Oil Tank Fill & Vent Piping Elbows & Swing Joints
Oil tank fill & vent piping bends or elbows: what are the limitations?
This heating oil piping article series gives advice and example photos for the installation, inspection, & leak troubleshooting of oil tank fill & vent piping for both buried and above ground oil storage tanks.
The page top photo shows a basic oil fill and vent pipe installation outdoor termination at which there is a simple 90 degree elbow to raise both fill and vent pipe upwards.
At this older installation, the oil delivery driver is listening to the vent pipe to determine when the oil tank is filled: a vent alarm was missing.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Above: inside the same building as shown at page top, we see a very simple and effective piping arrangement: both fill and vent pipes rise vertically from the oil storage tank and make a single 90 degree bend to extend outside through the building's foundation wall.
Below in our photograph, an oil fill pipe at a property in Dunedin, New Zealand (South Island) doubles back on itself to give the oil delivery driver a fighting chance at filling an oil tank that is uphill from the point of fill.
To me [DF] this is a rather ugly installation that seems likely to lead to a spill.
We have not found an explicit limit on elbows on oil tank fill or vent piping, though one would want to keep the number to a minimum.
Using the ICC as adopted by New York City as the 2008 NYC Mechanical Code, an example we have this:
Mechanical Code 1305.6 [Oil Storage Tank] Fill piping.
Fill piping shall comply with the requirements of Sections 1305.6.1 through 1305.6.6.
1305.6.1 Size.
Fill piping shall be a minimum of 2 inches (51 mm) in diameter or 3 inches (76 mm) for No. 6 fuel oil.
305.6.2 Termination location.
A fill pipe shall terminate outside of a building at or above grade at a point least 2 feet (610 mm) from any building opening and 5 feet (1524 mm) away from any subway grating at the same or lower level.
A fill pipe shall terminate in a manner designed to minimize spilling when the filling hose is disconnected.
Where No. 6 fuel oil is used, the fill pipe terminal shall be within 3 feet (914 mm) of the curb unless otherwise required by the Department of Transportation or the Transit Authority.
If facilities exist for an oil delivery truck to drive onto the premises, the fuel-oil terminal may be located elsewhere other than the curb.
1305.6.3 Separate fill piping.
Each storage tank shall be provided with a separate fill pipe, except that where a battery of tanks containing the same grade of oil is installed, a common fill and header pipe may be installed.
Also see NFPA 31 that governs oil tank installation & piping that has similar language:
From NFPA31 as adopted by Warren Co VA cites the fittings and tubing requirements for oil fill & vent pipes:
NFPA 31 section 8.2.5
Pipe shall be connected with standard fittings and tubing with fittings of listed types.
My heating oil tank is in my basement. my gauge is not accurate. I attempted to measure my oil level from the outside filler pipe.
I bought a piece of flexible PVC pipe barely half inch diameter and marked off every 6 inches on the pipe. My outdoor filer pipe goes through my basement wall about a foot then a slight bend downward into the top of the oil tank.
my problem is I can't get the pipe any further than about 12 inches. It feels like there is an obstruction right before the pipe goes into the tank..[275 gallon].
Is there something in a filler pipe like what would be in a bathtub drain to keep debris from getting into your tank[ example; maybe kids dropping a stone or something into your fill pipe?
I can not get through any more than a foot before I hit something that is stopping it. BTW: tank is in full use. Oil was dropped off this week]... thanks for any input.
Before the Fill pipe goes into my tank, it screws into a "90' and and another small pipe comes out the other end of the 90 then into the tank.
So I'm hitting the pipe threads on the "other end [inside the pipe]." Also, my tank is in a dark area of my basement so I never noticed that there is another threaded access port on the far end I assume giving you a choice of connecting your fill pipe to either side.
There is a square cap covering that port so with a Pipe wrench I should be able to check oil lever from there pretty easy.
My tank is 275 gallon, dimensions are: 60" long/ 44" high[ on legs but only measured the tank], and 23-24" wide.
Can u tell me how many inches equals how many gallons ? - On 2013-03-09 by Tony -
Even if you could get a flexible PVC tube down into the oil tank (which can be done on some piping arrangements) without a procedure for keeping the tube dead straight you would not get an accurate reading.
About oil tank gauge accuracy, because of the shape of the tank the gauge will generally never be able to be precisely accurate except at 3 points:
Full
Half Full
Empty (Even "empty" may leave a bit of oil in the tank).
I'd consider the gauge more as an indicator of when to ask for an oil delivery if you're not on automatic delivery (which I prefer). If the gauge is at 1/4 tank or below you'd best give the oil company a call.
For applications where a more accurate oil tank gauge is really needed there are some after-market devices that use electronics and are more consistent.
...
Definition: Swing joints on fuel piping are a technique for providing flexibility at various points in an underground piping system by making up joints composed of steel 90-degree elbows and nipples. (PEI 2025)
Requirement: swing joints on residential oil tank fill and vent piping are normally not required but there may be exceptions, as we'll explain below.
Details:
Swing joints in piping systems (for other readers) are a combination of pipe elbows that allow piping to tolerate movement, such in underground piping systems, or where they are needed to align pipes that otherwise don't line-up.
Bottom line: swing joints are not a specific requirement in most oil tank installations.
On occasion we've seen swing joints used to align an existing oil tank fill and vent pipe with the installation of a new or replacement oil storage tank. The installer may find it easier to use a combination of pipe elbows and nipples to join oil fill or vent lines than to move either the oil tank or existing fill and vent pipes that may have already been installed through the building wall.
Really? Well yes, but at OIL TANK REPLACEMENT PROCEDURE you'll see that the installer made a neat clean oil tank installation by shifting the new oil tank so that its fill and vent pipe openings aligned neatly with the existing fill and vent pipes through the building wall.
However if a residential oil tank is installed in an earthquake zone then your state, provincial or local codes might recommend swing joints or other flexible piping joints as well as extra measures to secure the oil tank against falling-over.
The Unisource FireGuard flexible connector shown below is described by the manufacturer as extremely flexible and easy to install, and is used in both aboveground or underground installations where accommodation of movement or alignment problems are a concern.

Some industrial fuel piping installations will require swing joints or an equivalent flexible connector on fuel piping.
For industrial piping installations that might need swing joints see
...
Continue reading at OIL TANK FILL / VENT PIPE LEAK REPAIRS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
OIL TANK FILL & VENT PIPING BENDS & ELBOWS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.