Building Inspection, Diagnosis & Repair Info

Oil filler pipe too far down hill (C) Daniel Friedman Dunedin New ZealandOil Tank Fill & Vent Piping Installation & Inspection

  • POST a QUESTION or COMMENT about oil fill & vent piping location, diameter, length, routing, connections, leaks, & troubleshooting.

Our oil stroage tank fill & vent piping installation & inspection guide starts here with a simple piping checklist.

Inspection for Above Ground Heating Oil Storage Tanks (ASTs) includes a careful check of the oil tank fill and vent piping for size, routing, and other concerns that, if not handled properly, can increase the risk of oil spills or in the worst case, a catastropic oil tank leak from excessive pressure during tank fill-up.

This heating oil piping article series gives advice and example photos for the installation, inspection, & leak troubleshooting of oil tank fill & vent piping for both buried and above ground oil storage tanks.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Heating Oil Fill & Vent Piping installation, Photograph of a in-home oil tank - notice the small diameter vent line?inspection, troubleshooting

Here are some important indicators of tank condition and requirements for oil tank fill and vent pipe size, location, termination, and routing that any home owner or home inspector can examine when an oil storage tank is visible and accessible inside or at a building.

Article Series Contents

[Click to enlarge any image]

Oil Tank Piping Inspection Checklist

  • Are both oil storage tank's fill and vent pipes properly sized? 

    with the right size piping (1 1/2" on older systems, 2" diameter piping by current standards). A too small oil storage tank vent (above right) subjects the tank to extra pressure during fill-up and may contribute to or even cause a leak or oil spill.

    In the photo, a 1 1/2" vent line is installed. Some older oil tank installations use 1 1/4" diameter vent piping, considered undersized if the oil tank is larger than 660 gallons in capacity.

    In most jurisdictions your oil company recommends going to 2" for vent pipe diameter, and most new oil tank installations use a two-inch diameter vent pipe.

    We've seen vent piping as small as one inch on oil tanks. (photo below).

    Why is undersized venting on an oil tank a worry? During fill, fuel is delivered at an average rate of 60 or even 70 gallons per minute.



    Improper or blocked oil tank air exit venting can place excessive stress on tank seams and piping. For older oil tank installations where the tank may suffer from hidden, internal rust and corrosion, the risk of an expensive oil spill from a leaky or burst oil tank is still greater.

    See OIL TANK PRESSURE for a detailed explanation.
Undersized oil tank vent piping(C) Daniel Friedman
  • If the oil tank is indoors, 

    does the tank vent extend to outside?
  • Are the outdoor fill and vent pipes readily accessible 

    to the oil delivery driver. These can be no further than 100 ft. from an accessible road or drive and must be at an accessible height.

Oil tank piping requirements sketch

Below, in our photograph, an oil fill pipe at a property in Dunedin, New Zealand (South Island) doubles back on itself to give the oil delivery driver a fighting chance at filling an oil tank that is uphill from the point of fill. To me [DF] this is a rather ugly installation that seems likely to lead to a spill.

Oil filler pipe too far down hill (C) Daniel Friedman Dunedin New Zealand

  • Is the oil tank vent line properly capped 

    with a screened weather-resistant cap to prevent water entry or clogging by mud or insects?

Oil tank fill and vent piping at an outside wall serving an indoor oil storage tank in a basement (C) Daniel Friedman

  • Is the oil tank piping tight,

    leak-free, and does it drain freely into the tank? Has the piping been equipped with a whistle to signal the delivery person when the tank is full?

Plastic oil tank vent pipe (C) Daniel Friedman Glens Falls NY

  • Are all tank plugs and piping tightly in place?

    Openings in the oil storage tank should be closed with proper fittings.

... Rust damaged oil tank fill & vent piping = leak risk (C) Daniel Friedman Rhinebeck NY

  • Has black or galvanized iron piping been used 

    for oil tank filler and vent lines? Proper and best piping materials for the fill and vent pipe include black iron pipe or galvanized iron pipe;

    Cast iron fittings shall not be used.
  • Has plastic or PVC piping been used

    for the oil tank vent or fill piping?

    Plastic oil storage tank fill or vent piping (above left) may come apart at the seams during a fill up. Some plastic lines can shatter or break in extremely cold weather.

    [Some communities may permit plastic vent piping - Ed.]

    See details on oil fill and vent piping materials at

    at OIL TANK LEAK & ABANDONMENT REGULATIONS
  • Are the oil tank fill & vent pipes damaged or badly rusted 

    so as to risk failure or leakage (photo, above right showing exfoliating rust and swelling of the oil tank piping).

UST oil tank filler and vent pipes at or below ground (C) Daniel Friedman FDR estate Hyde Park NY

...

UST oil tank filler and vent pipes at or below ground (C) Daniel Friedman FDR estate Hyde Park NY

  • Are oil storage tank fill and/or vent pipes close-to or below ground well-protected 

    from water or melting snow? If a cap is loose, can water enter the oil system?

    The photos above show the oil tank fill piping is unprotected and very close to the ground, a risk for water entry from melting, accumulated snow if a cap is loose or its gasket defective.

    See OIL FILL / VENT PIPE RUST-CAUSED LEAKS for details.

Heating oil spilling out of a chimney base cleanout into the home basement after a severe oil tank leak shortly after an oil delivery (C) InspectApedia.com  and  ASHI inspector Lawrence Transue Dec 2017

  • Is there a visible, accessible oil tank vent pipe?

    Is the oil tank vent pipe missing, blocked, or removed?

    At BURIED OIL TANK (UST) GUIDE, we describe a catastrophic indoor oil leak when (apparently) a buried oil tank burst and then leaked a high volume of heating oil underground, under the building foundation, and up through the basement floor slab where it filled the sump pit, chimney cleanout base, and then entered the basement floor (heating oil leak photo above).

    A missing or buried or blocked tank vent may have had a role in this oil tank failure and spill.

No oil tank alarm, please listen (C) Daniel Friedman at InspectApedia.com

Oil tank piping requirements sketch

  • Is the tank vent next to or close to the oil filler pipe 

    so that the delivery person can listen to the vent alarm (some call this the oil tank vent whistle) and determine when the tank is full?

    And in the case of no alarm, for other less attentive oil truck drivers who were over-filling the oil tank, we added a "NO ALARM - PLEASE LISTEN" reminder.

    Why is the driver listening at the oil tank vent pipe?

    There are several reasons:

    The oil delivery driver wants to be sure that oil is flowing into an intact oil tank not into an empty room where the oil tank was removed or where the tank has fallen apart - avoiding an oil spill catastrophe.

    Also

    He wants to know when the oil tank has been filled to a proper level, especially in the event that the oil tank does not have a working vent alarm.

    What is the heating oil delivery driver listening for?


    What will he hear?

    Listening at the tank vent, the oil delivery driver will hear an echo of the filler nozzle being connected to the filler pipe, and he will hear the sound of oil rushing into the hollow oil tank interior. He'll also hear air rushing out of the tank vent as oil entering the tank displaces air.

    He will also hear a "slap" sound if rising oil in the tank hits the bottom of the vent alarm (even if the vent alarm is not working) or a slap when the oil hits the bottom of the tank vent if no vent alarm is working.

    An oil delivery driver explained to me that when he hears that tank-full slap he always steps back quickly from the vent out of an inbred concern for being shot in the ear with heating oil - though that actually never happens.

    Special thanks to Bottini Oil, Poughkeepsie, New York, for these helpful tips from a savvy oil delivery driver (December 2017).

    Watch out: heating oil tanks that are not equipped with a vent alarm are at risk of being over-filled or over-pressurized, damaged, or even burst from an oil delivery.
King Fill oil tank vent alarm - also see Durst & Scully
  • Is there a working vent alarm or tank whistle?

    If not, there is a risk of oil storage tank over-filling and leaks or even tank damage. The blue vent alarm shown here is a King Fill™ oil storage tank vent alarm.

    The vent alarm prevents over filling and is recommended for both underground and above ground tanks. It should be mounted at the top of the tank at the vent pipe opening. (Naturally inspectors cannot see this component on buried tanks.)

    You can't see most of this vent alarm when it's installed as the threaded portion and copper down-tube extend down into the oil tank; the oil tank vent pipe is connected to the tank vent alarm top; as the oil tank is being filled, air pushed out of the tank by incoming oil causes the alarm to make a whistling sound.

    When oil reaches nearly the top of the tank, it stops air from passing out through the brass down-tube and thus stops the whistle while the oil level is an inch or two below the very top of the oil tank.

    Also see Durst and Scully for more oil tank vent alarm devices

    See details

    at OIL TANK GAUGE & VENT ALARM INSTALL / REPLACE

    See OIL TANK SPILL CLEANUP / PREVENTION for additional over-fill prevention and leak or spill detection devices

    Below: when a tank alarm was added (along with a new oil storage tank), we amended the message to the oil delivery driver accordingly.

Oil delivery driver notice: tank alarm installed, please listen (C) Daniel Friedman at InspectApedia.com

  • Is the oil tank gauge installed and tight. 

    Loose or broken oil tank gauges can cause spills during tank fill operations.

    See OIL TANK GAUGE LEAK REPAIR for details.
  • Is there evidence of seepage, leakage, spills 

    around the fill or vent piping or on the ground around the oil tank or filler fitting?

    See OIL TANK FILL / VENT PIPE LEAK REPAIRS for details.
  • Is there a proper vent cap and screen atop the oil tank vent pipe?

    See the illustration below.

Slip on oil tank vent pipe cover & screen - cited & discussed at InspectApedia.com

Approved Oil Tank Piping Materials

Now moved

to OIL TANK FILL & VENT PIPING MATERIALS

Oil Tank Fill & Vent Piping Size / Diameter Requirements

Moved to OIL TANK FILL & VENT PIPING SIZE REQUIREMENTS

Fill and Vent Piping for Duplex Heating Oil Storage Tanks

Now found at OIL TANK PIPING for DUAL OIL TANK INSTALLATIONS

Oil Fill & Vent Pipe Termination: Outdoors, Clearance Distances

Moved to OIL TANK FILL & VENT PIPING OUTDOOR TERMINATION & CLEARANCES

Oil Tank Piping Bends & Elbows

Now at OIL TANK FILL & VENT PIPING BENDS & ELBOWS

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

My Oil Tank Gauge said 1/8 but the delivery only accepted 60 gallons - what's wrong?

My indoor oil tank gauge was at 1/8”, and I ordered 150 gallons of oil. The driver could only put in around 60 gallons, because the vent stopped whistling. The level gauge was now slightly under 1/2 full for my 275 gallon tank.

Could this be a gusher or air vent problem, since both seem to be someway working ?
Any ideas or help would be appreciated. Thanks On 2023-03-17 by Ed

by InspectApedia Editor (mod) - can't fill oil tank - vent alarm or gauge stopped working

@Ed,

Thanks, that's an interesting oil tank gauge troubleshooting problem.

It would help if you'd post a photo of your tank gauge so that I can see the type.

Most oil tank gauges use a float attached to a hinged rod in the oil tank. They're not precisely accurate, but when a gauge is way-off I suspect that the hinged, floating rod is stuck or, less-likely, bent.

If your gauge is one that shows the tank level with a vertical wire carrying an indicator disc on the wire top, often we can, without removing the gauge from the tank, fix a stuck gauge by un-screwing the plastic cover over the floating indicator and then pushing it gently down or lifting it gently up a couple of times to see if it will begin to move freely.

 

Required distance between oil tank fill & vent pipes and a power vent exhaust?

How far does the fill and vent need to be from a power venter On 2022-12-29 by Nick

by InspectApedia Publisher (mod) - clearance distance oil tank vent to power exhaust vent outlet

@Nick,

Thanks that's an interesting question; I have not found a model code that specifies a clearance distance between an oil tank fill/vent pipe and a power vent exhaust from heating equipment.

If as we are forced to guess, your power vent is an exhaust-only system then there's no concern with an oil fume intake - even during oil tank fill-up.

 

Can you fill an oil tank by running a hose through a large building ?

Washington DC commercial building needing oil delivery (C) InspectApedia.com Ali

I purchased a commercial building in an industrial zone in Washington, DC and there is an oil tank behind the building in the rear. The oil tank is behind a brick wall, with a visible exterior fill-pipe visible outside that wall. The rear of the building is approximately 150 ft from the main road.

There are only three ways a driver can access the fill pipe. 1) By driving their vehicle through the driveway on the side of the building in which case they could drive very close to the fill pipe in the rear (they could also run a hose through the driveway into the rear), or by running a hose through the 150 ft building itself from the main road in the front and out the loading dock in the back.

My question is, is it common for a driver to fill an oil tank by running a hose through such a large building itself?

To me it would seem unsafe to run a hose through the building itself but I'm wondering if there is some regulation, code, manual, best practice that I can point to that says that. It would be very helpful if I could find such a regulation/code/manual. I've attached an image. On 2022-12-13 by Ali

by InspectApedia (mod) - can you fill an oil tank by running a hose through a large building

@Ali,

There are few oil companies who use an oil delivery truck with a 150' long hose, although that length is possible.

There's an extra cost to install a large hose from on the oil delivery truck and a lot more trouble to unwind and pull the hose over that distance and to rewind.

So more likely the oil company delivery truck wants to drive close to your oil tank.

Have you called the oil company who delivers to that building to ask how they access tank?

by Ali

@InspectApedia ,

Thank you for the quick response. I don't have a particular oil company in mind at this point, this is more at the proof of concept stage.

I did stumble upon

§ 177.837 Class 3 materials [PDF] Copy at InspectApedia.com at

https://inspectapedia.com/oiltanks/49-CFR-177.837-12-12-2022.pdf

- original source: https://www.ecfr.gov/current/title-49/subtitle-B/chapter-I/subchapter-C/part-177/subpart-B/section-177.837

where it says all the way at the bottom that the person filling the tank needs to be 150 ft or less away from the delivery truck which would seem difficult/impossible given the size of the building unless they went into the back.

Unloading combustible liquids.

For a cargo tank unloading a material meeting the definition for combustible liquid in § 173.150(f) of this subchapter, the qualified person attending the unloading operation must remain within 45.72 meters (150 feet) of the cargo tank and 7.62 meters (25 feet) of the delivery hose and must observe both the cargo tank and the receiving container at least once every five minutes during unloading operations that take more than five minutes to complete.

by InspectApedia (Editor) -

@Ali,

That federal regulation surely does not apply to building heating oil tank filling procedures where it is entirely common for the driver to stand next to the oil fill and vent pipe during filling - as you will see in photographs on this page.

Here is the proper document title

Title 49 - Transportation
Subtitle B - Other Regulations Relating to Transportation
Chapter I - Pipeline and Hazardous Materials Safety Administration, Department of
Transportation
Subchapter C - Hazardous Materials Regulations
Part 177 - Carriage by Public Highway
Subpart B - Loading and Unloading
Authority: 49 U.S.C. 5101-5128; sec. 112 of Pub. L. 103-311, 108 Stat. 1673, 1676 (1994); sec. 32509 of Pub. L. 112-141, 126
Stat. 405, 805 (2012); 49 CFR 1.81 and 1.97.
§ 177.837 Class 3 materials.

 

Where on my buried oil tank will the pipes that I can see above ground connect?

I have a 1000 gallon in ground oil tank and need to do some trenching near it for a gas line (the oil tank will be removed next spring.)

My memory from 40 years ago is that the fill and vent pipes sticking out of the ground are near one end of the tank rather than in the middle.

I can find info online that the tank is likely to be 130" long, but can't find anything about where the inlet would be on the tank - center or near an end. Can you speculate based on your experience, or point me to a specs page that would show the tank details? On 2021-08-04 by George

by inspectapedia.com.moderator - buried oil tank pipe connections can be at either end or in the middle

@George,

Buried oil tank pipe connections can be at either end or in the middle;

Worse, where the fill and vent pipes are brought to the surface are not always even over the tank; for example often they're brought up close to a building so as to be out of the way and less likely to be run over by a mower.

The top of the tank won't be that deep; choices to mark off a safe distance from the tank include

See details and our articles on various methods for locating the tank more-exactly starting at

OIL TANK, BURIED, FINDING

 

Is it ok to install a concrete sidewalk around my oil tank fill/vent pipes?

I have an ingrown oil tank with both a fill pipe & tall air pipe in ground properly separated for years now, since built.

My question they are replacing the concrete walkway on side of my home, can the concrete still surround this pipe or do they have to put something around the pipe? The pipe is solid & intact. On 2021-05-23 by Linda White

by danjoefriedman (mod) - Concrete can be placed around the fill and vent pipes for your buried oil tank

@Linda White,

Concrete can be placed around the fill and vent pipes for your buried oil tank.

Keep in mind that IF the tank is old and is going to need to be replaced soon, it might make sense to have it opened, emptied, cleaned and filled in before the sidewalk goes in just because it'll be easier and a bit less costly.

So you might want it tested for leaks.

Watch out: having pipes of any sort sticking up through a sidewalk is a trip hazard that could both hurt someone and punch a hole in your savings. - Daniel Friedman

...

Continue reading at OIL TANK FILL & VENT PIPING MATERIALS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see OIL FILL & VENT PIPING FAQs - questions and answers posted originally on this page.

Or see these

Recommended Articles

Suggested citation for this web page

OIL TANK FILL & VENT PIPING INSPECTION CHECKLIST at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING OIL, OIL BURNERS, OIL FIRED HEATERS, OIL TANKS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor [Website: /www.house-whisperer.com ] is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-873-8534 or by Email: johncranor@verizon.net
  • Arlene Puentes [Website: www.octoberhome.com ] , an ASHI member and a licensed home inspector in Kingston, NY, and has served on ASHI national committees as well as HVASHI Chapter President. Ms. Puentes can be contacted at ap@octoberhome.com
  • [1] Audels OIL BURNER GUIDE, Installing, Servicing, Repairing [Free online copy] Frank D. Graham, Theo. Audel & Co., New York 1946, 1947, 1955 (out of print, copies occasionally available from antique book dealers and on EBay).
  • [12] Fuel oil safety valves, Webster Fuel Pumps & Valves, 219 Hahn Road Frankfort, Ky. 40601, Tel: (800) 766-1233 Email: czahalka@cctoolinc.com (Curtis Zahalka Sales Mgr/Mkt /Cust Service/Tech Support/Webmaster ) web search 10/12/2011 original source http://www.websterfuelpumps.com/pdffiles/osv1.pdf
  • [13] Webster Service Technicians' Handbook, Webster Fuel Pumps & Valves, 219 Hahn Road Frankfort, Ky. 40601, Tel: (800) 766-1233
  • [16] Tigerloop: oil line de-aerator devices, Westwood Products Inc., 330 William St., PO Box 610, South River, NJ 08882-0610 - (732) 651-7700
  • Dave Ferris - M&S Environmental Systems, Dutchess County, New York. Mr. Ferris was an HVAC expert.

    Personal communication to DJF 1987.

    Remove the firematic or fusible oil supply line valve on return oil-line side - in case of fire if this one closes first the pump continues to run, blows its seal, and sprays oil all over the fire.

    Proper installation is to have a fusible link valve only on the supply side, and to install a check valve on the return line to prevent back-siphonage from the tank.
  • National Association of Oil Heat Service Managers, PO Box 380, Elmwood Park, NJ 07407
  • "Homeowners Guide to Fuel Storage," Agway Energy Products, Verbank, NY, November 1990
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT