InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
WATER PUMPS, TANKS, TESTS, WELLS, REPAIRS

FILTERS, WATER
GREYWATER SYSTEMS

WATER CONTAMINANT LEVELS
WATER FILTERS
WATER HAMMER NOISE DIAGNOSE & CURE
WATER HEATERS
WATER ODORS, CAUSE CURE
WATER PUMP REPAIR GUIDE
WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE REPAIR GUIDE - WELLS
WATER PUMP SHORT CYCLING
WATER PUMPS, TANKS, WELLS - BASICS
WATER PURIFIERS
WATER SOFTENERS & CONDITIONERS
WATER TANK BLADDERS & CAPTIVE AIR
WATER TANK REPAIRS
WATER TANK: USES, TROUBLESHOOTING
WATER TESTS, CONTAMINANTS, TREATMENT
WATER TREATMENT EQUIPMENT CHOICES
WELLS CISTERNS & SPRINGS
WELL WATER PRESSURE DIAGNOSIS

More Information

Well Tank Repairs
Water Pressure Tank / Water Tank Diagnosis & Repair Guide
InspectAPedia®  -      

  • Do I need a new water tank or well tank?
  • Reasons to replace a water tank
  • What is the the function of water pressure tank?
  • How to diagnose & correct water pump short cycling "on-off" and loss of air in water tanks
  • How to adjust the water pump pressure control switch
  • How to add air back to a water pressure tank
  • Well pump & water tank diagnosis & repair procedures
  • Questions & answers about well water tanks: types, diagnosis, installation, repair, & replacement of water pressure tanks

Water tank repair or replacement guide: The water tank troubleshooting article series beginning here describes how to determine if you need to replace the water pressure tank. Synonyms for water pressure tank include: water tank, water storage tank, well tank, pressure tank, pressure control tank, Extrol, WellXTrol, bladder tank, bladderless water tank.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

Water Pressure Tank Diagnosis & Repair Advice

Our complete list of water tank diagnosis & repair articles is at the end of this page.

Short cycling of a water pump which is defined at SHORT CYCLING WATER PUMP means that the water pump or "well pump" turns on and off too rapidly or too frequently when water is being run in the building. If this is the problem with your water pump, SHORT CYCLING CAUSES describes the most common causes of this problem. We also provide a complete SHORT CYCLING DIAGNOSIS TABLE that lists all possible causes of well pump rapid cycling on and off. If you are not sure what "water pump short cycling" means or how it is recognized, read SHORT CYCLING WATER PUMP.

Intermittent water pump cycling which is discussed at Intermittent Water Pump Cycling When No Water is Running means that the water pump comes on for no apparent reason.

Loss of water pressure means that the pressure with which water enters a plumbing fixture has become too slow, or is sometimes too slow or weak in water flow rate, or water flow may stop entirely. See WATER PRESSURE LOSS DIAGNOSIS & REPAIR

Readers of this document should see WATER PUMP TYPES & LIFE EXPECTANCY, and also see WATER TANK LIFE EXPECTANCY and WELL LIFE EXPECTANCY, but before assuming that a water problem is due to the pump or well itself, see Water pump and pressure tank repair diagnosis & cost a specific case which offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost.

© 2010 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

Frequently Asked Questions (FAQs) about well water pressure tank diagnosis & repair

Question: Do I Need a New Water Tank? - should I replace my old water tank?

We just had our pump replaced after 18 years. Total cost with tax was $2400. Project was done on emergency basis on a Friday night and we were really stuck. During his visit the plumber/owner suggested we consider a larger pressure tank than our 20 gallon unit, also recently replaced. The system worked well for many years and I don't see the need to purchase another larger tank. Any thoughts? - Wayne Ouellette

Reply: You may not need a new water pressure tank.

If your water tank is a newer bladder type, even a smaller 20-gallon tank gives the equivalent of a larger old style (non-bladder) tank in the draw-down cycle - the amount of time that you can run the water before the pump has to come on.

As long as your pump is not short cycling (which may shorten pump life), the gain from a larger tank is probably not much. If your tank is an older type with no internal bladder, the reason to go to a newer tank would be reliability and reduced maintenance.

Some Reasons to Consider a New Water Tank

  1. The water tank is perforated, damaged, or leaking - you need a new one
  2. The water pump has constant short cycling problems and the water tank is an older non-bladder type you can reduce the frequency of water tank maintenance (adding air) and eliminate problems with automatic air volume controls that try to add air for you by installing a new bladder type water pressure tank. At WATER TANK TYPES: WATER, OIL, EXPANSION, ALL we explain the different types of water tanks.
  3. Your well has a poor flow rate and you often run out of water. Less costly than drilling a new well is the addition of greater water storage capacity in one or a series of larger water tanks. But first see WATER PRESSURE LOSS DIAGNOSIS & REPAIR, and see WATER PRESSURE REPAIR GUIDE - WELLS.

Watch out: before you go to the trouble and expense of replacing a water pressure tank, make sure that you have correctly diagnosed the problem that you are "curing" - you wouldn't want to replace a water tank only to find that you still have the water pressure or quantity problem because another, perhaps less costly, part was at fault.

Also see WATER TANK REPLACEMENT. The illustration at page top is courtesy of Carson Dunlop, Inc. in Toronto.

Question: I installed a new pump because the old one was short cycling on and off - now the problem is back.

I installed new pump in feb. problem of pump going on and off was corrected. it's may, the problem is back. what's the problem now and who should i call..plumber or well guy? -Karen

Reply: short rapid cycling on and off of the well pump is usually a waterlogged pressure tank, a bad pressure switch, or clogged tube that sends water pressure to the switch. But you may have slow intermittent pump cycling.

Karen: About the well pump cycling on and off:

If you mean the pump turns on and off to often when you are using or running water, see SHORT CYCLING WATER PUMP for diagnosis and repair help.

Assuming that you mean that the pump turns on and off unexpectedly when no one is running water inthe home, there are several possible causes of pump cycling on and off, including a leak in the well piping or building piping that drain off pressure even if you are not running any fixtures, or even a running toilet. If your pump is a submersible unit - in the well - then replacing it could have also replaced a check valve that might have stopped unnecessary pump cycling. But as the problem seems to have stopped and then returned, I'd start by looking for a plumbing leak somewhere.

See our article titled: INTERMITTENT CYCLING WATER PUMPS for detailed diagnosis and repair suggestions. Or start with these simple suggestions:

Turn off water into the house at your pressure tank and

  • watch the pressure tank gauge. If pressure drops we'd suspect a problem in well piping or in a check valve;

    If pressure does not drop and if the well pump stays off, I'd suspect a leak in house piping or a running toilet.

    IF on the other hand you meant that the water pump cycles on and off too rapidly when you are running water, see the diagnosis and repair guide in our page left links titled SHORT CYCLING DIAGNOSIS TABLE.

Question: does the color of the water tank matter?

Can you paint the pressure tank a different color than blue?

Reply: no.... and maybe. Don't paint an outdoor tank exposed to hot sun a dark color

Sure you can paint your water pressure tank any color you like.

However if the tank is located outdoors in bright sunlight you might want to stick to lighter colors so that you don't unnecessarily heat up your water (and increase tank pressure).

Question: air keeps spurting out of my faucets

I get a lot of air in my water lines. What can I do to fix that problem? - Dennis

Reply:

How to diagnose air discharge in water supply pipes or at plumbing fixtures:

At AIR DISCHARGE at FAUCETS, FIXTURES we provide a procedure to diagnose and fix this problem.

Question: I just changed my well pump but the breaker keeps blowing

i just changed the water pump and my pressure tank, the psi is reading correctly but the pump is loud and it keeps blowing the braker, what else could be wrong when i have all new put in? - Sonni

Reply: check the pump impeller assembly or replace the whole unit

Sonni:

it sounds as if your well pump is damaged and needs replacement. I would think that you'd made a wiring error, but I'm not sure that would explain a bad pump. If it's very noisy and is tripping the circuit breaker I suspect it's jamming and the motor is drawing high amps and thus causing the circuit breaker to trip.

Before replacing the pump, consider disassembling the impeller assembly portion of the pump (you'll have to turn off power and remove the pump to do this). A broken impeller or debris that got sucked into the impeller could also be jamming up the water pump or making it sound horrible.

Question: my well pump runs all the time our irrigation system is running

I'm told that when my irrigation system comes on my pump should run the whole time I'm watering. My thoughts were that the well will cycle and turn on at 30-psi and turn off at 50-psi letting the pump rest while the bladder distributes the water until guage drops to 30-psi and the pump turns back on the the cycle keeps going.

Please let me know the correct answer, - Mike 6/18/11

Reply:

Mike: with so little information, I can't promise that I can give the correct answer, but certainly I wouldn't give you an incorrect answer on purpose.

The irrigation pump is a separate unit from your well pump, right?

If so it will run all the time you are watering but your well pump will turn on and off as needed.

If your irrigation system and house water run off of the same water supply system, then either the irrigation system fast enough that the pump never reaches cut-off pressure (entirely possible), or your water usage rate is faster than the well inflow rate and a tailpiece in the well is limiting the flow out - leaving the pump running all the time.

Question: I have no water and the switch or pump keep humming

errr i have no water and it sounds like the switch is trying to kick in by making like a hummimg sound and my pressure gauge says 0 so i have replaced the switch and the gauge and still nothing any thoughts in what i can do next to try to get some water? - Jenn 7/11/11

Reply:

Jenn:

Is your pump above ground or in the well. If the humming is coming from an aboveground pump and the pump is not running it is either jammed or is having trouble starting.

Watch out: shut off the power to avoid burning up the pump motor.

If it's a motor start problem, a hard-start capacitor kit might do the trick.

Question: My pressure tank has a pinhole leak - can this be repaired?

My pressure tank has a very small pin hole . Can the pressure tank be welded or sealed in anyway , or will the tank need replaced completely ? - Tom A. 8/11/11

Reply:

Yes, Tom. At your local hardware store you can probably purchase a special screw and washer part (less than $5.00. U.S.) intended to temporarily fix pinholes in water pressure tanks.

Watch out though: often a pinhole on the exterior wall of the tank will be found to be a bigger hole when you start messing with it - because the tank is corroding from the inside (usually) the area of thin walled steel may be bigger than you think. Buy several repair screws of varying size and start with a small one to see if that can screw in tightly enough to stop the leak. If it won't, you'll need to use a larger screw.

Welding is technically possible but not economical, and a repair epoxy might work with good surface cleaning provided you could take the tank out of service long enough and keep it dry during the gluing process, but like the little DUtch boy with a finger in the surface of the dike, that's not the most reliable repair.

Figure a new water tank is in your future.

Question: in the morning our cold water supply smells funny

why is there odor..in morning on cold side..of faucet but does clear up - Timothy Hannon

Reply:

Timothy your question doesn't give a lot to go on, like what the odor smells like. If I were to nevertheless GUESS, I'd guess it's a sulphur or rotten egg smell. If that's what you smell in cold water in the mornings, your water supply may contain sulphur gases.

See ODORS IN WATER for some diagnostic and remedy advice.

Question: our pressure switch stuck on and the gauge hit 90 psi. Now the water smells like sulfur.

Have a well with a pressure tank and a 20/40 switch The switch stuck on, not sure how long, the gauge read about 80-90 when I turned pump off.. I've replaced the faulty switch.

1st problem - the water now has an oily or sulfur odor, seemed clear but if it sits it becomes clouded. Ran about 50 gallons of water and that seemed to help..The well is only used on weekends.. The smell & some of the cloudiness returns after sitting over night or all week..

2nd problem - the pressure tank now has a high pitched noise just before it cycles off..I think the air pressure is at 30 lbs. Can check pressure again this weekend - Wally 7/25/11

Reply:

Wally,

It sounds as if your pump was damaged by overwork. I'm not sure where else in a water system you'd get oil into the water supply (except for a leak into the water well itself).

A lurking sulphur odor may have been disclosed in the actual water supply when the system ran for a long time, perhaps dropping the water table beyond normal, though if the pump was running but water in the building was OFF, that doesn't apply.

Anyway, if there are contaminants in the water pressure tank, running water dilutes what's in the tank but it could take many pump cycles to clean it out.

A better procedure would be to drain the water tank. Turn off the pump, (preserve water if needed for priming the pump), drain the water tank, then repressurize it and flush out the pipes one last time.

Follow-up from Wally:

Thanks, this weekend I did drain the pressure tank & flushed it. After draining, rechecking air pressure & adding more air, it stopped the squeal when the pump stopped .

Flushing the system for a good 10 minutes, changed a sediment filter and flushed it again for 10 minutes. Water tasted & smelled much better even after sitting over night..

Now this Labor Day weekend will check the system again, see what it's like after sitting all week..Thanks again! - Wally 8/29/11

Question: why would the inlet pipe from the well blow off of our pump?

What would cause the inlet piping at the pump (from the well) to blow off. The pvc adapter keeps blowing off the galvanized nipple at the pumps inlet. When I cut off the valve between the pump and the pressure tank, the pump quick cycles (should the valve be after the tank?). - Dennis 10/28/11

Reply:

Dennis, about blowing apart well piping connections,

If your well pump is a 2-line jet pump, it is sending water down into the well, through a pick-up venturi valve, and then back up through the larger of 2 pipes into the pump assembly and onwards to the pressure tank. So if the pump is at abnormal pressure, or more often if the connection was not properly made, that connector can blow off.

When you heat black PVC well piping and shove it over a male fitting such as a pump connector, you should then use one or two stainless steel clamps to hold that connection in place. But sometimes we disassemble and re-use that same connection several times in the course of working on a pump. If so, the end of the well piping may have become too-enlarged or othewise damaged. The fix, IF that is the problem, is to cut off the well-used, enlarged plastic pipe end and connect to a freshly cut end. If that leaves your well pipe too short to reach the pump, cut off a large enough section, say two feet, to permit splicing in a new section of plastic well piping.

Also:

1. check the pressure gauge to be sure your water pressure is 60 psi or below

2. if the water pressure is in normal range, then most likely the connections were improperly made

3. I can imagine that problems with check valves could cause a severe water hammer that could also blow apart well piping connections.

Question: we have surging water pressure at toilets, the hose, etc.

I noticed surging at my toilet, faucets, outdoor hose where I have water pressure, then a drop, then water pressure. It seems the pump is cycling, but it is too far from the house to know. I checked my well today, the pressure tank has 0 psi and some water comes out the pressure valve stem. I noticed my in-line water pressure guage at the manifold has no water in it and is also at 0 psi. how could this be if the pressure switch will keep it at least at 40 psi on the 40-60 rating? And does water coming out of my pressure tank air valve mean it is water logged or is there some other reason I would have water in the bladder... moisture... condensation... I just saw a little bit of water come out each time I put the guage on it trying to measure the pressure... which after several attempts, I came up with 0 psi. - Craig 11/11/11

Reply:

Craig, surging water pressure, on a private well and pump system, is usually caused by a waterlogged water pressure tank - see the article titled SHORT CYCLING WATER PUMP for advice on how to diagnose and fix this problem.

Also, your pressure gauge may be sticking at 0; or your bladder in the tank could be stuck shut;

Yes if water comes squirting out of the pressure tank air valve the tank is waterlogged - and if it's a bladder type tank, the bladder has ruptured.

Question: we had no water, tapped the pressure switch and things started working

This morning we had no water. We went down and checked the water pressure gauge, it was at zero. We tapped the pressure switch, it then moved up to 40 and we then had water. Since then, we have had water, and the pressure on the gauge moves from 60 to 35. Could we have a problem with the pressure switch or the pressure tank? - Nina 2/19/12

Reply:

Yep Nina, you did a great job of discovering most of the problem with the loss of water pressure.

But the root problem may not be the pressur switch contacts themselves. Pressure switches for pump controls mount on a small diameter pipe or tube, often 1/8" or sometimes 1/4" diameter piping. If your water supply includes mud, silt, rust, iron, minerals, or any other crud, it's easy to clog up that pipe, or to clog the still smaller opening in the bottom of the pressure control switch through which water pressure is sensed.

The fix is to try replacing that pipe nipple or replace the switch and nipple at the same time.

Question: is it OK to install a water pressure tank on its side? Does it matter whether a horizontal or vertical water tank is used?

Is it okay for the pressure tank to be on it's side? This is under the house in the crawlspace. Does it matter whether or not a horizontal or vertical tank is used? - Jason

Reply:

Jason, it depends.

A bladderless water tank can often work in any position provided you can find convenient pipe connection points. But a vertical water tank that uses an internal bladder usually has to be installed upright. Or buy a tank designed to be installed horizontally. Othewise the tank and bladder or diaphragam may not work properly and the tank may be damaged.

Question: Our well pump runs continually even after the tank fills up

We Have a 4.5 hourse power well pump that will continually run even after the tank fills up. We had someone come to diagnose the problem and we were told that because we don't have an inground sprinkler system (we use oscillating sprinklers over approximately 3/4 of an acre) that the pump is going out and eventually the pump will burn up. Could this be the cause of our problem? If so, please explain how watering our property with oscillating sprinklers can do this?

Thank you for your help! - Kathy 5/23/12

Reply:

Kathy, at WATER PUMP WONT STOP RUNNING we provide the procedure for diagnosing and repairing a well pump that won't stop running.

The problem could be a bad pressure switch, a pressure switch with the cut-off pressure set higher than the pump can achieve, bad pump, bad pump impeller, a well that has lost its recovery rate, a leak in well piping, a leak in house piping, a clogged sensor on the bottom of the pressure switch (try tapping on the switch to see if the pump stops), or even low voltage that leaves the pump unable to reach the pressure control switch cutoff pressure.

 

Questions & Answers regarding this article

Questions & answers about well water tanks: types, diagnosis, installation, repair, & replacement of water pressure tanks.

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

WATER PRESSURE LOSS DIAGNOSIS & REPAIR
WATER PRESSURE PROBLEM DIAGNOSIS TABLE

WATER TANK: USES, TROUBLESHOOTING
WATER TANK AIR, HOW TO ADD
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK AIR ADD AT AIR VALVE
  WATER TANK AIR ADD BY DRAINING
  WATER TANK AIR HOW MUCH TO ADD
  WATER TANK AIR HOW OFTEN TO ADD
WATER TANK AIR INLET VALVE
WATER TANK AIR LOSS SIGNS
WATER TANK AIR VALVE REPAIRS
WATER TANK AIR VOLUME CONTROLS
WATER TANK BLADDERS & CAPTIVE AIR
  How Water Pressure Tanks Work
  Bladder Type Captive Air vs. Bladderless Water Tanks
  Bladder type Water Tank Failures
  Repair for Burst Tank Bladder
  WATER TANK BLADDER PRESSURE ADJUSTMENT
WATER TANK CAPTIVE AIR vs TRADITIONAL WellMate

WATER TANK CONTROLS & SWITCHES
  AIR VOLUME CONTROLS, WATER TANK
  WATER PUMP PRESSURE CONTROL SWITCH
  WATER PUMP RELAY SWITCH
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK AIR INLET VALVE
  WATER TANK AIR VALVE REPAIRS
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK DRAIN VALVE
  WATER TANK PRESSURE GAUGE
  WATER PRESSURE GAUGE ACCURACY
  WATER TANK RELIEF VALVE
WATER TANK LIFE EXPECTANCY

WATER TANK PRESSURE CALCULATIONS
WATER TANK PRESSURE GAUGE
WATER TANK PRESSURE GAUGE ACCURACY
WATER TANK PRESSURE RELIEF VALVE

WATER TANK REPAIRS
  AIR DISCHARGE at FAUCETS, FIXTURES
  CONTROLS & SWITCHES on WATER TANKS
  INTERMITTENT CYCLING WATER PUMPS
  SHORT CYCLING WATER PUMP
  SHORT CYCLING CAUSES
  SHORT CYCLING CAUSE: WELL PIPE LEAKS
  SHORT CYCLING DIAGNOSIS TABLE
  WATER TANK AIR, HOW TO ADD
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK AIR ADD AT AIR VALVE
  WATER TANK AIR ADD BY DRAINING
  WATER TANK AIR HOW MUCH TO ADD
  WATER TANK AIR HOW OFTEN TO ADD
  WATER TANK AIR INLET VALVE
  WATER TANK AIR LOSS SIGNS
  WATER TANK AIR VALVE REPAIRS
  WATER TANK AIR VOLUME CONTROLS
  WATER TANK BLADDERS & CAPTIVE AIR
    Repair for Burst Tank Bladder
    WATER TANK BLADDER PRESSURE ADJUSTMENT
  WATER TANK DRAIN VALVE

WATER TANK REPLACEMENT
WATER TANK SAFETY
WATER TANK SIZE & VOLUME

WATER TANK TYPES: WATER, OIL, EXPANSION, ALL

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Thanks to reader Wayne Ouellette for discussing water tank replacement needs May 2010
  • Pumptrol® Pressure Switch Adjustment, Square D, Schneider Electric Corporation, 8001 Knightdale Blvd., Knightdale< NC 27545 1-888-778-2733 - Square D Technical Library, web search 07/24/2010 original source: http://ecatalog.squared.com/techlib/docdetail.cfm?oid=09008926800a93be
  • 9013 Pumptrol® Commercial Pressure Switches Type F and 9013 Commercial Pressure Switches Type G, Catalog, SquareD, Schneider Electric Industries SAS, Schneider Electric Industries SAS, web search 02/23/2011, original source: http://ecatalog.squared.com/pubs/Machine Control/
    Pressure-Float-Vacuum Switches/Pressure Switches-Water and Air/9013CT9701.pdf
    Square D is a brand of Schneider Electric.
  • Class 9013 Square D Commercial Pressure Switches: Water Pump Pressure Control Switch Class 9013, Type F, G, Manual, Square D Company, 8001 Highway 64 East, Knightdale, NC 27545-9023, USA, (919) 266-3671, www.squared.com, web search 02/24/2011, original source: stevenengineering.com/tech_support/PDFs/45COM.pdf. Quoting:

    The Type FSG, FYG, FRG - PUMPTROL® Water Pump Pressure Switches are used to control Water Pump Pressure Switches are used to control
    electrically driven water pumps and have the following features:
    • The Type FSG is the standard water pump switch, suitable for all types of pumps: jets, submersible,
      reciprocating, etc.
    • The Type FYG is designed to meet higher horsepower and pressure requirements.
    • The Type FRG is reverse acting: the contacts open on falling pressure.
      All are diaphragm actuated.

    The Type G - PUMPTROL® Commercial/Light Industrial Pressure Switch is used to control electrically driven water pumps and air compressors. It has higher electrical ratings for direct control of motors in pump and compressor applications. The Type G switch is diaphragm actuated and has contacts that open on rising pressure.
  • Access Water Energy, PO Box 2061, Moorabbin, VIC 3189, Australia, Tel: 1300 797 758, email: sales@accesswater.com.au Moorabbin Office: Kingston Trade Centre, 100 Cochranes Rd, Moorabbin, VIC 3189
    Australian supplier of: Greywater systems, Solar power to grid packages, Edwards solar systems, Vulcan compact solar systems, water & solar system pumps & controls, and a wide rage of above ground & under ground water storage tanks: concrete, steel, plastic, modular, and bladder storage tanks.
  • Life Expectancy of Water Pumps - Well Pumps: how long should a water pump last? What affects pump life?
  • Life Expectancy of Wells & Water Tanks how long should a water well and its components last?
  • Smart Tank, Installation Instructions [ copy on file as /water/Smart_Tank_Flexcon.pdf ] - , Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf
  • Typical Shallow Well One Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect_Jet_Pumps_1.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Typical Deep Well Two Line Jet Pump Installation [ copy on file as /water/Jet_Pump_Grove_Elect.pdf ] - , Grove Electric, G&G Electric & Plumbing, 1900 NE 78th St., Suite 101, Vancouver WA 98665 www.grovelectric.com - web search -7/15/2010 original source: http://www.groverelectric.com/howto/38_Typical%20Jet%20Pump%20Installation.pdf
  • Water Fact Sheet #3, Using Low-Yielding Wells [ copy on file as /water/Low_Yield_Wells_Penn_State.pdf ] - , Penn State College of Agricultural Sciences, Cooperative Extension, School of Forest Resources, web search 07/24/2010, original source: http://pubs.cas.psu.edu/FreePubs/pdfs/XH0002.pdf
  • Water pressure tanks - how to diagnose the need for air, how to add air, stop water pump short cycling to avoid damage - water storage water pressure tank safety.
  • Water pump and pressure tank repair diagnosis & cost an specific case offers an example of diagnosis of loss of water pressure, loss of water, and analyzes the actual repair cost
  • Water pressure tank failures & water pump short cycling diagnosis and repair

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.

Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com