Building Inspection, Diagnosis & Repair Info

furnace fan limit switch control switch (C) Daniel FriedmanFAQs: Furnace Blower Fan Cycles On / Off After Call for Heat

FAQs about why a furnace turns on after call for heat has ended:

These questions & answers help diagnose & fix a heating furnace blower fan that cycles on and off after the call for heat has stopped.

For safety this furnace fan cycling problem should be diagnosed and repaired promptly. This article is part of a series of heating furnace blower fan diagnosis & repair procedures given free at InspectApedia.com. Content suggestions are always welcomed.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Why the Blower Fan Keeps Cycling On/Off After Call for Heat Has Stopped

These questions & answers about furnace blower fans that cycle (or should but don't) after the thermostat is satisfied were posted originally

at FURNACE FAN CYCLES AFTER HEAT - be sure to see that diagnosis and repair article.

Also see our index to all fan limit control switch questions & answers found at FAN LIMIT SWITCH FAQs

Sometimes the furnace blower seems to stick "ON"

I have a electric furnace, it works fine until I put the thermostat in the manual mode to run constantly.

Then it will cycle on off on off on off but doesnt do it all the time. In the auto thermostat mode it runs fine, heats and cool the house fine.

From time to time the blower will stick in the run mode and not shut off for short periods. not often. Please reply to email address rkiddle59@aol.com
Thanks On 2021-01-22 by Jerry Riddle

by (mod) - furnace fan shuts off sometimes when in manual ON mode at the thermostat

Jerry

Let's start with the diagnostics at

FURNACE FAN CYCLES AFTER HEAT

or consider that your furnace plenum is overheating and the unit is being turned off at the HIGH LIMIT.

Watch the fan limit control switch dial turn to see if, during operation of the furnace, it's rotating to the HI LIMIT position.

or if you are running the fan itself in ON mode at the thermostat, the opposite could be happening: if the furnace heating plenum gets too cool then the fan will stop so as to avoid blowing cold air on occupanrs; in this case the blower is getting ahead of the burner; check for a dirty heat exchanger.

Why does blower fan run immediately and run for a short time?

When calling for heat, why does the blower fan come on first and run for 90 seconds? On 2020-03-28 by AL

by (mod) -

That sounds like a wiring problem or control board error.

After Carrier furnace and gas shut off, fan recycles on & off

Carrier furnace and control board (C) InspectApedia.com Den

Carrier Furnace & its control board [photo above]

I have a Carrier Day Night furnace unit.

After it heat and gas shuts off fan will recycle a few times.

New Thermostat, Clean filter, blower motor and housing. Tested the two limit switches one in heat exchanger about 3 in long one by downdraft reset type with button Both are O.K.
Bypassed limit switches and it does same thing?

What Else could be causing this? On 2019-12-14 by Den -

by (mod) - usually due to poor heat transfer, reaching the fan LIMIT setting

CARRIER 313680-751 Inducer Control Board  at InspectApedia.comDen

Even though your filter and blower motor are said to be "clean" there are a couple of things I'd check:

1. look VERY closely at the blades on that squirrel cage fan in the air handler unit. The curvature of the blades isn't much, so if there's dirt on the blades air flow can be reduced enough to slow the cooling down of the heat exchanger at the end of an on cycle.

2. check that there are no airflow obstructions in the return or supply duct systems.

3. I'd like details (brand, model, photos) of the two limit switches and model number of your furnace; I'm not familiar with heating systems that use multiple limit controls.

Is your furnace using a separate inducer control such as the CARRIER 313680-751 Inducer Control Board shown here?

We list several causes of fan cycling at the end of a heat-on cycle
at
FURNACE FAN CYCLES AFTER HEAT

Please take a look at those diagnostics and then let me know what questions remain.

Followup by Den

Thank You Dan For your help

Carrier Product#394JAZ048065AAFA

Mod#394JAZ048065

s/n#2890A0079

Unit very clean. Took apart blower unit cleaned. Dow draft and inlets clean Unit works perfectly.
Nice and quit. Just this on and off problem. And does not do it on the A/C side.

by (mod) -

Carrier furnace control board (C) InspectApedia.com Den

Thanks Den I'll see if I can find out more or find the IO manual for this Carrier unit. Indeed even in your photos it looks clean.

Usually the post-heating fan cycling problem is due to a heat retention problem that turns the fan back on; the other category of causes might be a bad sensor or control board or relay.

If there is a fan limit control with a temperature dial that you can watch at the end of a heat-on cycle that may give us some diagnostic data. For example if you see the dial temperature drop to a lower number and then rise after the fan stops we figure it's a residual heat issue. That's what leads me to question air flow through such a system.

Has your heating service tech expressed a view?

Den

If the main burner is shutting off quickly after start-up, check the pilot assembly as it may need replacent.

Otherwise I'd be looking for the easy snafu's first, such as a dirty air filter, blocked return air, or dirty heat exchanger.

This Carrrier, BDP, Bryant Day & Night & Payne DAY-NIGHT GAS FURNACE 394GAD 394 GAD Series MANUAL [PDF] may be of help.

CARRIER AIR CONDITIONERS BOILERS FURNACES AGE MANUALS has manuals for Carrier furnaces.

Readers also may want this

ICP International Comfort Products CONDENSING GAS FURNACE SERVICE MANUAL Model N9MSB (B Series) [PDF] (2012)

Gas furnace turns off before coming up to full temperature

combination furnace control Honeywell L4064B with cover onMy gas fired furnace will kick on but not come up to full temp before it turns off. When I turn off thermostat and back on it kicks on and does reach temp and stay there until the next day. The temp never goes below the evening lowered temp when i get up the next morning.

The thermostat is new & I replaced a relay and they are all working. This only occurs in 1 of my zones (Dec 23, 2014) brent hewitt

Reply:

Brent

The limit switch turns off a furnace if the plenum temperature is too high - risking damage to the equipment.

Look for a dirty or blocked air filter.

brent lewis said:

i replaced filter & appears to be working better, getting cold the next few days, so that will be a good test

 

Furnace blower blower never shuts off

My furnace burner goes on and reaches the heat setting then turns off but the blower never shuts off it runs continuously and i replaced the thermostat but made no difference (Jan 4, 2015) Anonymous

Reply:

Anon:

In the article list at CONTINUE READING you might want to see FAN LIMIT SWITCH TROUBLESHOOTING for some diagnostics. It could be something as simple as the fan switch set to ON rather than AUTO - there are swtiches on many thermostats and on some limit switches. Another cause can be FAN ON wires from a thermostat that are incorrectly wired or are shorted together.

 

OK to set the fan limit switch FAN OFF down 5 degrees to fix extra fan-on cycling?

I'm setting the fan limit switch FAN OFF down 5 degrees seemed to fix extra fan-on cycling - is this OK?

I notice that the fan on the heater came on briefly after the heating cycle concluded. I checked this article and decided to adjust the fan switch shut off temperature from 90 degrees to 85 degrees. So far the problem of an additional, short running fan cycle has not reoccurred. I've not read where this remedy is recommended. - Larry K 1/8/12

R/M said: This is a solution. (Jan 4, 2015)

Reply:

Thanks for the comment Larry. Indeed in the article above we discuss the concern of blower fan cycling on and off one or more extra times at the end of a heating cycle. If that small shut-off temperature fixed the problem that's a great tip for other readers.

Just be sure that none of the more problematic reasons for fan cycling are the cause (as we describe above) and you should be ok

 

Trouble setting or repairing a Camstat Time Delay Blower Control Model BC-7070 - set the TIME OFF dial

Fan limit switch BC-7070-A/M (C) InspectApedia.comI am having a similar issue as several of these topics. The furnace will kick off then the blower will kick off shortly after. Then the blower will kick on briefly for a few seconds then off. It will do this repeatedly for 3-5 times. I did not see a similar switch in my furnace as what your pictures show.

I did take a pic of the Limit Switch, which is a BC-7070 AM. It has a Time On and Time Off adjustable dial (4 minutes). Should I increase the Time On dial so the blower runs longer after the furnace kicks off? It seems like this may blow the rest of the heat out which would prevent it from having to kick on/off. (Jan 7, 2015) Chris

Reply:

Chris

If this is a *change* in how the furnace operates then we want to diagnose and fix something, not just change a setting.

Often when a blower turns on and then off again then on again at the end of a furnace burner-on cycle it suggests that the residual heat in the heat exchanger is heating up air in the plenum enough to turn the blower fan back on again.

This might occur if the fan is not moving enough air (dirty air filter, clogged heat exchanger, obstructed air flow) or if the on-cycle is not long enough. If the air filters are not dirty and the ductwork not clogged, check also the blower fan itself for dirt or debris: a small amount of dirt on a blower fan - the squirrell cage type - can dramatically cut the air flow rate of the fan.

if none of those problems are present I'd try setting up the ON time to 5-6 minutes.

keep us posted as what you find will help other readers

Chris said

Unfortunately I'm not sure if this is a "change" or not. It's really cold out now which is making the furnace run more which is who I've noticed this issue recently.

I did just buy this house a few months ago too which is another reason why I'm not sure if it's change. I have been good about changing the filters and will check for debris and dirt tonight. I have been reading more on Timer Delays. Isn't the TIME ON delay for when the blower kicks on after the furnace has kicked on? From what I've seen, I think I actually may want to adjust the TIME OFF delay to increase the time before the blower kicks off. Is this correct or am I mistaken? Once I resolve this issue I will be sure to update. Thanks!

(mod) said:

Chris, we've posted some PDF's that describe the Honeywell Fan Limit Switch installation and operation - linked in the References to (for example) the FAN LIMIT CONTROL SETTINGS article found in ARTICLE INDEX . But I'm not sure we cover your switch.

Your switch is a Camstat Time Delay Blower Control Model BC-7070 sold by various suppliers including A-1 Components Corp. The ON and OFF times can be adjusted between 0-240 seconds. The ON is the time delay before the fan starts after a call for heat. And as you suggest, the OFF time is the delay in turning off the fan AFTER the call for heat is satisfied.

We'll upload and link to a PDF with specifications for this control as well as other documents we can find when we move your comments into the article above. [ASAP]

Can you send me photos of your limit switch - use the email at our CONTACT US link found at page top or bottom and I'll research further.

Chris said:

I've done some digging around and haven't found anything that covers my switch really. I have had a hard time even finding any instructions for this switch on the web. You're correct I have the one made by A-1 components. I am also emailing you a picture of the switch now. Thanks!

(mod) said:

Chris by Email I've sent you the two PDFs of product info we have located so far.

Keep me posted

Daniel

Subsequent reply from Chris [by private email]

Thanks a lot for sending me these two documents Daniel. If I were to time when the blower fan kicks on and off and it doesn't correspond to the Delay switches at all, is it safe to say the limit switch is going out? There does appear to be quite a bit of dust in my squirrel cage. I was hesitant to change anything last night as it was the coldest day of the year so far

Moderator replied:

Chris I don't know this particular brand very well but I suspect you're right.

Do clean the fan if you can - I've measured airflow and seen a very big drop in air movement if the blades are dirty. They are just shallow-concave so it doesn't take much dust to flatten them thus reducing airflow. I'd like to see photos of the fan before and after cleaning.

Chris said

Daniel-
I increased the Time Off dial and it fixed the problem. The extra time allows for the furnace to cool down enough that the blower doesn't continue to kick on. Thanks for the advice.

Reply:

Thanks for the feedback - it will assist others.

It's interesting that the approach taken by the manufacturer of your control relies on a simple timer setting. Other limit controls actually monitor the plenum temperature and turn the fan on or off accordingly. Your switch design is perhaps rugged, simple and economical but appears to eschew that more sophisticated approach.

 

What sets the time limits for the blower ON-OFF when a 7070 blower Camstdat control relay is in use?

Coleman Intertherm electric furnace limit switch snap switch control at InspectApedial.com and at hvacpartsstorecom and other vendorsDoes anyone know where the timer on/off on this relay should be for the 7070 blower control relay ? On 2019-01-15 by Jay - see photo above - Ed.

by (mod) - Camstat type fan limit control swith adjustment

Jay,

I don't know everything that specific control but I can tell you it's a Camstat type fan limit control switch whose two adjustable dials allow you to set the blower on and blower off time limits between 0 and 240 seconds.

Here is an image of the Coleman Intertherm 140 L140-30F Limit Switch Electric Furnace 7945-3281 7945-328 avaliable from hvacpartsstore.com and from many other vendors.

I can't say what are the correct settings for your (uknown) heating system, but in general what you want is the following:

At the end of a heat-on cycle when the thermostat is satisfies and stops calling for heat, you want the fan to run long enough to drop the heat exchanger temperature down to warm - not hot - (subjectively determined) to avoid cracking the heat exchanger.

My GUESS is that's 100 degF or lower.

So there is probably NOT a single "right" number or setting on the control in your photo as the additional fan-on time needed to cool down the heat exchanger to a safe level will vary by furnace brand, model, fuel (yours is gas), air-flow rate, return air temperature, BTHh rating etc.

Note also that there are no numbers on the dial, just + and - but the range is 0-240 seconds.

So a subjective setting is possible as I've described, or just leave it at 3/4 of maximum where it's shown.

At FAN LIMIT SWITCH https://inspectapedia.com/heat/Fan_Limit_Switch_Guide.php

in our description of "Cam-stat® type Fan Limit Control Switch" you'll find a link to the manual and wiring diagram for your control.

How to fix fan cycling on and off at end of heating cycle - non-adjustable limit switch

I have a similar issue, except I do not have a adjustable limit switch. After a heat cycle completes the fan stops and than it kicks in for a 1 second and than off again. At first it happened occasionally but now its every time. I checked filter and looked for clogs. My furnace is Bryant 394G it does not look like there is any way to adjust the fan timing. It has a time delay circuit that I think has preset time on it. - Mike

Reply:

Mike:

Make *certain* that there is good air flow through the heating plenum by replacing any air filters, checking for ductwork obstructions, and assuring that the squirrel cage blower fan is clean and working.

If there is good air flow and you've got a non-adjustable limit switch my next step would be to replace the switch.

There are on some non-adjustable limit switches a sealed snap switch that responds to temperature. If one of those fails, in theory it could be replaced but it's safer to just replace the fan limit switch assembly.

 

Furnace fan cycles during heat and one more time after burner turns off

we installed a new motor to an older gas furnace. so the fan works now. however, it kicks on and off while the heat is on and after the heat has reached its temp. and kicks of the fan kicks off. then comes back on one last time stays on a min then goes back off. could you tell me what this might be. (Mar 4, 2015) jeff

Reply: check the fan speed and fan cleanliness

Jeff,

I'd start by asking if the new motor changed the fan speed. If not d look for a dirty air filter or dirty blower fan assembly that are,slowing air through the heat exchanger and plenum.

 

Thermo Pride Furnace OC5, humming from fan relay

(Mar 14, 2015) Maxine Frese said:
We have a Thermo Pride oil furnace model OC5, direct drive. We replace the blower motor. Also, vacuumed the flue and clean out ports. We were very careful to label all the wiring on the motor when it was removed, so we know the wiring was plugged in correctly. We turned the power on and ran the furnace which started up fine.

The furnace heated up and shut down correctly, the fan came on and shut off correctly. We thought everything was fixed, but then we heard a humming sound coming from the fan center relay area. Now, we never really noticed if the humming was there before we replaced the motor. It almost seem like there are contact stuck closed in the relay. We tapped on the relay but this didn't make a difference. Any thoughts on what the humming might be?

Reply:

CHeck for a bad start / run capacitor on the fan motor or for a bad relay.

 

Furnace blower fan runs by itself during summer

I have a 20+ year old gas furnace in the attic which is on top of 2nd floor. It works fine in the winter. In the summer, I keep my thermostate to "OFF" (neither Heat nor Cool) most of the time.

On a hot summer day, the blower fan in the furnace turns on (no heating or cooling, just the fan), even though thermostat is in OFF position. What adjustment is needed so that blower fan will stop running automatically in summer ?
Thanks. PD (May 26, 2015) P Dave


I have the same issue as P Dave, sort of. I have a 20-year-old oil-fired hot water system in the basement with forced air heat and air conditioning working off it. In the attic above the 2nd floor, there is another forced air system working off hot water pipes from the basement boiler (and a second air conditioning unit).

The blower in the attic keeps going on every few minutes, even though the thermostat is switched to OFF. The only way to stop it is to turn off the power switch on the attic unit -- but then I can't use the air conditioning. I'd like to know what I'm dealing with before I call for service. (May 28, 2015) jpmorris55

Reply:

It would be odd but not impossible for a plenum to get hot enough to turn on a blower fan even when the burner is off, but I'd look first for a loose wire or bad control board or for a thermostat FAN ON switch that's shorting-on.

 

Fan motor surges at end of a cycle

My HVAC fan motor lunges at the end of a cycle (Dec 14, 2015) R jolliff

Reply:

RJ

If you mean the fan is cycling on and off at the end of the heating cycle, please review the suggestions in the article above and let me know if questions remain.

If you mean the motor speeds-up, I suspect a control board or wiring failure.

 

Rheem furnace with ECM blower, fan set to manual ON -but blower stops at start of call for heat

I have a Rheem furnace with ecm blower motor. New system. I have set the fan to on during the winter to circulate air ( ceiling heat vents in house) to get a more even heat in the house. Also, to avoid the stop/start of the blower motor.

The blower stop when the thermostat calls for heat and then comes back on after about 20 seconds. When the call for heat stops, system shuts down completely, and then the blower starts up again. Should the blower be stopping and starting when FAN is to ON? (Dec 17, 2015) magibson53

Reply:

I suspect that your control thinks it's preventing blowing cold air into the occupied space. I don't know how to fix this system but I suspect it can be corrected by control board settings; I'd call my HVAC service manager to discuss the problem and then ask for help from an experienced Rheem furnace service technician.

magibson53 said:

Installer said "On startup that how it's supposed to work. Needs to run tests before starting burners and kicking on the blower". Doesn't seem right to me.

 

My furnace has no limit switch

I was told my furnace has no limit switch (They say it's the circuit board) I don't know if I'm being told the truth. I never had this problem of of on and off during cool down until they put in new gas valve that did not fix the furnace. When they finally replaced thermostat (that finally made the furnace work and cycle right) this new problem started with this immediately.

They took $727.00 from me and now I have this problem. So stressed out. I have Comforter Maker RPJ II Model # GNJ075N12C1, Serial # L962216625.

All everybody say's horrible furnace, I bought this home in 2012 and this is what I have. But I didn't need new gas valve, now I'm being told I need circuit board and God knows what else.

I'm being robbed, I can't afford a new furnace. Does this furnace have a limit switch?

Again this was not the original problem and it never existed before this Hgt. & cooling place came here. They switched blower speed to high for what reason I don't know, the noise was horrible so second guy turned it back down.

They also slammed the side of burners with pipe wrench (his way of cleaning pilot) 3 visits and I'm now stuck with this on/off back and forth in cooling mode. I can't sleep, this wakes me up. Verge of nervous breakdown. Can't trust another furnace person. Please help and give me some insight. (Dec 21, 2015) Linda

Reply:

Linda at the Continue Reading link you'll see more images of Limit Switches so you can see what they look like. Even with a printed circuit board there must be a temperature sensor monitoring temperature in your furnace.

Every heating furnace has to have limit controls, otherwise the system would be unsafe and could not operate; but it is true that not all models use a field-adjustable switch. Some use a fixed temperature range sensor control.

If you are not confident about what a service tech is telling you it may make sense to ask for a second opinion from an independent company.

Also be sure that your service tech is familiar with your particular equipment - that can reduce the chances of shotgunning approaches to repair: try replacing suspect parts. To be fair, often it's cheaper to replace a part than to do more extensive diagnostics - it depends.

Linda said:
This is kind of circuit board mine has (Note: this is the replacement for this model No.) mouse over picture enlarges, Please, can you tell me where the temperature sensor on it is.

Can this alone be repaired without the whole thing being replaced. You can see what it can be purchased for not only here but locally, hgt. service wants over $400.00. I'm just wondering if the place that ripped me off could have messed with this or messed it up switching blower speeds.All your help is appreciated.

It is the inducer fan not blower fan going up and down in cool down. I flipped the fan on thermostat from auto to on, and it was this fan going on/off. I beginning to wonder if the thermostat that put on wasn't a used defective one. All this is very confusing for the fact this was never a part of original problem.

Reply: problem was in the thermostat

Linda, By disconnecting the thermostat wires and joining them at one end then the other it's easy to determine if the wires are shorted or broken.

Reader follow-up:

It was the Thermostat that rip off hgt. & cooling place put in. No doubt they knew it was defective trying to then sell me a circuit board I didn't need.

I bought a new thermostat and had a friend put it in, has NOT made inducer fan go back on and off once during cool down. Normal thermo's heat one degree above what you set temp at, theirs never did. Fan probably kept coming back on and off because of it. Infuriating.

Reply:

Linda, Do you think perhaps the thermostat wa2miswired or a switch misplaced?

 

Blower runs, blowing cool air for 10 minutes after burner is off

My problem is that after the burner is off (the thermostat is satisfied), the blower keeps running for over 10 minutes blowing cool air. It is like the heater is on for some time with hot air and then the air conditioner is on for some time after the heater.

It not only waste energy, but also don't make us feel comfortable. Does anyone know what is wrong and what we could do? Thanks! Wish everyone a happy New Year! (Dec 30, 2015) Jay

Reply:

Jay

Take a look at the fan limit control in the blower assembly: make note of what it does after the burner shuts off; if the plenum is very hot the blower will keep running until it cools down. Start by checking for a dirty air filter, inadequate return air, crimped ductwork.

Reader follow-up:

Thanks (mod) for your response and suggestion!

Actually I noticed just now that when I set a temperature, it started to heat with the blower on. However, when the temperature is satisfied, the blower didn't stop. Instead, it blows cold air after the burner is off and starts to blow hot air after a while and this cycle continues.

We just changed the air filter and also the limit control. If we lower the temperature (e.g., 2 degrees lower) setting, the blower will stop in a minute or two.

Reply:

Usually the blower won't turn on until the plenum is warm enough, and the blower continues after the burner shuts off until the plenum has cooled down - to avoid damage to the heat exchanger as well as for efficiency. It shouldn't continue to blow cool air.

Watching the dial on the limit switch might tell you if the switch is working normally and at what plenum temperatures it thinks it's responding. If the switch looks good I suspect a relay or control problem at the furnace.

It's easy to foul up a limit switch when changing its settings as if you don't handle it with care its spring can be bent. That'd leave it out of calibration. And maybe not so safe. It's also easy to mis-wire a thermostat or to mis-adjust its external and internal switches such as a heat anticipator.

Jay said:
Hi (mod) , Thanks again!

How long do you think is normal for the blower to continue running after the blower shuts off?

Is there a way to adjust the limit switch to control its responding time? Or maybe the new limit switch is accidentally out of calibration when installed so it is not functioning the right way? So we need another new limit switch?
Wish you a Happy New Year!

Follow up: Finally we asked for help from a professional guy. He replaced the thermostat. It works normally now.

Thanks (mod) for your comments and kind suggestion.

He explained to me about the difference between the old and new thermostats, but I don't understand completely.

He said the old thermostat is not for gas heater (if I understand correctly). Hopefully this will help someone later with similar problems.

Reply;

Thanks so much for the feed-back, Jay, that'll help other readers.

Most thermostats work equally well for gas or oil fired heating boilers, but pehaps your service tech saw something we don't know about. The defect that would permit a thermostat to keep a blower ON when the thermostat is satisfied on a call for heat would be a a FAN ON switch set to ON or perhaps internal damage to that switch.

 

Husband wired around the limit switch - do we need to change it

Hi our furnace wasn't blowing hot air, my husband thinks it a limit switch because some of the wires were loose and when he pushed on them the air turned hot again but only for a bit.

So he replaced the wires and now we have heat.

The only thing I am concerned about now is when the furnace kicks on, you can hear the blower but it takes a good minute for the air to come out, is this normal?

Do we still need to change the limit switch? Please and thank you (Feb 10, 2016) Nicole

Reply:

Nicole

If the blower is running but you have no heat the furnace itself is not heating. It sounds as if you found a loose wire.

Taking a minute for air to be felt at a supply register is a little bit long; I'd look for a damaged or loose fan assembly.

Nicole said:

Thank you so much! Do you think there is any concern for carbon monoxide problems with these issues?

Reply:

No Nicole, if the heat exchanger is not damaged (not leaky) fan cycling after heat is not unsafe.

However IF a limit switch is not set properly or is damaged and that allows the heat exchanger to overheat (burner runs but fan does not, for example) then the heat exchanger can crack and leak and thus become unsafe

 

Induction blower causing blower cycling ?

My intertherm mobile home furnace has an induction blower. could this have an effect on fan blower cycling after the stat is satisfied on the heat cycle? 2016/03/21 larryinmich

Reply:

Larry I'm not sure what you're describing. If you mean that your furnace uses a draft inducer fan to vent the furnace oil or gas burner, that might indeed be drawing room air through the heat exchanger after the burner cut off.

But that would cool DOWN the heat exchanger and plenum faster rather than more slowly, so it should reduce rather than increase the extra air-circulating blower-fan cycling on and off after the burner has turned off.

I'd start by checking the suggestions in the article FURNACE FAN CYCLES AFTER HEAT. Do keep me posted a what you find will help other readers.


...

Continue reading at FURNACE FAN CYCLES AFTER HEAT or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see FURNACE FAN CYCLES AFTER HEAT FAQs-2 - more-recent Q&A about diagnosing a blower fan that cycles on after heating has stopped

Or see these

Recommended Articles

Suggested citation for this web page

FURNACE FAN CYCLES AFTER HEAT-FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING FURNACES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT