Building Inspection, Diagnosis & Repair Info

Photograph of a water pressure tank air volume controlAir Volume Control (AVC) Repair Procedures

How to fix the water tank air volume control device:

This article describes the repair of several problems at air volume controls including water leaks at the AVC, too much air in the water tank, not enough air in the water tank, or an air volume control that is simply not working as it should.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Repair a Leaky US Gauge Type WJ or Type 300L Drainback System or Snifter Valve System Pressure Tank Air Volume Control

Photograph of a water pressure tank air volume control

[Click to enlarge any image]

Recapping, both types of these air volume controls are used only on bladderless water pressure tanks - tanks that do not use an internal bladder. At above left a photo of a US Gauge a Type 6 Air Volume Control showing its operating float (that you cannot normally see as it is inside the water tank). This control is used on shallow wells and jet pumps.

Available at plumbing supplies and via Grainger online who describe the product as "Maintains Balanced Air Volume in Standard Air Over Water Storage Tanks when Using Shallow Well Pump." The installation kit includes 2" Diameter 0-100 Pounds Gauge, 48" Polyethylene, 1/4" Tubing and 1/4" Connectors

On the deep well model WJ 300 or WJ310 AVC from U.S. Gauge, the device excludes the tube connecting from the AVC to the well pump and you won't see the brass fitting on the bottom of the shallow-well AVC model illustrated at CAN I REPLACE e a Round Diaphragm AVC .

Reader Question: how to fix water leaks at a round Brady AV-series air volume control

Brady AV30 air volume control - repairable - InspectApedia.com &  americangranby.com

 

I had a Brady AV-30 air volume control installed when a new water pump was installed 19 months ago. What could be causing the air volume control to leak water from the middle of the thumbnut at the bottom of the control?

The thumb-nut is not loose and is apparently not to be turned with a pliers or wrench. It is leaking enough to nearly fill a bucket in 12 hours.

Brady   air volume control -  InspectApedia.com &  americangranby.com What is the purpose of the thumb nut? Can this leak be repaired? I have called the pump repairman, but he has not yet called back.

The pump is operating normally and is not short cycling, although it may run once every few hours due to this leak even though no other water is being used.7/16/14 anonymous

Reply:

The Wayne - Brady AV-series air volume controls use an internal diaphragm to operate the device.

If the diaphragm has ruptured the air volume control may leak and needs repair or replacement.

If your AV unit is assembled with screws around its round outer perimeter the device is repairable - a new internal diaphragm and spring can be installed. If the round exterior perimeter is simply crimped together, the unit is not repairable and simply is replaced.

Your model, the Wayne Brady AV30 is intended for a 42-gallon water pressure tank and is a repairable model.

There are two ports on these AVCs, a 1/4" threaded tank port and a 7/16"x24 suction port. The thumbscrew which contains a warning "do not use wrench" is an air inlet.

In addition to the air port some Brady air volume controls include a tapped gauge port. Below we give sources for purchasing this air volume control device and repair parts for it.

Brady Air Volume Controls, depending on the model, are field-repairable using a factory-supplied repair kit.

Where to buy Round Wayne Brady Air Volume Controls & Parts

Brady Air Volume Control Repair Kits

AVC Model Repair Kit Part No
AV30 1190
AV42 1191
AV80 1192
AV120 1193

Notes to the table above

Shown below: the Brady AV-45 Zinc Air Volume Control. Excerpting from the product description at Grainger.com (a vendor of these and thousands of other plumbing and HVACR parts):

These well water tank air volume controls (AVCs) are devices that maintain the correct air pressure in well water tanks that do not have an air bladder to control water pressure in the system. The AVCs have floats that mount inside the tank or saucer-shaped diaphragms that install on the outside of the tank to detect the water level inside the tank and keep water pressure at a consistent level.

Brady Air Volume Control No. AV-45 cited & discussed at InspectApedia.com

Regrettably the only Brady AV-45 INSTALLATION INSTRUCTIONS [PDF] we've found to date are in English and French.

 

Thank you to our readers for their generous comments

Great information! Thanks again you were very helpful. - On 2022-03-25 by Ken

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Water coming out of the air volume control

The air volume control Type L on my water tank releses a steady stream of water out of a little hole on the bottom as soon as the pump cuts off.

When the pump cuts back on the stream of water stops until it reaches the psi of your choice. It doesn't matter if it is 40-60 30-50 20-40 it still does the same thing.

I just bought a new air volume control type l this morning and had the same results. I own a bladderless galvanized tank.

I just bought a Myers HCM 150 a month ago because the old one stopped running. I haven't had running water ever sense I replaced it. The pump seems to work fine.

I just can't figure out why that air volume control keeps releasing water out of the hole in the bottom. Thank you. (Mar 8, 2014) Jeremiah

Reply:

You are describing an air volume control used on a bladderless water pressure tank. It sounds as if the internal valve assembly of the valve or the float assembly that projects into the water tank has failed. The repair is to replace the AVC control.

Also It's possible that you've installed the wrong control type; the models for deep wells vs. shallow wells are different.

See AIR VOLUME CONTROLS, WATER TANK for details.

 

Brady AV-45 air volume control device is leaking

Water leaks from the control valve (AV-45) when pump is on. I do have trouble priming the pump. Once primed and pressure reached, the valve does not leak. On 2022-03-23 by Ken

by Inspectapedia Com Moderator -

@Ken,

What's needed depends on a careful inspection of your Brady AV-45 air volume control device so as to see exactly the location of the leak. If the leakage is at the AVC base's threaded fitting you should be able to stop it by removing pressure from the water tank, lowering water in the tank until it's below the AVC mount point, then remove and re-install the device with new teflon tape on the AVC base.

If it's at the AVC pressure outlet tube threaded fitting, try re-making and sealing that fitting.

If the AVC is leaking at its moulded seam around the circumference of the AVC, then the control should be replaced.

I've included a photo of this Brady AV-45 AVC above on this page where we note that some AV models are repairable and others, not.

The AV-45 is not a "repairable" model.

by Ken

The valve only leaks when pump is on. I'll have to replace it. Do I need to adjust the valve? The pump is at my cabin and I drain the system every time we leave (during winter months). I would think some water stays in the bottom of the disc and freezes. probably gave way after a while.

Would this problem be the cause of difficult priming of the pump when I recharge the system?

by Inspectapedia Com Moderator

@Ken,

Adjustment is not going to correct a leak.

And no I don't think that the amount of air in the water pressure tank has an effect on the difficulties in priming the pump.

It would be a bad check valve or foot valve that's leaking and allowing your pump to lose prime.

by Ken - is adjustment necessary when I replace an air volume control?

I know that adjustment won't fix the leak. Just asking if any adjustment for the new valve was necessary. Thanks so much for your help. Most appreciated.

by Inspectapedia Com Moderator - No, the Brady AV-45 valve is not adjustable

@Ken,

Sorry for the misunderstanding.

Some bladderless pressure tank air volume controls are adjustable, such as the US Gauge WJ AVC that we explain at

AIR VOLUME CONTROL ADJUSTMENT

but your Brady AV-45 is not adjustable.

There are three apparent "fittings" on these valves:

  • a threaded nipple that mounts to the water tank
  • a larger threaded nipple that connects a water/air line to the water pump
  • a hex-sided fitting that acts as an air valve (spring and valve parts open at factory set pressure)

Brady describes these AV-nn air volume control valves as automatic:

"Brady automatic air volume control maintains the correct volume of air in an atmospheric pressure tank ...."

The -nn suffix, such as AV-45 (your model) refers to the maximum water pressure tank size that the AVC is designed to handle.

Eg. the AV-42 is described as

Brady Air Volume Control (42 Gallon) # AV42T. Brady automatic air volume control maintains the correct volume of air in a atmospheric pressure tank up to 70 gallons capacity. Zinc die cast body, Buna N diaphragm and seal cap, brass spring and orifice; 100 PSI maximum pressure; 1/4" FNPT (Female pipe thread)tank, suction connection and gauge port; 1.01 lbs.

How does the Brady AV-45 type AVC work? This is a diaphragm type air volume control valve (hence the round disc shape of the device).

When water in the pressure tank is at a level at or above the location of the valve's mounting point on the water tank body, at each pump-on cycle the valve will inject some air into the water pressure tank.

Other AVC models such as the AVC-DWP and AVC-DWR DO include an adjustable pressure relief valve that vents excess air from the pressure tank when the pump is re-filling the tank.

For other readers: in this article series you'll see descriptions of several types of air volume controls or AVC valves:

Diaphragm air volume controls like the Brady AV's we're discussing here that inject air into the water pressure tank depending on the water level in the tank.

Float-type air volume controls that use a hinged float on a metal arm to open or close the AVC to admit air or not as water level drops or rises (suitable especially for larger water pressure tanks up to 220g).

Other Float-type AVCs for deep wells that can inject or release larger volumes of air.

AVC systems that use a snifter valve in the well and air vent at the water tank - discussed in this article series and suitable for deep wells using a submersible pump discussed

at DRAIN BACK & SNIFTER VALVE SYSTEM COMPONENTS

and though we don't see them often, Bottle-AVCs that simply inject some air into the pressure tank at each pump-on cycle (suitable for smaller water pressure tanks up to about 80 gallons)

...

Continue reading at AIR VOLUME CONTROLS, REPLACE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

AIR VOLUME CONTROL REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • [1] U.S. Gauge Special Application Gauges: Type 300L and 310WJ Air Volume Controls, product description, 2002, Ametek® Inc, U.S. Gauge, 820 Pennsylvania Blvd., Feasterville PA 19053, USA, Tel: 215-355-6900 www.ametekusg.com Customer Service: 863-534-1504, web search 03/23/2011, original source: http://www.jlwinstruments.com/PDF_files/D17_MODEL300-310.PDF Sadly this URL now reroutes to a dead end
  • [2] AMTEK, 900 Clymer Avenue 8600 Somerset Drive Sellersville, PA 18960 U.S.A. or Customer Service at AMTEK, Largo, FL 33773 U.S.A.Sales/Technical Support: 215-257-6531, Customer Service: 727-536-7831, Website: www.amtekusg.com, Email US Gauge at usg.sales@ametek.com.
  • [3] flosource.com/ provides links to some US Gauge air volume control products installation and adjustment
  • Rasmussen Well Drilling, Inc., 1793 Hwy 61, Two Harbors MN. Jeremy Rasmussen provides third generation well drilling and plumbing services on the North Shore of Lake Superior. Photos by DJF. Tel 218-834-3387. Email: rasmussenwell@frontier.com
    Quoting: We serve the north Shore – Lake, Cook, St. Louis, Carlton and Pine counties, including Duluth, Grand Marais, Clouqet, Carlton, Finland, Isabella, Silver Bay, Grand Portage, Saginaw, and everywhere in Northeastern Minnesota.
  • [5] Dill Air Controls Products, 1500 Williamsboro St., PO Box 159, Oxford, NC 27565, Tel: (919) 692‐2300, Website: http://dillaircontrols.com
  • Smart Tank, Installation Instructions, Flexcon Industries, 300 Pond St., Randolph MA 02368, www.flexconind.com, Tel: 800-527-0030 - web search 07/24/2010, original source: http://www.flexconind.com/pdf/st_install.pdf [Copy on file as /water/Smart_Tank_Flexcon.pdf ] -
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT