Building Inspection, Diagnosis & Repair Info

Photograph of a in-home oil tank - notice the small diameter vent line?Oil Tank Fill & Vent Piping Materials

Oil tank fill & vent piping materials - what types of pipe are permitted?

This heating oil piping article series gives advice and example photos for the installation, inspection, & leak troubleshooting of oil tank fill & vent piping for both buried and above ground oil storage tanks.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Heating Oil Fill & Vent Piping Materials Choices

Approved Oil Tank Piping Materials

Permitted Fill & Vent & Fuel Line Piping Material for Oil Storage Tanks & Oil Burners

Using the Seattle 2015 Mechanical Code Chapter 13 as a model, we can see a summary of permitted fuel oil piping materials in table form with the applicable piping standards listed below:

Table 1302.3 FUEL OIL PIPING

Material
Copper or copper alloy pipe
Copper or copper-alloy tubing (Type K, L, or M) 1
Labeled pipe
Nonmetallic pipe
Steel pipe
Steel tubing

Notes to the table above:

  1. Type M copper which has thinner walls than type K or L, may not be permitted in some jurisdictions.
  2. Notice that the adopted and model mechanical codes do not mention the word "galvanized" nor "iron" - though in popular parlance some installers may refer to steel piping as "black iron" or "galvanized iron" pipe. There is no prohibition nor even use of either of those terms.
  3. The practical distinction between "pipe" and "tubing" is that tubing is flexible and is commonly used in smaller sizes for fuel distribution between an oil storage tank and the oil burner.
  4. Source: 2015 SEATTLE MECHANICAL CODE, CHAPTER 13, FUEL OIL PIPING AND STORAGE [PDF] retrieved 2021/10/03, original source: http://www.seattle.gov/documents/Departments/SDCI/Codes/MechanicalCode/2015SMCChapter13.pdf

Typical Mechanical Code Sources for Fuel Oil (Heating Oil) Piping Materials

Plastic oil tank vent pipe (C) Daniel Friedman Glens Falls NYPhoto: this installer used iron pipe for the fill pipe and plastic for the oil tank vent pipe. Is this allowed? Maybe.

[Click to enlarge any image]

  • Brass pipe (where permitted) joints

    shall be brazed, mechanical, or threaded - IMC 1303.4
  • Brass tubing joints

    shall be brazed or mechanical - IMC 1303.5
  • Copper or copper alloy pipe joints

    shall be brazed, mechanical, threaded, or welded - IMC 1303.6
  • Copper or copper alloy tubing joints

    shall be brazed or mechanical, or flared - IMC 1303.7
  • Joints between different piping materials

    must use approved adapter fittings, dielectric fittings, or brass converter fittings; fittings must be approved for fuel-oil piping systems and must be made tight with appropriate sealants; - IMC 1303.1.1, 1303.3
  • Non-metallic piping,

    permitted in some jurisdictions; connections must be as per manufacturer - IMC 1303.8
  • Steel pipe joints

    are threaded or welded; note that the model codes don't mention a distinction between black steel pipe and galvanized steel pipe for heating oil applications - IMC 1303.89
  • Steel tubing joints

    shall be mechanical or welded - IMC 1303.10

Not-Permitted Oil Tank Piping Materials

  • Cast iron fittings

    shall not be used - IMC 1303.1

 

Reader Comment: ok to use galvanized fittings on oil tank piping?

Galvanized fittings should not be used on oil pipe from tank. Which is contrary to your recommendations. - John, 2021/09/30

This comment and reply were posted originally

at OIL FILL & VENT PIPING FAQs

Moderator reply: steel oil tank piping (black or galvanized "iron") and in some cases plastic (non-metallic) piping for fill and vent pipes

@John,

Thank you for the comment as your opinion contradicts typical oil tank piping codes on types of oil tank piping permitted and so led us to double-check our research on this question

Oil tanks supplying oil burners used in residential and commercial heating applications are fueled by above-ground or buried oil storage tanks whose fill and vent piping is usually steel (referred to also as black iron pipe or galvanized iron pipe); in some jurisdictions non-metallic piping is permitted, though code details will specify that any joints or connections must be made using the manufacturer's instructions.

Here is a typical oil tank piping code excerpt on the types of piping permitted at oil tanks - focusing on the fill and vent pipe where either black iron or galvanized iron are permitted along with brass and copper or steel.

Where flexible copper is used, of course, is not for the fill and vent pipe to the oil storage tank but for piping fuel between the oil storage tank and the oil burner .

Adding a few details on oil piping in Connecticut using Norwalk's code as an example

47-22 Connections and unions.

All connections shall be made perfectly tight with well-fitted joints. Unions shall be used as burners to facilitate removal. All unions, shall be of an approved type, having conically faced joint, and obviating the use of packing and gaskets.

ยง 47-30 Type of pipe;

brass union required; material on pipe joints; cutoff in steam installations.

A.

All pipes used in fuel-oil heating installations shall be of standard, full-weight brass, copper, galvanized iron or steel, with suitable brass or galvanized malleable iron or steel fittings. No rubber or other packages shall be used.

If unions are used, at least one face must be of brass with close-fitting conical joints. Litharge and glycerin, shellac or other suitable material shall be used on pipe joints. Such piping shall run under the cellar wherever possible and shall be protected from injury.

using the 2015 UMC as an example, Chapter 13, Section 1303, Joints & Connections:

1303.1 Approval:

Joints and connections shall be approved and of a type approved for fuel-oil piping systems. Threaded joints and connections shall be made tight with suitable lubricant or pipe compound.

Unions requiring gaskets or packings, right or left couplings, and sweat fittings employing a solder having a melting point of less than 1,000 F (538 degC) shall not be used on oil lines. Cast iron fittings shall not be used. Joints and connections shall be tight for the pressure required by the test.

On copper oil piping lines, flare unions like the brass 3/8" flare nipple union... are common on oil piping (not underground).

---

So where might John have heard advice on avoiding use of galvanized iron piping with oil fuels?

In automotive applications, not heating oil burner applications, one should not use galvanized iron piping because the additives in diesel fuel can dissolve components of the galvanized coating on pipes, sending the dissolved constituents into the automotive engine where it may foul the engine's fuel system.

In sum,

  • It is proper to use black or galvanized iron pipes for the oil storage tank fill and vent pipes. Non-metallic piping is permitted in some jurisdictions.
  • Do not use galvanized iron pipes in automotive engine fuel supply systems.

John, if you have another authoritative source that gives contrary information please do share it as that would be most helpful.

On 2021-10-03 by inspectapedia.com.moderator - use black or galvanized iron pipes for the oil storage tank fill and vent pipes

@John,

Thank you for the comment as your opinion contradicts typical oil tank piping codes on types of oil tank piping permitted and so led us to double-check our research on this question.

Please see your question and our complete response in the article above on this page.

On 2021-09-30 by John

Galvanized fittings should not be used on oil pipe from tank. Which is contrary to your recommendations.


...

Continue reading at OIL TANK FILL & VENT PIPING SIZE REQUIREMENTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

OIL TANK FILL & VENT PIPING MATERIALS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING OIL, OIL BURNERS, OIL FIRED HEATERS, OIL TANKS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT