are found at the same bookstore)
  • Principles of Home Inspection: Chimneys & Wood Heating, in (Principles of Home Inspection), Carson Dunlop, Associates, Toronto, Ontario
  • NFPA 211 - 3-3 - Termination Height for chimneys
  • NFPA 211 - 3-4 - Clearance from Combustible Material
  • NFPA 54 - 7-1 - Venting of Equipment into chimneys
  • American Gas Association - New Vent Sizing Tables
  • National Chimney Sweep Guild [Website] 1255 SW Prairie Trail Pkwy Ankeny, Iowa 50023 USA, Tel: +1 (317) 837-1500 Email: office@ncsg.org NCSG certifies chimney sweep (cleaning) professionals.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT